PD-Series
Ground Fault Circuit Protection
SmartGuard is an equipment ground fault protection device
that functions as a standard high-quality Carling hydraulic/
magnetic circuit breaker, offering customized overload and
short circuit protection. In addition, this breaker senses
and guards against faults to ground using a state of the art
integrated circuit developed by Carling. This new technology
detects faults and when a fault occurs, the breaker trips and
an LED illuminates. The LED gives a clear indication that the
trip occurred as a result of leakage. This protection helps
prevent serious equipment damage and fire.
Features:
Overload, short circuit and ground fault protection in a
single package
Handle style actuators with optional handleguard
Wiping Contacts - Mechanical linkage with two-step
Agency Certifications:
actuation cleans contacts, provides high, positive
contact pressure & longer contact life UL Standard 1077 Component Recognition Program as
A trip-free mechanism, a safety feature, makes it Equipment Leakage Circuit Interrupter
impossible to manually hold the contacts closed during and, Protectors, Supplementary (FTTJ2, File
overload or fault conditions. E177510).
A common trip linkage between all poles, another safety UL Standard 943 Tested as Ground Fault Circuit Interrupters
feature, ensures that an overload in one pole will trip all for Equipment Protection.
adjacent poles. CSA Certified Component Equipment Leakage Current
Front panel or DIN rail mounting options Interrupter with Supplementary Protector,
State of the art integrated circuit developed by Carling under Class C22.2,No. 144-M91, FIle
Equipment leakage sensitivity from 10 to 100 milliamps LR47848-50
Integral push-to-test button and LED tripped indicator TUV Certified IEC 947-2 and appendix B: Circuit Breakers
Immediate reset after fault has been cleared incorporating Residual Current Protection.
Complies with waveform requirements of
IEC 1008-1, Type A.
Carling Technologies, Inc.
60 Johnson Avenue Plainville, CT 06062-1177
Phone: (860) 793-9281 Fax: (860) 793-9231
Email: sales@carlingtech.com www.carlingtech.com|
2 PD-Series Circuit Breaker - General Specifications
Electrical Tables
Table A: Lists UL Recognized & CSA Certified configurations and Table B: Lists TUV Certified configurations and performance capabilities
performance capabilities as a Component Supplementary Protector. as a Circuit breaker incorporating residual current protection.
PD-SERIES TABLE A: COMPONENT SUPPLEMENTARY PROTECTOR & EARTH LEAKAGE CURRENT INTERRUPTER
INTERRUPTING L EAKAGE
VOLTAGE CURRENT RATING
CAPACITY (AMPS) CURRENT
FULL GENERAL UL / CSA MUST - TRIP
CIRCUITRMAX ATING L OAD PURPOSE WITHOUTRATING
FREQUENCY
CONFIGURATION VOLTS HERTZ PHASE AMPS AMPS BACKUP FUSE(MILLIAMPS)
120/208 50/60 1 1-50 --- 5000 7-100
120/208 50/60 31 1-50 --- 5000 7-100
SERIES
208-240 50/60 3 1-50 --- 2000 7-100
480Y 50/60 3 1-30 30.1-50 2000 7-100
Electrical
Mechanical
Maximum Voltage AC, 480 WYE/277 VAC, 50/60 Hz
Endurance 10,000 ON-OFF operations @ 6 per
Standard Current Ratings
1.00, 2.50, 5.00, 7.50, 10.0, 15.0, minute; with rated current and voltage.
20.0, 25.0, 30.0, 35.0, 40.0 & 50.0
Trip Free All SmartGuard equipment leakeage
amps. For other ratings, consult factory.
circuit breakers will trip on overload
Insulation Resistance Minimum of 100 Megohms @ 500 VDC.
or leakage to ground, even when
Dielectric Strength 1960 VAC, 60 Hz for one minute
actuator is forcibly held in the ON
between all electrically isolated position.
terminals.
Trip Indication The actuator moves to the OFF
Resistance, Impedance from Line to Load Terminal
position when an overload or earth
(Values Based on Series Trip Circuit
leakage ground fault causes the
Breaker)
breaker to trip. The LED is illuminated
RESISTANCE, IMPEDANCE VALUES
when leakage to ground causes the
from Line to Load Terminals
Ampere Rating
circuit breaker to trip.
Physical
Number of Poles 2, 3 & 4
20.1 - 50.0
Length (included switched
or unswitched neutral)
4.2 inches ( 106.7 mm)
Pulse Tolerance Curve
Width
2-pole: 3.0 inches (76.2 mm)
60 Hz 1/2 Cycle
Inrush Pulse Tolerance
I
r
3-pole: 3.75 inches (95.3 mm)
4-pole: 4.5 inches (114.3 mm)
Time Delay Curves Depth
2.5inches (63.5mm).
22, 24, 26
12x
Weight: 2-pole
16.0 oz. (453.6 gm)
t
3-pole: 21.4 oz. (606.7 gm)
8.33
16.67
4.165
Time in
4-pole: 26.9 oz. (762.6 gm)
Milliseconds
Standard Colors
Housing - gray;
Actuator - black, red, or white
Mounting
Front Panel or Standard 35mm
Symmetrical DIN Rail (35 x 7.5 or
Leakage To Ground
35 x 15mm per DIN EN5002).
Standard Must Trip
Termination
Box Lug
Leakage Current Ratings
7, 10, 15, 30, 50 & 100 milliamps. For
other ratings, consult factory.
Environmental
Trip Time 300 ms Max. @ 100%, 40ms Max. @
500% of must trip leakage current. Operating Temperature +10C to +50C
Test Button On breaker face above actuator.
Leakage Trip Indicator
Red LED on breaker face above
actuator.
*Manufacturer reserves the right to change product specification without prior notice.