WM40 96 Energy Management Smart Modular Power Analyzer Type WM40 96 Class 0.5S (kWh) according to EN62053-22 Class 2 (kvarh) according to EN62053-23 Accuracy 0.2% RDG (current/voltage) Instantaneous variables readout: 4x4 DGT Energies readout: 9+1 DGT System variables: VLL, VLN, A, VA, W, var, PF, Hz, phase-sequence, phase-asymmetry and phaseloss. Single phase variables: VLL, VLN, AL, An (calculated or real depending on the option), VA, W, var, PF Both system and singles phase variables with average, max and min calculation Direct neutral current measurement (on request) Harmonic analysis (FFT) up to the 32nd harmonic (current and voltage) with harmonics source detection Optical front communication port (ANSI type 2) (imported/exported, only via serial port) Up to one RS232 and RS485 port (on request) Energy measurements (imported/exported): total and Communication protocol: MODBUS-RTU partial kWh and kvarh (inductive and capacitive) or MODBUS TCP/IP Ethernet port (on request) based on 6 different tariffs (on request) BACnet-IP over Ethernet port (on request) Energy measurements according to ANSI C12.20, BACnet MS/TP over RS485, BTL approved (on request) CA 0.5, ANSI C12.1 Profibus DP V0 port, PROFIBUS Nutzerorganisation Gas, cold water, hot water, remote heating e.V. approved (on request) measurements (on request) Up to 6 digital inputs for tariff selection, dmd synch, Run hours counter (8+2 DGT) gas/water (hot-cold) and remote heating metering (on Real time clock function request) Data stamping of up to 10,000 events: alarm, min, Up to 8 static outputs (pulse, alarm, remote control) max, digital input status, digital output status, resets, (on request) programming changing (on request) Up to 6 relay outputs (pulse, alarm, remote control) Application adaptable display and programming (on request) procedure (Easyprog function) Up to 16 freely configurable alarms with OR/AND logic Universal power supply: linkable with up to either 4 relay outputs or up to 6 24-48 VDC/AC, 100-240 VDC/AC static outputs (on request) Front dimensions: 96x96 mm Up to 4 analogue outputs (+20mA, +10VDC) (on Front protection degree: IP65, NEMA4x, NEMA12 request) Product Description Three-phase smart power analyzer with built-in application The instrument is equipped with optical communication port, configuration system and LCD data displaying. Particularly further I/Os such as: RS485/RS232, Ethernet, BACnet-IP, recommended for the measurement of the main electrical BACnet MS/TP or Profibus DP V0 communication ports, variables. pulse and alarm outputs and 6 digital inputs or analogue WM40 is based on a modular housing for panel mounting outputs are available on request. Parameters programming with IP65 (front) protection degree. Moreover the analyzer and data reading can be easily performed by means of UCS can be provided with digital outputs that can be either for (Universal Configuration Software). pulse proportional to the active and reactive total, partial and tariff energy being measured or/and for alarm outputs. Specifications are subject to change without notice WM40 96 DS 161120 1WM40 96WM40 96 How to order WM40-96 AV5 3 H R4 CT S1 XX Model Range code System Power Supply A Inputs/Outputs B Inputs/Outputs Communication and data stamping Option Type Selection Range codes System Power supply A Inputs/Outputs AV4: 3x220 (380)... 3: balanced and H: 100-240 +/-10% XX: none 3x400(690)V 1(2)A unbalanced load: (90 to 255) VDC/AC R2: Dual channel relay V : 220 to 400 LN 3-phase, 4-wire (50/60 Hz) output V : 380 to 690 LL 3-phase, 3-wire L: 24-48 +/-15% O2: Dual channel static AV5: 3x220(380)... 2-phase, 3-wire (20 to 55) VDC/AC output 3x400(690)V 5(6)A 1-phase, 2-wire (50/60 Hz) A2: Dual channel V : 220 to 400 LN 20mADC output V : 380 to 690 LL V2: Dual channel 10VDC AV6: 3x57.7(100)... output 3x133(230)V 5(6)A R4: Advanced six chan- V : 57.7 to 133 LN nel digital inputs + V : 100 to 230 LL four channel relay AV7: 3x57.7(100)... outputs + OR/AND 3x133(230)V 1(2)A alarm logic manage- Communication and data S. V : 57.7 to 133 LN ment V : 100 to 230 LL O6: Advanced six chan- XX: none nel digital inputs + S1: RS485/RS232 port six channel static S3: RS485/RS232 port outputs + OR/AND with data stamping alarm logic manage- E2: Ethernet / Internet ment B Inputs/Outputs Options port E3: Ethernet / Internet port with data stamp- XX: none XX: none ing A2: Dual channel B1: BACnet (IP) over 20mADC output Ethernet V2: Dual channel 10VDC B2: BACnet (IP) over output Ethernet with data TP: One temperature stamping and one process sig- B3: BACnet (MS/TP) nal input over RS485 CT: Direct neutral current B4: BACnet (MS/TP) measurement + One over RS485 with temperature and one data stamping process signal input P1: Profibus DP/V0 port P2: Profibus DP/V0 port with data stamping 2 Specifications are subject to change without notice WM40 96 DS 161120