Functionelement,MSC-DEA/XTSEA Partno. PKE-SWD-32 Articleno. 126895 Deliveryprogramme Product range SmartWire-DT slave Basic function Motor protection Motor protection for heavy starting duty Product range Accessories Accessories SmartWire-DT PKE module (motor-starter combinations) Function For connecting the motor-starter combination to SmartWire-DT,expande 24 VDC version (MSC-DEA) up to 15 kW. Description Surface-mounting to contactors. One module per contactor and PKE necessary. Additional SWD contactor module required fir actuation of reversing starter. 1 electrical interlock for the surface mounting of reversing starters. 1-0-A switch for manual or automatic operation. Selectable overload relay function (ZMR) for switching off the contactor on overload. Wiring sets DILM 12-XRL and PKZM0-XRM12 cannot be used. Messages Switch position contactor/PKE/1-0-A switch Motor current in % Thermal motor image in % Trip indications (Overload, Short-circuit,...) Set value of overload releases Set time lag (CLASS) Part no. of trip block Commands Contactor actuation Activation Overload relay function (ZMR) Information about equipment supplied Connecting cable between module and trip block PKE-XTUA- included as standard. For use with DILM(C)7 - DILM(C)32 MSC-DEA Connection to SmartWire-DT yes Connection type Push in terminals Notes Take into account the max. current consumption of the contactor coils per SmartWire-Darwin line. A2 connections must not be bridged. Wiring sets DILM 12-XRL and PKZM0-XRM12 cannot be used. Additional SWD contactor module required fir actuation of reversing starter. Approvals NA Certification Request filed for UL and CSA Partno. PKE-SWD-32 General Standards IEC/EN 61131-2 EN 50178 IEC/EN 60947 Dimensions (W x H x D) mm 45 x 38 x 76 Weight kg 0.04 Mounting on DILM7DILM32 Mounting position as DILM7 to DILM32 Ambientconditions,mec hanic al Protection type (IEC/EN 60529, EN50178, VBG 4) IP20 Vibrations (IEC/EN 61131-2:2008) Constant amplitude 3,5 mm Hz 5 - 8.4 Constant acceleration 1 g Hz 8.4 - 150 Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 Impacts 9 g/11 ms Drop to IEC/EN 60068-2-31 Drop mm 50 height Free fall, packaged (IEC/EN 60068-2-32) m 0.3 Electromagneticcompatibility(EMC) Overvoltage category II Pollution degree 2 06/25/2012 HPL-ED2012 V1.1 EN 1 / 4Electrostatic discharge (IEC/EN 61131-2:2008) Air discharge (Level 3) kV 8 Contact discharge (Level 2) kV 4 Electromagnetic fields (IEC/EN 61131-2:2008) 80 - 1000 MHz V/m 10 1.4 - 2 GHz V/m 3 2 - 2.7 GHz V/m 1 Radio interference suppression (SmartWire-DT) EN 55011 Class A Burst (IEC/EN 61131-2:2008, Level 3) CAN/DP bus cable kV 1 SmartWire-DT cables kV 1 Radiated RFI (IEC/EN 61131-2:2008, Level 3) V 10 Climaticenvironmentalconditions Operating ambient temperature (IEC 60068-2) C Ambient temperature C -25 - +60 Condensation Take appropriate measures to prevent condensation Storage C -30 - +70 relative humidity, non-condensing (IEC/EN 60068-2-30) % 5 - 95 SmartWire-DTnetwork Station type SmartWire-DT slave Address allocation automatic SmartWire-DT status LED LED green/orange Connections Plug, 8-pole Connection External device plug SWD4-8SF2-5 Current consumption mA 58 Pick-up power for DILM 7-9 W 3 for DILM 12-15 W 4.5 for DILM 17-38 W 12 Pick-up current for DILM 7-9 mA 125 for DILM 12-15 mA 188 for DILM 17-38 mA 500 Holding power for DILM 7-9 W 3 for DILM 12-15 W 4.5 for DILM 17-38 W 0.5 Holding current for DILM 17-38 mA 21 for DILM 12-15 mA 188 for DILM 7-9 mA 125 Modeparameter Manual/automatic mode yes Setting Rotary switch Connectionauxiliarycontact Cable length m 2.8 Connection type Push in terminals Terminalc apac ities 2 Solid 0.2 - 1.5 (AWG 24 - 16) mm 2 Flexible with ferrule 0.25 - 1.5 mm Tec hnic aldataETIM4.0 Radiostandard Bluetooth No Short-circuit protective device, outputs available No Type of voltage (input voltage) DC 06/25/2012 HPL-ED2012 V1.1 EN 2 / 4