TECHNICAL DATASHEET CliQ II DIN Rail Power Supply 24 V 240 W 3 Phase / DRP024V240W3B Highlights & Features Universal AC input voltage range Power will not de-rate for the entire input voltage range Power Boost of 150% for 5 seconds Full corrosion resistant aluminium casing Conforms to harmonic current IEC/EN 61000-3-2, Class A Extreme low temperature cold start at -40C Conformal coating on PCBAs to protect against common dust and chemical pollutants Hazardous Locations approval to ATEX and Class I, Div 2 (DRP024V240W3BA) Certified according to IEC/EN/UL 62368-1 Safety Standards CB Certified for worldwide use Model Number: DRP024V240W3B Unit Weight: 0.89 kg (1.96 lb) Dimensions (L x W x D): 121 x 70 x 117.3 mm (4.76 x 2.76 x 4.62 inch) General Description The CliQ II 3-phase DIN rail power supply series offers output voltage of 24 V. These products are encased in rugged yet lightweight full aluminium body that can withstand shock and vibration according to IEC 60068-2 standard. The series of 3-phase products can operate over a wide temperature range of -25C to +80C. These products also feature universal AC input voltage range for 3-phase from 320 Vac to 600 Vac or 2-phase from 360 Vac to 600 Vac, and the power will not de-rate throughout the entire range. Another great feature is the conformal coating on the PCBA which allows selected models to be certified to ATEX and Class I, Div 2 for use in hazardous locations. The design conforms to harmonic current emission IEC/EN 61000-3-2, Class A. Model Information CliQ II DIN Rail Power Supply Model Number Input Voltage Range Rated Output Voltage Rated Output Current DRP024V240W3B 3 x 320-600 Vac (3-Phase) or 24 Vdc 10.0 A 2 x 360-600 Vac (2-Phase) Model Numbering DR P 024V 240W 3 B DIN Rail Power Supply Output Voltage Output Power Three Phase CliQ II Series A - Metal Case, with Class I, Div 2 N - Metal Case, without Class I, Div 2 All parameters are specified at 25C ambient and AC input unless otherwise indicated. 1 www.DeltaPSU.com (June 2021, Rev. 07) TECHNICAL DATASHEET CliQ II DIN Rail Power Supply 24 V 240 W 3 Phase / DRP024V240W3B Specifications Input Ratings / Characteristics Nominal Input Voltage 3 x 400-500 Vac 1) Input Voltage Range 3 x 320-600 Vac (3-Phase) or 2 x 360-600 Vac (2-Phase) Nominal Input Frequency 50-60 Hz Input Frequency Range 47-63 Hz 2) DC Input Voltage Range 450-800 Vdc Input Current < 0.75A 3 x 400 Vac, < 0.65 A 3 x 500 Vac Efficiency at 100% Load > 91.0% 3 x 400 Vac & 3 x 500 Vac Max Power Dissipation 0% load < 6.5 W 3 x 400 Vac & 3 x 500 Vac 100% load < 23.0 W 3 x 400 Vac & 3 x 500 Vac Max Inrush Current (Cold Start) < 40 A 3 x 400 Vac & 3 x 500 Vac Leakage Current < 3.5 mA 500 Vac 1) Fulfills test conditions for up to 600 Vac maximum. 2) Fulfills the test conditions for this range. 3) Output Ratings / Characteristics Nominal Output Voltage 24 Vdc Factory Set Point Tolerance 24 Vdc 2% Output Voltage Adjustment Range 24-28 Vdc Output Current 10.0 A (continuously operating at 24 V) 15.0 A (Power Boost for 5 seconds at 24 V, refer to the details in the Functions section) Output Power 240 W (continuously operating at 24 V) 360 W (Power Boost for 5 seconds at 24 V, refer to the details in the Functions section) Line Regulation < 0.5% ( 3 x 320-600 Vac input, 100% load) Load Regulation < 1.0% ( 3 x 320-600 Vac input, 0-100% load) 4) PARD (20 MHz) < 150 mVpp Rise Time < 100 ms nominal input (100% load) Start-up Time < 1,000 ms nominal input (100% load) Hold-up Time > 20 ms 3 x 400 Vac, > 40 ms 3 x 500 Vac (100% load) Dynamic Response 5% 3 x 320-600 Vac input, 0-100% load (Overshoot & Undershoot O/P Voltage) (Slew Rate: 0.1 A/s, 50% duty cycle 5 Hz to 1 KHz) Start-up with Capacitive Loads 10,000 F Max 3) For power de-rating from 50C to 80C, see power de-rating on page 3. 4) PARD is measured with an AC coupling mode, 5 cm wires, and in parallel with 0.1 F ceramic capacitor & 47 F electrolytic capacitor. All parameters are specified at 25C ambient and AC input unless otherwise indicated. 2 www.DeltaPSU.com (June 2021, Rev. 07)