1 2 3 4 5 6 7 8 9 10 12 14 16 1820 GFL Series - 1 Pole+N, B Trip, 10 mA 10kA UL489 Listed Branch Circuit Breaker with Equipment Ground Fault Protection (RCBO) The GFL Series range is a combined Branch Circuit Breaker and Equipment Ground Fault Protector, featuring dual pole switching (live and neutral disconnect) and designed to provide protection against short circuits, overloads, AC ground faults (residual current faults) as well as pulsating DC ground faults. C.B. W/EQ.GFP E483494 Ordering Information Rated Type/ Rated Current Cat. No. Voltage 5.0A GFL2B050102 240V AC 6.0A GFL2B060102 240V AC GFL Series RCBO 8.0A GFL2B080102 240V AC Overload Trip Curves Characteristics B , C, D 10A GFL2B100102 240V AC 7200 3600 12A GFL2B120102 240V AC 2400 1200 13A GFL2B130102 240V AC 600 480 360 240 15A GFL2B150102 240V AC 120 16A GFL2B160102 240V AC 60 40 20A GFL2B200102 240V AC 20 10 25A GFL2B250102 240V AC 5 1 0.5 Technical Specification Number of Poles 1+N B C D Voltage Rating (maximum) 240V AC 0.1 Ground Fault Sensitivity Level 10 mA 0.05 Rated Short Circuit Interrupt Capacity 10 kA Rated Frequency 50/60Hz 0.01 Trip Characteristic B 1.05 1.35 2 2 Cable Size & Tightening Torque Stranded Wire: 16 - 3 AWG (1.5 mm - 25 mm ) 17.5 lb-in (2.0 Nm) Rated current multiple x I n 2 2 16 - 10 AWG (1.5 mm - 5.5 mm ) 17.5 lb-in (2.0 Nm) Solid Wire: 2 2 18 - 16 AWG (1 mm - 1.5 mm ) 25 lb-in (2.8 Nm) Electrical Life 6000 Switching Operations Mechanical Life 10000 Switching Operations GFL Series RCBO Dimensions (to convert to inches multply by 0.03937) Ground Fault Trip Curve 105mm 45mm 0.5 35mm 0.4 0.2 0.3 0.15 0.1 0.05 0.04 0.03 0.02 0.015 0.01 0.005 0.5 1 5 0.85 1.15 I In 17.5mm Weight 220 g 1 35 Royal Road Flemington, NJ 08822-6000 t 908-806-9400 f 908-806-9490 www.altechcorp.com UL 489 Branch Circuit Breaker with Ground Fault Relay 71mm 60mm 44mm t(s) Switch o time t(s)UL 489 Branch Circuit Breaker with Ground Fault Relay GFL Series - 1 Pole+N, B Trip, 10 mA Applicable voltage systems and wiring examples. L1 GFL...2 240 V 400 V 400 V L2 240 V 400 V 400Y/240V AC N 240 V L3 L1 GFL...2 120 V 208 V 208 V L2 120 V 208 V 208Y/120V AC N 120 V L3 GFL...2 L2 240 V 120 V N 120/240V AC 120 V L1 GFL...2 L2 240 V 120 V NOTE: Wiring a hot leg/phase to N N terminal is not permitted. 120 V L1 2 35 Royal Road Flemington, NJ 08822-6000 t 908-806-9400 f 908-806-9490 www.altechcorp.com LOAD LOAD LOAD LOAD N 1 LINE N 2 1 N LINE N 2