TECHNICAL DATASHEET CliQ DIN Rail Power Supply 24 V 60 W 1 Phase / DRP024V060W1AZ Highlights & Features Universal AC input voltage range Power will not de-rate for the entire input voltage range Power Boost of 150% for 3 seconds Rugged and compact design (Vibration 5 G, Shock 30 G) Conforms to harmonics current IEC/EN 61000-3-2, Class A Wide operating temperature range -20C to 80C Overvoltage / Overcurrent / Over Temperature / Short Circuit Protections Certified according to IEC/EN/UL 62368-1 Safety Standards CB Certified for worldwide use Model Number: DRP024V060W1AZ Unit Weight: 0.33 kg (0.73 lb) Dimensions (L x W x D): 120.6 x 32 x 113 mm (4.75 x 1.26 x 4.45 inch) General Description The DRP024V060W1AZ is part of the CliQ DIN rail power supply series from one of the worlds leading power supply companies, Delta Electronics Group, offers state-of-the-art designs made to withstand harsh industrial environments. Its rugged plastic casing has a compact body at only 32 mm, which is both shock and vibration resistant according to IEC 60068-2 standard. The DRP024V060W1AZ operates within a wide temperature range from -20C to +80C and universal AC input voltage range from 85 Vac to 264 Vac, the power will not de-rate for the entire input voltage range value. The single phase power supply unit includes overvoltage, overcurrent, over temperature and short circuit protections. The feature built-in Power Boost of 150% for 3 seconds enables reserve power to be always available for reliable startup of loads with high inrush current, thus eliminating the need of a more expensive power supply unit at higher power rating. Model Information CliQ DIN Rail Power Supply Model Number Input Voltage Range Rated Output Voltage Rated Output Current DRP024V060W1AZ 85-264 Vac (120-375 Vdc) 24 Vdc 2.50 A Model Numbering DR P 024V 060W 1 A Z DIN Rail Power Supply Output Voltage Output Power Single Phase CliQ Series Plastic Case All parameters are specified at 25C ambient and AC input unless otherwise indicated. 1 www.DeltaPSU.com (September 2021, Rev. 10) TECHNICAL DATASHEET CliQ DIN Rail Power Supply 24 V 60 W 1 Phase / DRP024V060W1AZ Specifications Input Ratings / Characteristics Nominal Input Voltage 100-240 Vac Input Voltage Range 85-264 Vac Nominal Input Frequency 50-60 Hz Input Frequency Range 47-63 Hz DC Input Voltage Range* 120-375 Vdc Input Current < 1.10 A 115 Vac, < 0.70 A 230 Vac Efficiency at 100% Load > 86.0% 115 Vac, > 87.0% 230 Vac Max Power Dissipation 0% load < 0.6 W 115 Vac & < 1.2 W 230 Vac 100% load < 10 W 115 Vac & 230 Vac Max Inrush Current (Cold Start) < 40 A 115 Vac, < 80 A 230 Vac Leakage Current < 1 mA 240 Vac *Safety approval according to IEC/EN/UL 60950-1 and IEC/EN/UL 62368-1. Output Ratings / Characteristics** Nominal Output Voltage 24 Vdc Factory Set Point Tolerance 24 Vdc 2% Output Voltage Adjustment Range 22-28 Vdc Output Current 2.50 A (continuously operating at 24 V) 3.75 A (Power Boost for 3 seconds at 24 V, refer to the details in the Functions section) Output Power 60 W (continuously operating at 24 V) 90 W (Power Boost for 3 seconds at 24 V, refer to the details in the Functions section) Line Regulation < 0.5% ( 85-264 Vac input, 100% load) Load Regulation < 1.0% ( 85-264 Vac input, 0-100% load) PARD*** (20 MHz) < 240 mVpp Rise Time < 100 ms nominal input (100% load) Start-up Time < 2,500 ms nominal input (100% load) Hold-up Time > 20 ms 115 Vac (100% load) > 125 ms 230 Vac (100% load) Dynamic Response 5% 85-264 Vac input, 10-90% load (Overshoot & Undershoot O/P Voltage) (Slew Rate: 0.1 A/s, 50% duty cycle 5 Hz to 1 KHz) Start-up with Capacitive Loads 8,000 F Max **For power de-rating from 50C to 80C, see power de-rating on page 3. ***PARD is measured with an AC coupling mode, 5 cm wires, and in parallel with 0.1 F ceramic capacitor. All parameters are specified at 25C ambient and AC input unless otherwise indicated. 2 www.DeltaPSU.com (September 2021, Rev. 10)