RFE2500 Series Specifications Model RFE2500-12 RFE2500-24 RFE2500-48 Input Input Voltage Range Vac 85 - 265Vac. See model selector for power derating(2) Input Frequency Hz 47 - 63 Input Current (Max) (110/230Vac) A 15 / 12 Inrush Current A <50 Leakage Current mA Less than 0.8 /1.6mA at 115/230Vac, 60Hz Power Factor Correction - Meets EN61000-3-2, PF >0.98 at full load Harmonic Compliance - Meets IEC61000-3-2 Hold Up Time ms >10ms, 100/230Vac Input, 80% loading Efficiency % 90 / 92 90 / 92 91 / 93 Conducted EMI - Built to meet EN55032 Class B, FCC part 15 Class-B, VCCI Class-B Radiated EMI - Built to meet EN55032 Class A, FCC part 15 Class-A, VCCI Class-A Immunity - See immunity section Safety Agency Certifications - IEC/UL/CSA/EN62368-1, 60950-1, CE Mark Immunity Test Standard Test Level Criteria Notes ESD EN61000-4-2 2,3 B - Radiated Susceptibility EN61000-4-3 2 A - Electrical Fast Transient Burst EN61000-4-4 2 B - Surge EN61000-4-5 3,4 B - Conducted Susceptibility EN61000-4-6 2 A - Magnetic Fields EN61000-4-8 4 A - >95% for 0.5 cycles B - Voltage Dips / Interruptions EN61000-4-11 30% for 25/30 cycles C - >95% for 250/300 cycles C - Specifications Model RFE2500-12 RFE2500-24 RFE2500-48 Output Line Regulation mV 30 60 120 Load Regulation mV 60 120 240 External Load Capacitance uF/A 1000 Ripple & Noise mV 240 240 480 Temperature Coefficient %/C <0.02 Minimum Load - No minimum load required Overcurrent Protection % 115Vac:>110% 230Vac: 105 - 120% Overvoltage Protection (1) % 110% (Tracking). Cycle AC to reset or utilize Remote On/Off Overtemperature Protection - Shutdown with automatic reset. Warning signal provided (1) Remote Sense Compensation V/wire 0.25 0.5 1.0 Remote On/Off - Yes, inhibit & enable AC Fail Signal - Open Collector, ON when AC is within 85-270Vac DC Good Signal - Open Collector, ON when output is above 85 to 95% of setpoint (tracking) 2 Communication - Optional isolated PMBus (I C) interface ( /S suffix) or plug-in LAN module. See model selectors Auxiliary Output - 11.2 - 12.5V, 0.5A, 240mV ripple and noise Indicators - AC OK: Green LED, DC OK / Fail: Green / Red LED Parallel Operation - Yes, single wire current share, 5% accuracy of max current, up to 8 units Series Operation (1) - Two units maximum (external diodes required) 2 RFE2500 Series