DIN Rail Mount Datasheet GNR 90mm Series Current rating: 25 amps Output voltage rating: 48-600 VAC Direct Bond Copper (DBC) Substrate LED input status indicator UL 508 Endurance Rating for Enhaced Reliability UL/CSA Approved, CE Compliant Built-in overvoltage protection DIN Rail or Panel Mount Zero voltage or Instantaneous turn-on output PRODUCT SELECTION Control Voltage Zero-Crossing Random Turn-on 4-32 VDC GNR25DCZ GNR25DCR 90-140 VAC GNR25BCZ 180-280 VAC GNR25ACZ (1) OUTPUT SPECIFICATIONS Description GNR25 Operating Voltage (47-440Hz) Vrms 48-600 Transient Overvoltage Vpk, t=1 min. 1100 Maximum Load Current Arms 25 Minimum Load Current Arms 0.1 Maximum Off-State Leakage Current Rated Voltage mArms 0.25 Static Off-State dv/dt ( V/sec, Ta=25C) (2) 500 1 Second Surge Current (Apk Ta=25C) 50/60 Hz 130 Forward Voltage Drop (Vpk max, Ta=25C) 1.50 Maximum Surge Current (50/60 Hz, 1 cycle) Apk 286/300 Maximum I t for Fusing (50/60Hz, 1/2 cycle ) A sec 410/374 HP Ratings at 240V / FLA Arms 1/4.2 HP Ratings at 380V / FLA Arms 2/4.3 HP Ratings at 480V / FLA Arms 3/4.8 Min/Max stranded wire 16/8 AWG Min/Max solid wire 16/10 AWG (1) INPUT SPECIFICATIONS Description GNR25DCX GNR25BCZ GNR25ACZ Control Voltage Range (3) 4.0-32 VDC 90-140 Vrms 180-280 Vrms Minimum Turn-On Voltage 4.0 VDC 90 Vrms 180 Vrms Must Turn-Off Voltage 1.0 VDC 10 Vrms 10 Vrms Minimum Input Current (for on-state) 22 mA 15 mArms 19 mA Maximum Input Current 28 mA 19 mArms 24 mA Input Resistance Current Regulated Current Regulated Current Regulated Maximum Turn-Off Time msec 1/2 Cycle 20 20 Maximum Turn-On Time msec (4) 1/2 Cycle 30 30 Min/Max stranded/solid wire 24/16 AWG 24/16 AWG 24/16 AWG FDE-07-01 REV. A Do not forget to visit us at: www.crydom.com Copyright 2020 Crydom Inc. Specifications subject to change without notice.GNR25DCZ DIN Rail Mount Datasheet (1) GENERAL SPECIFICATIONS Description Parameters Ambient Operating Temperature Range (3) -20 to 80C Ambient Storage Temperature Range -40 to 100 C 4000 Vrms Dielectric Strength, Input to Output (50/60Hz) Dielectric Strength, Input/Output to Ground (50/60Hz) 2500 Vrms Maximum Capacitance, Input/Output 8 pF Housing Material UL 94V0 (self extinguishing) Input Status Indicator Green LED Weight (typical) 21.17 oz (600g) Recommended Terminal Screw Torque Range: 5.0-6.0 in-lb (0.6-0.7 Nm) GENERAL NOTES (1) All parameters at 25C unless otherwise specied. (2) Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1 (3) For 180-280 VAC Control. Maximum Ambient operating temperatures is 60C. (4) Turn-on time for Instantaneous version (R sufx) is 0.1 msec (for DC control only). For additional information or specic questions, contact Crydom Technical Support. (1) MECHANICAL SPECIFICATIONS Tolerances: 0.02 in / 0.5 mm All dimensions are in: inches millimeters 3.54 90.0 4.86 3.26 123.4 82.8 3.59 3.82 3.47 91.2 97.0 88.1 GNR25DCZ 0.18 4.5 3.26 82.8 Do not forget to visit us at: www.crydom.com Copyright 2020 Crydom Inc. Specifications subject to change without notice.