Ordering information AC-DC Power Supplies Enclosed type FCA 50 F -24 -O FCA50F 12345 1Series name R 2Output wattage FCA 3Universal input 4Output voltage 5Optional *6 N1 :with DIN rail attach- ment MODEL FCA50F-24 MAX OUTPUT WATTAGE W 50(Peak 160) ( ) DC OUTPUT 24V 2.1 Peak 6.7 A SPECIFICATIONS MODEL FCA50F-24 VOLTAGE V AC187 - 528 1 or DC265 - 746 f ACIN 240V 0.55typ CURRENT A ACIN 480V 0.30typ ( ) FREQUENCY Hz 50/60 47-63 INPUT ACIN 240V 82typ EFFICIENCY % ACIN 480V 78typ ACIN 240V 25typ (At cold start)(At Room Temperature) INRUSH CURRENT A ACIN 480V 50typ (At cold start)(At Room Temperature) LEAKAGE CURRENT mA 0.75max (60Hz, According to IEC60950) VOLTAGE V 24 1 ( ) CURRENT A * 2.1 Peak 6.7 LINE REGULATION mV 96max 0 - 2.1A 150max LOAD REGULATION mV 0 - 6.7A 480max 2 0to+50 * 240max C RIPPLE mVp-p *2 -10-0 320max C OUTPUT *2 0to+50C 680max RIPPLE NOISE mVp-p *2 -10-0C 720max TEMPERATURE REGULATION mV -10 to +50 600max C DRIFT mV *5 100max START-UP TIME ms 800max (ACIN 240V, Io=100%) HOLD-UP TIME ms 10typ (ACIN 240V, Io=100%) OUTPUT VOLTAGE ADJUSTMENT RANGE V 21.6 - 26.4 OVERCURRENT PROTECTION Works over 105% of peak current and recovers automatically PROTECTION CIRCUIT AND OVERVOLTAGE PROTECTION Works at 115 - 140% of rating OTHERS ( ) OPERATING INDICATION LED Green , , , ( ) INPUT-OUTPUT AC3 000V 1minute Cutoff current = 10mA DC500V 50M min At Room Temperature W , , , ( ) ISOLATION INPUT-FG AC2 000V 1minute Cutoff current = 10mA DC500V 50M min At Room Temperature W , , ( ) OUTPUT-FG AC500V 1minute Cutoff current = 100mA DC500V 50M min At Room Temperature W , , ( )( ), , ( , ) OPERATING TEMP. HUMID.AND ALTITUDE -10 to +70C 20 - 90%RH Non condensing Refer to DERATING CURVE 3 000m 10 000feet max , , ( ), , ( , ) STORAGE TEMP. HUMID.AND ALTITUDE -20 to +75C 20 - 90%RH Non condensing 9 000m 30 000feet max ENVIRONMENT 2 VIBRATION *3 10 - 55Hz, 19.6m/s (2G), 3minutes period, 60minutes each along X, Y and Z axis 2 IMPACT *3 196.1m/s (20G), 11ms, once each X, Y and Z axis SAFETY AND AGENCY APPROVALS UL60950-1, C-UL, EN60950-1 NOISE REGULATIONS CONDUCTED NOISE Complies with FCC-A, CISPR11-A, EN55011-A 4 ( ) CASE SIZE/WEIGHT * 50 125 124mm W H D / 640g max X X X X OTHERS COOLING METHOD Convection *1 Peak current for 150ms in a 30seconds period is acceptable. *2 In case of rated input/output(ACIN240-480v/2.1A), either the 20MHz oscilloscope or the ripple noise meter(equivalent to Keisokugiken:RM101) is used. *3 Option with DIN rail attachment(N1) is only for direction X(refer to sec4.2 in manual). *4 Depth of power supply is 132mm with DIN rail attachment. *5 Drift is the change in DC output for an eight hour period after a half-hour warm-up at 25C, with the input voltage held constant at the rated input/output. *6 Please contact us about safety approvals for the model with option. FCA-2FCA50F External view FCA 13max 50 30 ( ) 11.5 LED Voltage Adjust DIN Rail Attachment FCA50F-24 FCA50F-24-N1 only +V + - -V FG FG AC(L) AC(L) Spacer AC(N) AC(N) FCA50F-24-N1 only Terminal ( ) 7 Block (M4) 16 (15.5) 124 (8) (22) ( ) 24.5 ( ) 12 119 3-M3 Mounting Hole 3.8 Weight : 640g or less Tolerance : 1 Mounting torque : 0.6Nm (6.3kgfcm)max 0.5 Dimensions in mm. 71.1 Terminal Block Cover 45.9 18max Performance data STATIC CHARACTERISTICS RISE TIME & FALL TIME 24 DC Output 25 Output Voltage 22 20 20 100 18 15 Io=100% 16 75 Io=50% 10 Io=100% 14 Ripple 5 12 50 10 0 AC Input 8 25 ACIN 480V 150 160 170 180 190 200 210 220 230 240 250 50ms/DIV INPUT VOLTAGE (AC 100V) V 60Hz OVERCURRENT CHARACTERISTICS INRUSH CURRENT 26 Input Voltage AC480V Frequency 60Hz 24 Load 100% Input voltage AC480V 22 20 18 16 14 12 2468 10 12 50ms/DIV OUTPUT CURRENT A FCA-3 OUTPUT VOLTAGE V OUTPUT VOLTAGE V (110) 50 (102) 44.5 ( ) 34 13 10 25.4 RIPPLE mVp-p OUTPUT VOLTAGE V 20A/DIV 125 0.5 12.7 25.4 ( ) 116 (72) 7 ( ) 35.5