The FNP1500/1800 front-ends are power-factor-
corrected (PFC) which (depending on model type)
provide a 12 VDC or 48 VDC (1500 or 1800 watt)
output, and can be used in hot-swap redundant
systems. Their very small dimensions allow
configuration of up to three units in a 1U rack. The
FNP front-ends have a front-mounted AC
receptacle. The highly efficient thermal design with
internal-fan cooling permits their use over wide
temperature ranges and provides very high
reliability.
Status information is provided with front panel
2
LEDs, logic signals, and via an I C management
2
interface. In addition, the I C bus can enable the
power supply, set high fan speed, adjust the output
voltage, and set the output current limit. The
FNP1500/1800's meet international safety
RoHS compliant for all six substances standards and display the CE-Mark for the
European Low Voltage Directive (LVD).
3
High density front-ends 15.2 to 18.3 W/in
Wide input voltage range 85 to 264 VAC
FNR-3-12G and FNR-3-48G power-shelf solutions
12 V standby voltage, 1A per front-end
provide rectification, system management, and
power distribution, while maintaining high reliability
Highly efficient topology reduces operating costs
and offering flexibility for future expansion. The
2
I C interface status and control
power shelves can be configured with up to three
2
I C voltage and current limit setting
hot-swappable 1500 or 1800-watt AC-DC front-
Analog output voltage setting
ends.
Overtemperature, output overvoltage, and output
overcurrent protection
ORing circuits for true redundant operation:
Telecom
V : ORing FETs; V : ORing Diodes
o1 o2
Datacom
Status LEDs: AC OK, DC OK, and
Servers
Fan Fail/Overtemperature Fail
Distributed power systems
North America
+1-866.513.2839
Asia-Pacific
+86.755.29885888
Europe, Middle East
+353 61 225 977
tech.support@psbel.com
2015 Bel Power Solutions, Inc. BCD.00247_AB1
FNP1500/FNP1800
INPUT VOLTAGE OUTPUT 1 OUTPUT 2 RATED
COMPATIBLE
MODEL VAC POWER
V I V I 2
o1 nom o1 max o2 nom o2 max
SHELF
1
AUTO SELECTED W
VDC ADC VDC ADC
108 264 12 129 @ 11.64V 12 1 1512
3
FNP1500-12G FNR-3-12G
85 105 12 101.8 @ 11.78A 12 1 1212
105 264 48 32.2 12 1 1512
FNP1500-48G FNR-3-48G
85 105 48 25.4 12 1 1212
180 264 48 39.2 12 1 1812
FNP1800-48G 105 180 48 32.2 12 1 1512 FNR-3-48G
85 105 48 25.4 12 1 1212
1
The available output power is automatically adjusted depending on the input voltage.
2
1U standard racks are available from Bel Power Solutions. See the Rack (Power Shelf) section of this data sheet for configurations and
details.
3
Not recommended for new design.
Stress in excess of the absolute maximum ratings may cause performance degradation, adversely affect long-term reliability,
or cause permanent damage to the converter.
PARAMETER CONDITIONS / DESCRIPTION MIN MAX UNIT
Continuous 264 VAC
Input Voltage
Transient, 60 ms max. 300 VAC
V -V , I , cooling by internal fan
i min i max o nom
Operating Ambient Temperature @ 100 % load 0 50 C
@ 50 % load 0 70 C
Storage Temperature Non-Operating -40 85 C
Specification is valid for input voltage, load, and temperature ranges, unless otherwise stated.
PARAMETER CONDITIONS / DESCRIPTION MIN NOM MAX UNIT
Input Voltage 85 230 264 VAC
Input Frequency 47 50/60 63 Hz
Ramping up
Turn-On Input Voltage 79 85 VAC
Ramping down
Turn-Off Input Voltage 70 78 VAC
115/230 VAC acc. ETS 300 132-1
Inrush Current Limitation
< 100 ms
50 Apk
Hold-Up Time After last AC line peak ,Vi = 230 VAC, Po nom 20 ms
Vi nom, Io nom
Power Factor 0.95 W/VA
1
V = 230 VAC, I , T = 25 C
Efficiency i o nom C 89 90 %
Max Input Current 20 Arms
16A 20 A / 250 VAC; according to IEC320 C19
Input Connector
1
87% for FNP1500-12
866.513.2839