RFE1600 Series Specifications Model RFE1600-12 RFE1600-24 RFE1600-32 RFE1600-48 Input Input Voltage range Vac 85 - 265 Input Frequency Hz 47 - 63 Input Current (115/230Vac) A 11.6 / 8.1 Inrush Current A <35 Leakage Current mA Less than 0.75/1.5 at 115/230Vac Power Factor Correction - Meets EN61000-3-2, PF>0.98 at full load Harmonic Compliance - Meets IEC61000-3-2 Hold Up Time ms >10ms, 100/230Vac Input, 80% loading Efficiency % 87 / 90 88 / 90 88 / 90 89 / 92 Conducted & Radiated EMI - EN55032 & FCC part 15 Conducted class B, Radiated class A Immunity - See immunity section Safety Agency Certifications - IEC/UL/CSA/EN62368-1, 60950-1, CE Mark Immunity Test Standard Test Level Criteria Notes Radiated Susceptibility EN61000-4-3 2 A - Electrical Fast Transient Burst EN61000-4-4 2 B - Surge EN61000-4-5 3,4 B - Conducted Susceptibility EN61000-4-6 2 A - Magnetic fields EN61000-4-8 4 A - >95% for 0.5 cycles B - Voltage Dips EN61000-4-11 30% for 25/30 cycles C - Interruptions >95% for 250/300 cycles C - Specifications Model RFE1600-12 RFE1600-24 RFE1600-32 RFE1600-48 Output Line Regulation mV 30 60 80 120 Load Regulation mV 60 120 160 240 External Load Capacitance uF/A 1000 Ripple & Noise mV 240 240 320 480 Temperature Coefficient %/C <0.02 Minimum Load - No minimum load required Overcurrent Protection % 105-115 (Programmable) Overvoltage Protection (1) % 110% (Tracking). Cycle AC to reset or utilize Remote On/Off Overtemperature Protection - Shutdown with automatic reset. Warning signal provided (1) Remote Sense Compensation V/wire 0.25V 0.5V 0.75 1.0V Remote On/Off - Yes, inhibit & enable AC Good Signal - Open Collector, ON when AC is within 85-270Vac DC Good Signal - Open Collector, ON when output is above 85 to 95% of setpoint (tracking) 2 C) interface ( /S suffix) or plug-in LAN module. See model selectors Communication - Optional isolated PMBus (I Auxiliary Output - 11.2 - 12.5V, 0.5A, 240mV ripple and noise Indicators - AC OK: Green LED DC OK / Fail: Green / Red LED Parallel Operation - Yes, single wire current share, 5% accuracy of max current, up to 10 units Series Operation (1) - Two units maximum (external diodes required) 2 RFE1600 Series