6 7 8 9 10 12 14 16 1820 1 2 3 4 5 GFL Series - 1 Pole+N, C Trip, 30 mA 10kA UL489 Listed Branch Circuit Breaker with Equipment Ground Fault Protection (RCBO) The GFL Series range is a combined Branch Circuit Breaker and Equipment Ground Fault Protector, featuring dual pole switching (live and neutral disconnect) and designed to provide protection against short circuits, overloads, AC ground faults (residual current faults) as well as pulsating DC ground faults. C.B. W/EQ.GFP E483494 Ordering Information Rated Type/ Rated Current Cat. No. Voltage 5.0A GFL2C050302 240V AC 6.0A GFL2C060302 240V AC GFL Series RCBO 8.0A GFL2C080302 240V AC Overload Trip Curves 10A GFL2C100302 240V AC Characteristics B, C, D 7200 12A GFL2C120302 240V AC 3600 2400 13A GFL2C130302 240V AC 1200 600 480 15A GFL2C150302 240V AC 360 240 16A GFL2C160302 240V AC 120 60 40 20A GFL2C200302 240V AC 20 25A GFL2C250302 240V AC 10 5 Technical Specification 1 Number of Poles 1+N 0.5 Voltage Rating (maximum) 240V AC Ground Fault Sensitivity Level 30 mA B C D 0.1 Rated Short Circuit Interrupt Capacity 10 kA 0.05 Rated Frequency 50/60Hz Trip Characteristic C 2 2 Cable Size & Tightening Torque Stranded Wire: 16 - 3 AWG (1.5 mm - 25 mm ) 17.5 lb-in (2.0 Nm) 0.01 2 2 16 - 10 AWG (1.5 mm - 5.5 mm ) 17.5 lb-in (2.0 Nm) 1.05 1.35 Solid Wire: Rated current multiple x I 2 2 n 18 - 16 AWG (1 mm - 1.5 mm ) 25 lb-in (2.8 Nm) Electrical Life 6000 Switching Operations Mechanical Life 10000 Switching Operations Dimensions GFL Series RCBO (to convert to inches multply by 0.03937) 105mm Ground Fault Trip Curve 45mm 35mm 0.5 0.4 0.2 0.3 0.15 0.1 0.05 0.04 0.03 0.02 0.015 0.01 0.005 0.5 1 5 0.85 1.15 I In 17.5mm Weight 220 g 1 35 Royal Road Flemington, NJ 08822-6000 t 908-806-9400 f 908-806-9490 www.altechcorp.com UL 489 Branch Circuit Breaker with Ground Fault Relay 71mm 60mm 44mm Switch time t(s) t(s)UL 489 Branch Circuit Breaker with Ground Fault Relay GFL Series - 1 Pole+N, C Trip, 30 mA Applicable voltage systems and wiring examples. L1 GFL...2 240 V 400 V 400 V L2 240 V 400 V 400Y/240V AC N 240 V L3 L1 GFL...2 120 V 208 V 208 V L2 120 V 208 V 208Y/120V AC N 120 V L3 GFL...2 L2 240 V 120 V N 120/240V AC 120 V L1 GFL...2 L2 240 V 120 V NOTE: Wiring a hot leg/phase to N N terminal is not permitted. 120 V L1 2 35 Royal Road Flemington, NJ 08822-6000 t 908-806-9400 f 908-806-9490 www.altechcorp.com LOAD LOAD LOAD LOAD N 1 LINE N 2 1 N LINE N 2