Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
6307FE Multi-Conductor - Commercial Applications
For more Information
please call
1-800-Belden1
General Description:
Security & Alarm Cable, Plenum-CMP, 9-18 AWG stranded bare copper conductors with Flamarrest
insulation, Beldfoil shield and Flamarrest jacket with ripcord
Usage (Overall)
Suitable Applications: Security Systems, Intercom/PA Systems, Sound/Audio Systems, Power Limited Controls
Physical Characteristics (Overall)
Conductor
AWG:
# Conductors AWG Stranding Conductor Material
9 18 7x26 BC - Bare Copper
Total Number of Conductors: 9
Insulation
Insulation Material:
Insulation Trade Name Insulation Material Wall Thickness (in.)
Flamarrest LS PVC - Low Smoke Polyvinyl Chloride 0.009
Outer Shield
Outer Shield Material:
Outer Shield Trade Name Type Outer Shield Material Coverage (%)
Beldfoil Tape Aluminum Foil-Polyester Tape 100
Outer Shield Drain Wire AWG:
AWG Stranding Drain Wire Conductor Material
24 (7x32) TC - Tinned Copper
Outer Jacket
Outer Jacket Material:
Outer Jacket Trade Name Outer Jacket Material Nom. Wall Thickness (in.)
Flamarrest LS PVC - Low Smoke Polyvinyl Chloride .015
Outer Jacket Ripcord: Yes
Overall Cable
Overall Cabling Color Code Chart:
Number Color
1 Black
2 Red
3 White
4 Green
5 Brown
6 Blue
7 Orange
8 Yellow
9 Purple
Overall Nominal Diameter: 0.266 in.
Mechanical Characteristics (Overall)
Operating Temperature Range: 0C To +75C
UL Temperature Rating: 75C
Bulk Cable Weight: 67 lbs/1000 ft.
Max. Recommended Pulling Tension: 215.600 lbs.
Min. Bend Radius/Minor Axis: 2.750 in.
Page 1 of 3 09-11-2017Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
6307FE Multi-Conductor - Commercial Applications
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification: CMP
NEC Articles: 800
CEC/C(UL) Specification: CMP
EU Directive 2011/65/EU (ROHS II): Yes
EU CE Mark: Yes
EU Directive 2000/53/EC (ELV): Yes
EU Directive 2002/95/EC (RoHS): Yes
EU RoHS Compliance Date (mm/dd/yyyy): 04/01/2005
EU Directive 2002/96/EC (WEEE): Yes
EU Directive 2003/11/EC (BFR): Yes
CA Prop 65 (CJ for Wire & Cable): Yes
MII Order #39 (China RoHS): Yes
Flame Test
UL Flame Test: NFPA 262
C(UL) Flame Test: FT6
Plenum/Non-Plenum
Plenum (Y/N): Yes
Non-Plenum Number: 5307FE
Electrical Characteristics (Overall)
Nom. Capacitance Conductor to Conductor:
Capacitance (pF/ft)
42
Nom. Capacitance Cond. to Other Conductor & Shield:
Capacitance (pF/ft)
76
Nom. Conductor DC Resistance:
DCR @ 20C (Ohm/1000 ft)
6.5
Nominal Outer Shield DC Resistance:
DCR @ 20C (Ohm/1000 ft)
13.800
Max. Operating Voltage - UL:
Voltage
300 V RMS
Max. Recommended Current:
Current
3.5 Amps per conductor @ 25C
Put Ups and Colors:
Item # Putup Ship Weight Color Notes Item Desc
6307FE 8771000 1,000 FT 72.000 LB NATURAL C 9 #18 FLRST FS FLRST
6307FE 877500 500 FT 36.000 LB NATURAL TRANSFER REVIEW (20 TO 30)
Notes:
C = CRATE REEL PUT-UP.
Revision Number: 2 Revision Date: 01-19-2015
2017 Belden, Inc
All Rights Reserved.
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described herein are subject to error or omission and to
change without notice, and the listing of such information and specifications does not ensure product availability.
Belden provides the information and specifications herein on anAS I basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for
any damages (including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether
in an action under contract, negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the compliance date may be in stock at Belden facilities
and in our Distributors inventory. The information provided in this Product Disclosure, and the identification of materials listed as reportable or restricted within the Product Disclosure, is
correct to the best of Beldens knowledge, information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide for the
safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not to be considered a warranty or quality specification.
Page 2 of 3 09-11-2017