FNP600/850/1000 AC-DC Front-Ends & FNR-5-12G/FNR-5-48G Power Shelves Data Sheet 600-to-5000-Watt Front-End Power Solutions Features RoHS lead free solder and lead solder exempted products are available 3 High density front-ends 10.5 to 16.1 W/in Universal input voltage range (90-264 VAC) with PFC 1U or 2U height configurations Droop current share with ORing FETs 2 I C interface status and control Standby voltage of 12 VDC 0.5 A Overtemperature, overload, and overvoltage protection (600, 850, or 1000 Watts) Status LEDs: AC OK, DC OK, Overtemperature FNP850-12 model has airflow direction from 2 front-to-rear or from rear-to-front (-12R model) I C Management Software: All FNP front-ends 2 can be controlled via Power-One s GUI-driven I C ON/OFF Enable switch - shuts OFF Vo1 Vaux and fan 2 Management software and an I C-to-USB are operational. 2 interface (P/N HZZ02002G). An I C Programming Manual describes the complete range of parameters that can be programmed to these Applications front-ends. This manual is available by searching Telecom onFNP600 at www.power-one.com. Datacom Distributed power systems FNR-5 Power Shelf FNR-5-48G Power Shelves provide up to 5000 watts in a 19 rack. (See the Rack section for power shelf details.) Description The FNP600/850/1000 power factor corrected (PFC) front ends provide (depending on model) either a 12 VDC or a 48 VDC output for telecom, datacom, and other distributed power applications. Their small 1U by 2U size allows for configurations of either height in hot-swap redundant systems while their internal fan and cooling design permits wide use with reliable operation. 2 2 Status is provided with front panel LEDs, logic signals, and via the I C management interface bus. In addition, the I C bus can enable the power supply, control fan speed, and on the 12 VDC models it allows for adjusting the output voltage from 7 to 12 VDC. This powerful feature allows the same power supply to be used in various applications where bus voltages driving isolated dc-dc converters and POL regulators may be different. Also, the FNP850-12R is uniquely designed with airflow from the rear of the power supply to the front. This airflow direction supports those critical applications where space limitations and/or higher ambient temperatures near the rear of the rack system, prohibit the discharge of higher temperature airflow from regular front-to-rear cooled power supplies. The FNP600/850/1000 s meet international safety requirements and are CE marked to the Low Voltage Directive (LVD). BCD20034-G Rev. AD, 11-May-10 Page 1 of 15 www.power-one.com FNP600/850/1000 AC-DC Front-Ends & FNR-5-12G/FNR-5-48G Power Shelves Data Sheet Model Selection Nominal Maximum Model Output Adjustment Output Line Load Ripple & Compatible Voltage Range (VDC) Current Regulation Regulation Noise Shelf 3 1 2 (Amps) (%) pk-pk % (VDC) (%) FNP600-12 12 7 to 12 51 0.17 6 1 FNR-5-12 12 (Standby) N/A 0.5 8 8 1 FNP850-12 12 7 to 12 73 0.17 6 1 FNR-5-12 12 (Standby) N/A 0.5 8 8 1 4 12 7 to 12 73 0.17 6 1 FNR-5-12 FNP850-12R 12 (Standby) N/A 0.5 8 8 1 FNP600-48 48 44 to 50.5 12.6 0.17 6 1 FNR-5-48 12 (Standby) N/A 0.5 8 8 1 FNP1000-48 48 44 to 50.5 21 0.17 6 1 FNR-5-48 12 (Standby) N/A 0.5 8 8 1 1 Models with 5V and 3.3V standby voltages are also available. (Contact factory.) 2 Primary 12V and 48V outputs have built-in droop regulation. 3 Maximum peak-to-peak noise expressed as a percentage of output voltage 20 MHz bandwidth. 4 FNP850-12R model has airflow from rear to front. Ordering Information Options Suffixes to Add to Part Number RoHS lead solder exemption No RoHS suffix character required. RoHS compliant for all 6 substances Add as the last character of the part number. Input Specifications Parameter Conditions/Description Min. Nom. Max. Units AC Input Voltage Single-phase continuous input range. 90 264 VAC Input Frequency AC input. 47 63 Hz 1 Hold-up Time After last AC line peak at full power. At 115 VAC. 20 ms Input Current At full-rated load. At 90 VAC. 14 A rms Inrush Surge Current Internally limited. Vin = 230 VAC. 25 C 34 A pk Power Factor Per EN61000-3-2 0.97 W/VA 1 FNP1000-48 model has a hold-up time of 16 ms. BCD20034-G Rev. AD, 11-May-10 Page 2 of 15 www.power-one.com