C-Series
Circuit Breaker
The C-Series hydraulic/magnetic circuit breakers are ideal
for applications that require higher amperage and voltage
handling capability in a smaller package. They are available
in 1-6 poles, 0.02-100amps, UL Recognized up to 480VAC or
150VDC, UL489 Listed up to 240VAC or 125VDC, with choice
of time delays, terminal options, actuator styles and colors.
HANDLE ACTUATOR METAL TOGGLE ACTUATOR
Product Highlights:
The UL489 C-Series employs a unique arc chute design
which allows for higher interrupting capacities of up to
10,000 amps. New thermoset glass filled polyester half
shell construction provides for increased mechanical
and electrical strength. The wiping contacts, mechanical
linkage with two step actuation, clean contacts providing
high, positive contact pressure and longer contact life
Available with American Standard or Metric Threaded
Stud terminals, or Saddle Clamp screw terminals. Optional
PARALLEL POLE ACTUATOR
mid-trip handle style actuator allows visual indication of
electrical overload with or without alarm feature
Available with new solid color rocker actuators and
Agency Certifications:
unique two-color Visi-rocker actuators, which can be
UL Recognized
specified to indicate either the ON or TRIPPED/OFF mode
|
UL Standard 1077 UL Standard 508
Exclusive Rockerguard and Push-To-Reset bezel help
UL Standard 1500
prevent inadvertent actuation
UL Listed
The metal toggle option was tested to MIL-PRF-55629C
|
UL Standard 489 UL Standard 489A
for ingress protection when mounted in a panel, and also |
CSA Accepted CSA Certified
|
meets IP68 requirement. TUV Certified VDE Certified
* For full Agency Certifications, please see pg. 6
Carling Technologies, Inc.
60 Johnson Avenue Plainville, CT 06062
Phone: (860) 793-9281 Fax: (860) 793-9231
Email: sales@carlingtech.com www.carlingtech.com|
2 C-Series General Specifications
Electrical Tables
Table A: Lists UL Recognized & CSA Accepted configurations and performance capabilities as a Component Supplementary
Protector
C-SERIES TABLE A: COMPONENT SUPPLEMENTARY PROTECTORS
SHORT CIRCUIT CAPACITY (AMPS)
VOLTAGE CURRENT RATING APPLICATION CODES
UL/CSA
CIRCUIT
NOTES
CONFIGURATION
WITH BACKUP
MAX. FULL LOAD GENERAL WITHOUT BACKUP
FREQUENCY PHASE UL CSA
1
RATING AMPS PURPOSE AMPS FUSE
FUSE
32 DC --- 0.02 - 100 --- --- 5000 TC1, OL1, U2 TC1, OL1, U2
48 DC --- 110 - 150 --- --- 5000 TC1, OL1, U2 TC1, OL1, U2
65 DC --- 0.02 - 70 --- --- 5000 TC1,2, OL1,U1 TC1,2, OL1,U1
--- 71 -100 --- 5000 TC1,2, OL0,U1 TC1,2, OL0,U1
0.02 - 70 --- --- 7500 TC1,2, OL1,U1 TC1,2, OL1,U1
80 DC ---
--- 71 -100 --- 7500 TC1,2, OL0,U1 TC1,2, OL0,U1
0.02 - 70 --- --- 10,000 TC1,2, OL1,U1 TC1,2, OL1,U1 Must Have Agency Code
80 DC ---
--- 71 -100 --- 10,000 TC1,2, OL0,U1 TC1,2, OL0,U1 Must Have Agency Code
125 DC --- 0.02 - 50 --- 5000 TC1,2,OL1,U1 TC1,2,OL1,U1 Must Have Agency Code
125 / 250 DC --- 0.02 - 50 --- 5000 TC1,2,OL1,U1 TC1,2,OL1,U1 Must Have Agency Code
250 DC --- 0.02 - 50 --- 5000 TC1,2,OL1,U1 TC1,2,OL1,U1 Must Have Agency Code . 2 Pole Break Required for 250 Volts
0.02 - 100 --- --- 3000 TC1, OL1, U2 TC1, OL1, U2 Per Pole Rating
125 50 / 60 1
0.02 - 100 --- --- 5000 TC1,2,OL1,U1 TC1,2,OL1,U1 Must Have Agency Code
150 DC --- --- 80 - 100 --- 5000 TC1, OL0, U3 --- Must Have Agency Code
150 DC --- --- 101 - 175 --- 5000 TC1, OL0, U3 --- Must Have Agency Code Parallel Pole
SERIES
0.02 - 100 --- --- 3500 TC1, OL1, U2 TC1, OL1, U2
