A-SerieA-Ss eries
CIRCUIT BREAKER
Well known for their proven reliability, Carling Technologies A-Series hydraulic magnetic circuit breakers are
compact, temperature stable and designed for precision operation in OEM markets requiring general purpose
as well as full load amp applications. When front panel operation and aesthetics demand a clean, contemporary
design, the visi-rocker or paddle actuators are ideally suitable. A sealed toggle actuator style is also available and
ideal for harsh environment applications requiring additional sealing protection. Optional rocker-guard and push-
to-reset bezels, which help prevent inadvertent actuation, are also available.
1-6 poles; ratings from 0.02 to 50 amps, up to 277VAC or 80VDC; UL Recognized, UL Listed, UL1500, UL1077,
TUV, VDE & CSA
Resources:
Configure a Complete Part
Download CAD & Sales Drawing
Product Highlights: Typical Applications:
Up to 50 amps in a compact size Telecom / Datacom
Various actuator styles Marine
Sealed metal toggle option tested to Military
MIL-PRF-55629C. Meets IP68 Renewable Energy
Requirements Generators & Welder
Carling Technologies, Inc.
60 Johnson Avenue, Plainville, CT 06062
Email: sales@carlingtech.com www.carlingtech.com
Application Support: team2@carlingtech.com
Phone: 860.793.9281 Fax: 860.793.9231|
2 A-Series Circuit Breaker General Specifications
Electrical Mechanical
Maximum Voltage 277VAC 50/60 Hz, 80VDC Endurance 10,000 ON-OFF operations @ 6 per
Current Ratings Standard current coils: 0.100, minute; with rated Current & Voltage.
0.250, 0.500, 0.750, 1.00, 2.50, Trip Free All A-Series Circuit Breakers will trip
5.00, 7.50, 10.0, 15.0, 20.0, 25.0, on overload, even when the actuator
30.0, 35.0, 40.0, 50.0. Other ratings is forcibly held in the ON position.
available - consult ordering Trip Indication The operating actuator moves
scheme. positively to the OFF position when
Standard Voltage Coils DC-6V, 12V; AC-120V, Other ratings an overload causes the circuit
available, consult ordering scheme. breaker to trip. When mid-trip
Auxiliary Switch Rating SPDT; 10.1 A - 250VAC, handle is specified, the handle
1.0 A-65VDC/0.5 A - 80 VDC, moves to the mid position on
0.1A - 125VAC (with gold contacts). electrical trip of the circuit breaker.
Insulation Resistance Minimum: 100 Megohms at 500 When mid-trip handle with alarm
VDC switch is specified, the handle
Dielectric Strength UL, CSA - 1500V 60 Hz for one moves to the mid position & the
minute between all electrically alarm switch actuates when the
isolated terminals. A-Series rocker circuit breaker is electrically tripped.
circuit breakers comply with the
Physical
8mm spacing & 3750V dielectric
requirements from hazardous
Number of Poles 1 - 6 Poles (handle) and 1-3 poles
voltage to operator accessible
(rocker) at 30 Amps or less. 1 and 2
surfaces per EN 60950 and VDE
poles at 31 Amps thru 50 Amps.
0805.
Internal Circuit Config. Series, (with or without auxiliary
Resistance, Impedance Values from Line to Load Terminal
switch), Shunt and Relay with current
- based on Series Trip Circuit
or voltage trip coils, Dual Coil,
Breaker.
Switch Only with or without auxiliary
RESISTANCE PER POLE VALUES
switch.
from Line to Load Terminals
Weight Approximately 65 grams/pole.
(Values Based on Series Trip Circuit Breaker)
(Approximately 2.32 ounces/pole)
Standard Colors Housing - Black; Actuator- See
CURRENT TOLERANCE
(AMPS) (%) Ordering Scheme.
0.10 - 5.0 15
Environmental
5.1 - 20.0 25
Designed and tested in accordance with requirements of
specification MIL-PRF-55629 & MIL-STD-202 as follows:
20.1 - 50.0 35
Shock Withstands 100 Gs, 6ms, sawtooth
while carrying rated current per
Method 213, Test Condition I.
Instantaneous and ultra-short curves
tested @ 90% of rated current.
Vibration Withstands 0.060 excursion from
10-55 Hz, and 10 Gs 55-500 Hz,
at rated current per Method 204C,
Test Condition A. Instantaneous and
ultrashort curves tested at 90% of
rated current.
Pulse Tolerance Curves
Moisture Resistance Method 106D; ten 24-hour cycles @
+ 25C to +65C, 80-98% RH.56
days @ +85C, 85% RH.
Salt Spray Method 101, Condition A (90-95%
RH @ 5% NaCl Solution, 96 hrs).
Thermal Shock Method 107D, Condition A (Five
cycles @ -55C to +25C to +85C to
+25C).
Operating Temperature -40 C to +85 C
*Manufacturer reserves the right to change product specification without prior notice.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com