WM30 96 Energy Management Smart Modular Power Analyzer Type WM30 96 Class 0.5S (kWh) according to EN62053-22 Class C (kWh) according to EN50470-3 Class 2 (kvarh) according to EN62053-23 Accuracy 0.2% RDG (current/voltage) Instantaneous variables readout: 4x4 DGT Energies readout: 9+1 DGT System variables: VLL, VLN, A, VA, W, var, PF, Hz, Phase-sequence-asymmetry-loss. Single phase variables: VLL, VLN, AL, An (calculated), VA, W, var, PF Both system and single phase variables with average and max calculation Harmonic analysis (FFT) up to the 32nd harmonic (current and voltage) One RS232 and RS485 port (on request) Energy measurements (imported/exported): total and Communication protocol: MODBUS-RTU partial kWh and kvarh MODBUS TCP/IP Ethernet port (on request) Energy measurements according to ANSI C12.20 CA BACnet-IP over Ethernet port (on request) 0.5, ANSI C12.1 (revenue grade) BACnet MS/TP over RS485, BTL approved (on request) Run hours counter (8+2 DGT) Ethernet/IP port, ODVA approved (on request) Real time clock function Profibus DP V0 port (on request) Application adaptable display and programming Up to 2 digital outputs (pulse, alarm, remote control) procedure (Easyprog function) (on request) Universal power supply: 24-48 VDC/AC, 100-240 VDC/AC Up to 4 freely configurable virtual alarms Front dimensions: 96x96 mm Up to 2 analogue outputs (+20mA, +10VDC) (on request) Front protection degree: IP65, NEMA4X, NEMA12 Product Description How to order WM30-96 AV5 3 H R2 A2 S1 XX Model Three-phase smart power either for pulse proportional to the analyzer with built-in advanced active and reactive energy being Range code configuration system and LCD measured or/and for alarm outputs. System data displaying. Particularly The instrument can be equipped Power Supply recommended for the with the following modules: RS485/ A Outputs measurement of the main RS232, Ethernet, BACnet-IP, B Outputs electrical variables. WM30 is BACnet MS/TP or Profibus DP Communication based on a modular housing for V0 communication ports, pulse Option panel mounting with IP65 (front) and alarm outputs. Parameters protection degree. Moreover, programming and data reading can the analyzer can be provided be easily performed by means of with digital outputs that can be WM3040Soft. Type Selection Range codes System Power supply A Outputs AV4: 400/690V AC LL 3: balanced and H: 100-240 +/-10% (90 XX: none 1(2)A unbalanced load: to 255) VDC/AC O2: Dual channel static V : 160V to 480V LN LN 3-phase, 4-wire (50/60 Hz) output V : 277V to 830V LL LL 3-phase, 3-wire L: 24-48 +/-15% (20 to R2: Dual channel relay AV5: 400/690V AC LL 2-phase, 3-wire 55) VDC/AC output 5(6)A 1-phase, 2-wire (50/60 Hz) V : 160V to 480V LN LN V : 277V to 830V LL LL Options Communication B Outputs AV6: 100/208V AC LL 5(6)A XX: none XX: none XX: none V : 40V to 144V LN LN S1: RS485/RS232 port A2: Dual channel 20mA V : 70V to 250V LL LL E2: Ethernet / Internet DC output AV7: 100/208V AC LL port V2: Dual channel 10V 1(2)A B1: BACnet (IP) over DC output V : 40V to 144V LN LN Ethernet V : 70V to 250V LL LL B3: BACnet (MS/TP) over RS485 E6: Ethernet/IP port P1: Profibus DP/V0 port Specifications are subject to change without notice WM30 96 DS 310117 1WM30 96 Position of modules and combination Ref Description Main features Part number Pos. A Pos. B Pos. C Inputs/system: AV5.3 1 WM30 AV5 3 H Power supply: H Inputs/system: AV6.3 2 WM30 AV6 3 H Power supply: H Inputs/system: AV4.3 3 WM30 AV4 3 H Power supply: H Inputs/system: AV7.3 4 WM30 AV7 3 H Power supply: H WM30 base provided with display, power supply, measuring inputs Inputs/system: AV5.3 WM30 AV5 3 L Power supply: L Inputs/system: AV6.3 WM30 AV6 3 L Power supply: L Inputs/system: AV4.3 WM30 AV4 3 L Power supply: L Inputs/system: AV7.3 WM30 AV7 3 L Power supply: L 2-channel 5 Dual relay output (SPDT) M O R2 X Alarm or/and pulse output 2-channel 6 Dual static output (AC/DC Opto-Mos) M O O2 X Alarm or/and pulse output 7 Dual analogue output (+20mADC) 2-channel M O A2 X 8 Dual analogue output (+10VDC) 2-channel M O V2 X 9 RS485 / RS232 port module Max. 115.2 Kbps M C 485 232 X 10 Ethernet port module RJ45 10/100 BaseT M C ETH X 11 BACnet-IP port module Based on Ethernet bus M C BAC IP X 12 BACnet-MS/TP port module Over RS485 M C BAC MS X 13 Ethernet/IP Based on Ethernet M C E I X Profibus DP V0 14 Profibus module M C P B X Over RS485 NOTE: The position of the modules shall respect the sequence A-B-C. Possible arrangements are M, M-A, M-B, M-C, M-A-B, M-A-C, M-B-C and M-A-B-C where M is the basic module. It is possible to use the WM30-96 without any additional module as a simple indicator. 2 Specifications are subject to change without notice WM30 96 DS 310117