0.02 - 50 --- --- 3000 TC1,2,OL1,U1 TC1,2,OL1,U1 2 or 3 poles breaking single phase
125 / 250 50 / 60 1
51 - 100 --- --- 1000 TC1,2,OL1,U1 TC1,2,OL1,U1 2 or 3 poles breaking single phase
0.02 - 100 --- --- 5000 TC1,2,OL1,U2 TC1,2,OL1,U2 2 or 3 poles breaking single phase, Agency Code
0.02 - 50 --- --- 3500 TC1, OL1, U2 TC1, OL1, U2 Per Pole Rating
1 0.02 - 100 --- --- 5000 TC1,2,OL1,U1 TC1,2,OL1,U1 Must Have Agency Code
51 - 70 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1
250 50 / 60
--- 0.02 - 100 --- 3000 TC1, OL0, U2 TC1, OL0, U2
3 0.02 - 70 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 3 poles breaking 3 phase
--- 0.02 - 90 --- 5000 TC1,2,OL0,U1 TC1,2,OL0,U1 Must Have Agency Code
277 50 / 60 1 0.02 - 50 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1
0.02 - 30 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 3 poles breaking 3 phase
480 / 277 50 / 60 3
--- 31 - 50 5000 --- TC1,2,OL0,C1 TC1,2,OL0,C1
0.02 - 30 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 2 poles breaking 1 phase
480 50 / 60 1
--- 31 - 50 5000 --- TC1,2,OL0,C1 TC1,2,OL0,C1
80 DC --- 0.02 - 50 --- --- 7500 TC1,2, OL1,U1 TC1,2, OL1,U1
125 50 / 60 1 0.02 - 50 --- --- 3000 TC1, OL1, U2 TC1, OL1, U2 Per Pole Rating
0.02 - 50 --- --- 3500 TC1, OL1, U2 TC1, OL1, U2 2 or 3 poles breaking single phase
125 / 250 50 / 60 1
0.02 - 50 --- --- 3000 TC1,2,OL1,U1 TC1,2,OL1,U1 2 or 3 poles breaking single phase
DUAL COIL
1 0.02 - 50 --- --- 3500 TC1, OL1, U2 TC1, OL1, U2
250 50 / 60 0.02 - 50 --- --- 3000 TC1, OL0, U2 TC1, OL0, U2 Per Pole Rating
3
0.02 - 50 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1
277 50 / 60 1 0.02 - 50 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 3 poles breaking 3 phase
80 DC --- 0.02 - 50 --- --- 7500 TC1,2, OL1,U1 TC1,2, OL1,U1
277 50 / 60 1 0.02 - 50 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1
250 50 / 60 3 0.02 - 50 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 3 poles breaking 3 phase
0.02 - 30 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 3 poles breaking 3 phase
SHUNT
480 / 277 50 / 60 3
--- 31 - 50 5000 --- TC1,2,OL0,C1 TC1,2,OL0,C1
0.02 - 30 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 2 poles breaking 1 phase
480 50 / 60 1
--- 31 - 50 5000 --- TC1,2,OL0,C1 TC1,2,OL0,C1
80 DC --- 0.02 - 50 --- --- 7500 TC1,2, OL1,U1 TC1,2, OL1,U1
RELAY 277 50 / 60 1 0.02 - 50 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1
250 50 / 60 3 0.02 - 50 --- 5000 --- TC1,2,OL1,C1 TC1,2,OL1,C1 3 poles breaking 3 phase
0.02 - 70 --- --- --- --- ---
65 DC ---
--- 71 -100 --- --- --- ---
0.02 - 70 --- --- --- --- ---
80 DC ---
--- 71 -100 --- --- --- ---
125 50 / 60 1 0.02 - 100 --- --- --- --- ---
SWITCH ONLY 125 / 250 50 / 60 1 0.02 - 100 --- --- --- --- --- 2 or 3 poles breaking single phase
1 0.02 - 100 --- --- --- --- ---
250 50 / 60
3 0.02 - 70 --- --- --- --- ---
277 50 / 60 1 0.02 - 50 --- --- --- --- ---
0.02 - 30 --- --- --- --- --- 3 poles breaking 3 phase
480 / 277 50 / 60 3
--- 31 - 50 --- --- --- ---
Notes for Table A:
1 Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse rated 15A minimum and no more than 4 times full load amps not to exceed 125A for 50 Amp or less rating and
not to exceed 175 for 51 through 100 Amp rating
*Manufacturer reserves the right to change product specification without prior notice.
60 Johnson Avenue Plainville, CT 06062 Phone: (860) 7939281 Fax: (860) 7939231
Email: sales@carlingtech.com www.carlingtech.com