Ordering information
AC-DC Power Supplies Open Frame/Enclosed type
LDA 10 F -5 -O
LDA10F
12345
1Series name
R
Recommended EMI/EMC Filter
2Output wattage
NAC-06-472
3Universal input
4Output voltage
5Optional *2
C :with Coating
G :Low leakage current
S :with Chassis
SN:with Chassis & cover
High voltage pulse noise type : NAP series
Y :with Potentiometer
Low leakage current type : NAM series
*The EMI/EMC Filter is recommended
*to connect with several devices.
MODEL LDA10F-3 LDA10F-5 LDA10F-12 LDA10F-15 LDA10F-24
MAX OUTPUT WATTAGE[W] 6 10 10.8 10.5 12
DC OUTPUT 3V 2.0A 5V 2.0A 12V 0.9A 15V 0.7A 24V 0.5A
SPECIFICATIONS
MODEL LDA10F-3 LDA10F-5 LDA10F-12 LDA10F-15 LDA10F-24
VOLTAGE[V] AC85 - 264 1 or DC110 - 370
f
( )
ACIN 100V 0.25typ Io=100%
CURRENT[A]
( )
ACIN 200V 0.16typ Io=100%
LDA
FREQUENCY[Hz] 47 - 440 or DC
INPUT
EFFICIENCY[%] 68typ 72typ 74typ 74typ 78typ
( )( )
ACIN 100V 15typ Io=100% At cold start
INRUSH CURRENT[A]
( )( )
ACIN 200V 30typ Io=100% At cold start
( , , , )
LEAKAGE CURRENT[mA] 0.75max 60Hz According to UL CSA VDE and DEN-AN
VOLTAGE[V] 3 5 12 15 24
CURRENT[A] 2 2 0.9 0.7 0.5
LINE REGULATION[mV] 20max 20max 48max 60max 96max
LOAD REGULATION[mV] 40max 40max 100max 120max 150max
0to+50 80max 80max 120max 120max 120max
C
RIPPLE[mVp-p]
-10-0 140max 140max 160max 160max 160max
C
0to+50 120max 120max 150max 150max 150max
C
OUTPUT RIPPLE NOISE[mVp-p]
-10-0 160max 160max 180max 180max 180max
C
TEMPERATURE REGULATION[mV] 50max 50max 120max 150max 240max
1
DRIFT[mV] * 20max 20max 48max 60max 96max
( , )
START-UP TIME[ms] 200max ACIN 100V Io=100%
( , ) ( , ) ( , )
HOLD-UP TIME[ms] 10typ ACIN 85V Io=100% 20typ ACIN 100V Io=100% 100typ ACIN 200V Io=100%
( , , , )
OUTPUT VOLTAGE ADJUSTMENT RANGE[V] 2.85 - 3.6 Fixedwhich can be adjusted the output is available as option :5 12 15 24Vt10%
OUTPUT VOLTAGE SETTING[V] xx 4.9 - 5.3 11.5 - 12.5 14.4 - 15.6 23.0 - 25.0
OVERCURRENT PROTECTION Works over 105% of rating and recovers automatically
OVERVOLTAGE PROTECTION 4.00V min Works over 115% of rating, by zener diode clamping
PROTECTION
CIRCUIT AND OPERATING INDICATION Not provided
OTHERS
REMOTE SENSING Not provided
REMOTE ON/OFF Not provided
, , , ( )
INPUT-OUTPUT AC3 000V 1minute Cutoff current = 10mA DC500V 50M min At Room Temperature
W
, , , ( )
ISOLATION INPUT-FG AC2 000V 1minute Cutoff current = 10mA DC500V 50M min At Room Temperature
W
, , ( )
OUTPUT-FG AC500V 1minute Cutoff current = 100mA DC500V 50M min At Room Temperature
W
, , ( )( ) , ( , )
OPERATING TEMP. HUMID.AND ALTITUDE -10 to +60 20 - 90%RH Non condensing Refer to DERATING CURVE 3 000m 10 000feet max
C
, , ( ) , ( , )
STORAGE TEMP. HUMID.AND ALTITUDE -20 to +75 20 - 90%RH Non condensing 9 000m 30 000feet max
C
ENVIRONMENT
2
, ( ), , ,
VIBRATION 10 - 55Hz 19.6m/s 2G 3minutes period 60minutes each along X Y and Z axis
2
( ), , ,
IMPACT 196.1m/s 20G 11ms once each X Y and Z axis
SAFETY AND
, , ,
AGENCY APPROVALS UL60950-1 EN60950-1 EN50178 CSA C22.2 No.60950-1 Complies with DEN-AN and IEC60950-1
NOISE
CONDUCTED NOISE Complies with FCC-B, CISPR22-B, EN55022-B, VCCI-B
REGULATIONS
CASE SIZE/WEIGHT 50 21 105mm (W H D) /75g max (without chassis and cover)
X X X X
OTHERS
COOLING METHOD Convection
*1 Drift is the change in DC output for an eight hour period after a half-hour warm-up at 25C, with the input voltage held constant at the rated input/output.
*2 Please contact us about safety approvals for the model with option.
* Avoid prolonged use under over-load.
* Series/Parallel operation with other model is not possible.
* Derating is required when operated with chassis and cover.
LDA-2LDA10F
External view
LDA
Performance data
( ) ( )
STATIC CHARACTERISTICS LDA10F-5 RISE TIME & FALL TIME LDA10F-5
( )
OVERCURRENT CHARACTERISTICS LDA10F-5 DERATING CURVE
LDA-3