E-SE-Series eries
CIRCUIT BREAKER
The E-Series hydraulic-magnetic circuit breaker is ideally suited for higher current and voltage applications. It is
UL listed and CSA certified for branch circuit protection, which does not require a fuse back up. It is also UL
recognized and CSA certified as a supplementary protector and as a manual motor controller.
Its physical features include front and back mounting, screw and stud terminals and heavy duty box wire
connectors for solid wire or a pressure plate connector for standard wire. The E-series is available with handle
actuators and can be configured as .1-125 amps, up to 600VAC or 125VDC, with choice of time delays, actuator
colors and 1 to 6 poles configuration. Additionally, a Power Selector device is also available.
Resources:
Configure a Complete Part
Download CAD & Sales Drawing
Product Highlights: Typical Applications:
UL listed and CSA certified High Voltage / High Current Applications
Certified for circuit branch protection Renewable Energy
Recognized as a supplementary protector Military
and as a manual motor controller
Industrial Controls
Optional power selector device
Generators
Carling Technologies, Inc.
60 Johnson Avenue, Plainville, CT 06062
Email: sales@carlingtech.com www.carlingtech.com
Application Support: team2@carlingtech.com
Phone: 860.793.9281 Fax: 860.793.9231|
2 E-Series Circuit Breaker General Specifications
Electrical Mechanical
Maximum Voltage 600VAC 50/60 Hz, 125VDC (See Endurance 10,000 ON-OFF operations @ 6
Table A) per minute; with rated Current and
Current Ratings Standard current coils: 0.100, Voltage.
0.250, 0.500, 1.00, 2.50, 5.00, Trip Free All E-Series Circuit Breakers will
7.50, 10.0, 15.0, 20.0, 25.0, 30.0, trip on overload, even when
50.0, 60.0, 70.0 & 100 Amp. Handle is forcibly held in the ON
Auxiliary Switch Rating SPDT; 10.1A 250VAC, 1.0A position.
65VDC; 0.5A 80VDC, 0.1A 125VAC Trip Indication The operating Handle moves
(with gold contacts). positively to the OFF position
Insulation Resistance Minimum of 100 Megohms at 500 when an overload causes the
VDC. breaker to trip.
Dielectric Strength UL, CSA: 2200 V 50/60 Hz for one
Physical
minute between all electrically
isolated terminals. E-Series Circuit
Number of Poles 1 - 6
Breakers comply with the 8mm
Mounting A 3 minimum spacing must be
spacing and 3750V 50/60 Hz
provided between the circuit
dielectric requirements from
breaker arc venting area on back
hazardous voltage to operator
connected E-Series circuit
accessible surfaces, between
breakers and grounded
adjacent poles and from main
obstructions. E-Series circuit
circuits to auxiliary circuits per
breakers must be mounted on a
Publications EN 60950 and VDE
vertical surface.
0805.
Connectors, Box Type Front connected E-Series circuit
Resistance, Impedance Values from Line to Load Terminal
breakers are supplied with box
- based on Series Trip Circuit
type pressure connectors that
Breaker.
accept copper or aluminum
conductors as follows: 1/0-14
Copper, 1/0-12 Aluminum.
Internal Circuit Series and Switch Only, (with or
CURRENT TOLERANCE
Configuration without auxiliary switch). Shunt
(AMPS) (%)
with current coils.
0.10 - 5.0 15
Weight Approximately 252 grams/pole
5.1 - 20.0 25
(Approximately 9 ounces/pole)
Standard Colors Housing-Black; Actuator - See
20.1 - 50.0 35
Ordering Scheme.
Environmental
Designed in accordance with requirements of specification
MIL PRF-55629 & MIL-STD-202G as follows:
Shock Withstands 100 Gs, 6ms, sawtooth
while carrying rated current per
Pulse Tolerance Curves
Method 213, Test Condition I.
Vibration Withstands 0.060 excursion from
Time Delay Curves
10-55 Hz, and 10 Gs 55-500 Hz, at
62, 64 & 66
(100 Amps Max.)
rated current per Method 204C,
Time Delay Curves
Test Condition A.
22, 24 & 26 (100 Amps Max.)
Moisture Resistance Method 106D, i.e., ten 24-hour
cycles @ + 25C to +65C, 80-98%
RH.
Salt Spray Method 101, Condition A (90-95%
RH @ 5% NaCl Solution, 96 hrs).
Thermal Shock Method 107D, Condition A (Five
cycles @ -55C to +25C to +85C
to +25C).
Operating Temperature -40 C to +85 C
*Manufacturer reserves the right to change product specification without prior notice.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com