Switches & Pilot Lights Signaling Lights Relays & Sockets Timers Contactors Terminal Blocks Circuit Breakers
GE1A
Timers
GE1A Series ON Delay Timers
Single Function
Key features:
DPDT or SPDT + instantaneous SPDT
8-pin, octal base
Repeat error 0.2% maximum
Large, clear knob for easy setting
Instant monitoring of operational status by LED indicators
UL, c-UL Listed
File No. E55996
Specifications
24V AC/DC
Rated Operating Voltage 110 to 120V AC
220 to 240V AC
AC: 85 to 110%
Voltage Tolerance
DC: 90 to 110%
240V AC/5A
Contact Rating
24V DC/5A
Contact Form DPDT or SPDT+ instantaneous SPDT
Repeat Error 0.2% 10msec maximum
Voltage Error 0.5% 10msec maximum
Temperature Error 3% maximum
Setting Error 10% maximum
Reset Time 0.1 sec maximum
Insulation Resistance 100M minimum (500V DC megger)
Between power and output terminals: 2,000V AC, 1 minute
Dielectric Strength
Between contact circuits: 750V AC, 1 minute
Damage limits: Amplitude 0.75mm, 10 to 55 Hz
Vibration Resistance
Operating extremes: Amplitude 0.5mm, 10 to 55 Hz
2
Shock Resistance Damage limits: 500m/s (Approx. 50G)
24V AC type: 1.6 VA
24V DC type: 1.0W
GE1A-B
110V AC type: 3.8 VA
220V AC type: 7.7 VA
Power
Consumption
24V AC type: 2.0 VA
24V DC type: 0.8W
GE1A-C
110V AC type: 3.5 VA
220V AC type: 8.0 VA
Electrical Life 100,000 operations minimum (at full rated load)
B type: 10,000,000 operations minimum, C type: 5,000,0000
Mechanical Life
operations minimum
Operating Temperature 10 to +55C (without freezing)
Operating Humidity 35 to 85% RH (without freezing)
1705151136
800-262-IDEC (4332) USA & Canada
973GE1A
Timers
Part Numbering List
Mode of Operation Contact Output Rated Voltage Time Range Complete Part Number
220-240V AC GE1A-B10HA220
110-120V AC 0.1s - 10h GE1A-B10HA110
24V AC/DC GE1A-B10HAD24
Delayed SPDT +
Instantaneous SPDT
220-240V AC GE1A-B30HA220
110-120V AC 0.3s - 30h GE1A-B30HA110
24V AC/DC GE1A-B30HAD24
24V DC/120V AC, 5A
ON-Delay
240V AC, 5A
220-240V AC GE1A-C10HA220
110-120V AC 0.1s - 10h GE1A-C10HA110
24V AC/DC GE1A-C10HAD24
Delayed DPDT
220-240V AC GE1A-C30HA220
110-120V AC 0.3s - 30h GE1A-C30HA110
24V AC/DC GE1A-C30HAD24
Timing Diagrams/Schematics
GE1A-B GE1A-C
Delayed SPDT + Instantaneous SPDT Delayed DPDT
Operation
Mode Selection
Item Terminal Number Operation Item Terminal Number Operation
Set Time Set Time
ON-Delay 1
Power 2 - 7 (8p) Power 2 - 7 (8p)
5 - 8 (8p) (NC) 5 - 8 (8p) (NC)
MODE
Delayed Delayed
Contact Contact
6 - 8 (8p) (NO) 6 - 8 (8p) (NO)
A
1 - 4 (NC) POWER
Instantaneous
Indicator
Contact
1 - 3 (NO) OUT
POWER
Indicator
OUT
Note: Terminals 1, 3, and 4 are for the instantaneous contact
1705151136
www.IDEC.com
974
Circuit Breakers Terminal Blocks Contactors Timers Relays & Sockets Signaling Lights Switches & Pilot Lights