Motor Controllers
Industrial, 2-Phase Motor Reversing
Type RR2A
Motor reversing
for 3-phase induction motors up to 5.5 kW
Rated operational voltage: Up to 480 VACrms
Built-in interlock function
DC or AC control voltage
Built-in voltage transient protection
LED indication for direction
Isolation: Optocoupler (input-output)
4000 VACrms
Direct copper bonding technology
Product Des cript ion Ordering Key
RR 2 A 40 D 150
This family of 2-Phase Motor at ions (tran sients) by built-in
Motor reversing
Reversing Controller is de - varistors. Fur therm ore, op ti-
Number of phases
signed to control the directon mum re lia bil i ty is achieved by
Switching mode
of 3-phase motors rated up to sol deri ng the output thyristor
Rated operational voltage
5.5 kW. The built-in in ter lock- chips dir ec t ly on to the
Control input type
ing circuitry pre vents the relay ceramic substrate (Di rect
Motor power rating
from switchi ng both di rec- Copper Bondi ng).
tions simultaneously and pro-
duce a short-circuit between The housing is designed to
the 2 phases of the output. A incorporate a temperature
dual col our LED ind i cates di- lim it switch. It is recommend-
rec tionforw ar when green ed to install an appropriate
and di rec tionre vers when semi c on duct or fuse in series
red. The output is pro tect ed with the relay.
from exc ess ive volta ge fluc tu -
Type Selection
Switching mode
Rated ope ra t ion al Control voltage Motor rating
voltage, Ue
A: Zero Switching
40: 400 VACrms D: 10 - 40 VDC 150: 1.5 kW, 2 HP
48: 480 VACrms LA: 90 - 140 VAC 220: 2.2 kW, 3 HP
HA: 180 - 265 VAC 400: 4.0 kW, 5 HP
550: 5.5 kW, 7.5 HP
Selection Guide
Rated op er a- Control
Motor rating
tiona l voltage voltage
1.5 kW 2.2 kW 4.0 kW 5.5 kW
10 to 40 VDC RR2A40D150 RR2A40D400
400 VACrms
90 to 140 VAC RR2A40LA150 RR2A40LA400
180 to 265 VAC RR2A40HA150 RR2A40HA400
480 VACrms 10 to 40 VDC RR2A48D220 RR2A48D550
90 to 140 VAC RR2A48LA220 RR2A48LA550
180 to 265 VAC RR2A48HA220 RR2A48HA550
General Spec if i ca tions
RR2 A 40. .... RR2 A 48 . 220 RR2 A 48 . 550
Operational voltage range 40 to 440 VACrms 40 to 530 VACrms 40 to 530 VACrms
Blocking voltage 1200 V 1200 V 1600 V
p p p
Operational frequency range 45 to 65 Hz 45 to 65 Hz 45 to 65 Hz
Power factor 0.5 @ 400 VACrms 0.5 @ 480 VACrms 0.5 @ 480 VACrms
LED on indication Yes (Green for Forward, Red for Reverse)
Specifications are subject to change without notice (12.10.2017) 1RR2A
Input Spec if i ca tions
RR2A..D... RR2A..LA... RR2A..HA...
Control voltage range 10 - 40 VDC 90 - 140 VAC 180 - 265 VAC
Pick-up voltage 8.5 VDC 70 VAC 170 VAC
Input current range 10 - 20 mADC 7 - 12.5 mAAC 6 - 9.5 mAAC
Drop-out voltage 3.5 VDC 20 VAC 50 VAC
Response time input to output 10 ms 70 ms 100 ms
Time delay
F R, R F Typical 80 ms 200 ms* 200 ms*
Minimum 50 ms 30 ms 30 ms
Maximum 90 ms 300 ms 300 ms
* 300 ms for surrounding temperatures + 60C (140 F)
Output Speci f ic at ions
RR2A40.150 RR2A48.220 RR2A40.400 RR2A48.550
IEC and CCC
rated operational current Ie
(AC-53a) @ Ta = 40C 5 A 5 A 11 A 11 A
IEC rated operational current
Ie (AC-51) @ Ta = 40C 25 A** 25 A** 40 A** 40 A**
Assigned motor rating @ 40C/
UL rating @ 40C 1.5kW / 2HP 2.2kW / 3HP 4.0kW / 5HP 5.5kW / 7.5HP
Overload cycle according to
EN/IEC 60947-4-2 @ 40C 5A: AC53a: 6-6: 100-60 5A: AC53a: 6-6: 100-60 11A: AC53a: 8-3: 100-40** 11A: AC53a: 8-3: 100-40**
Number of starts/hr @ 40C 60 60 40 40
Unlimited starts/hr @40C 4A: AC53a: 6-6: 100 4A: AC53a: 6-6: 100 5A: AC53a: 6-3: 100 5A: AC53a: 6-3: 100
- unlimited** - unlimited** - unlimited** - unlimited**
3.5A: AC53a: 5-6: 100 3.5A: AC53a: 5-6: 100 4A: AC53a: 5-3: 100 4A: AC53a: 5-3: 100
- unlimited* - unlimited* - unlimited* - unlimited*
1.5A: AC53a: 4-6: 100 1.5A: AC53a: 4-6: 100 2A: AC53a: 5-3: 100 2A: AC53a: 5-3: 100
- unlimited - unlimited - unlimited - unlimited
Minimum operational current
Ta = 25C V out = 40Vrms 150 mArms 150 mArms 250 mArms 250 mArms
Off-state leakage current 1 mArms 1 mArms 1 mArms 1 mArms
Non-rep. surge current t=10ms 300A 350A 350A 350A
p p p p
2 2 2 2 2
I t for fusing t= 10ms 525 A s 525 A s 1800 A s 1800 A s
On-state voltage drop 1.6 Vrms 1.6 Vrms 1.6 Vrms 1.6 Vrms
Critical dv/dt off-state 500 V/us 500 V/us 1000 V/us 1000 V/us
* This overload cycle is applicable when device is mounted on heatsink type RHS300
** Applicable only when device is mounted on heatsink type RHS301
Environmental Specifications
Operating temperature -20C to +80C Degree of Protection IP10 (EN/IEC 60529)
(-4F to +176F)
Installation category III
Storage temperature -40C to +100C
Installation Altitude 1000m
(-40F to +212F)
Vibration
Relative humidity <95% non-condensing @40C
Sinusodial (IEC 60068-2-6) 13 to 25Hz: 2.0mm peak
Pollution Degree 3
2
25 to 150Hz: 20m/s
2 Specifications are subject to change without notice (12.10.2017)