time delay relays plug-in PROGRAMMABLE MULTI-RANGE ON DELAY, INTERVAL ON & FLASHER tm TR-6 Series Time Ranger The TR-6 Series offers the exible programmability of a multi-range time delay relay together with a universal input voltage. These products provide an easy method to select one of 16 time ranges between 0.05 seconds and 100 hours using a rotary switch. The actual time delay is then set by using the potentiometer to adjust within the selected time range. INPUT VOLTAGE CATALOG WIRING/ FUNCTION 50/60Hz. NUMBER SOCKETS ON DELAY 24-240V AC & TR-6022U 8 PIN OCTAL 12-125V DC 70169-D Each unit has 16 timing ranges built-in covering 0.05 seconds-100 INTERVAL ON 24-240V AC & TR-6052U hours 12-125V DC Selecting a range is easy using a rotary switch (no math is required or DIP switches to set) FLASHER 24-240V AC & TR-6082U (OFF 1st) 12-125V DC DIAGRAM 1 Universal input voltage: 24-240V AC & 12-125V DC Uses industry-standard 8 pin FLASHER 24-240V AC & TR-6092U octal sockets (ON 1st) 12-125V DC 10A DPDT output contacts can handle most pilot duty & fractional HP loads See De nitions of Timing Functions. Timing Ranges Select one of the 16 built-in time ranges by setting the rotary switch per a chart on the unit (see below) and then adjust within that range using the knob on top. Dial Setting Timing Range A 0.05 - 0.5 Sec. B 0.1 - 1 Sec. C 0.5 - 5 Sec. D 1 - 10 Sec. E 3 - 30 Sec. F 6 - 60 Sec. G 0.2 - 2 Min. H 0.5 - 5 Min. I 1 - 10 Min. J 3 - 30 Min. K 6 - 60 Min. L 0.2 - 2 Hr. M 0.5 - 5 Hr. N 1 - 10 Hr. O 2.4 - 24 Hr. P 10 - 100 Hr. 800.238.7474 Sockets & Accessories available www.macromatic.com sales macromatic.com Build your Time Delay Relays with the Online Product Builder 28time delay relays plug-in PROGRAMMABLE MULTI-RANGE tm TR-6 Series Time Ranger Application Data Voltage Tolerance: Triggering Off Delay, Single Shot or Watchdog Units: AC Operation: 20.4 264V at 50/60 Hz Timing sequence must be initiated only after input voltage is DC Operation: 10.2 137.5V applied to unit. Minimum required trigger switch closure time is 0.1 seconds. Load (Burden): Maximum of 3 VA for all voltages Compatibility: Using a solid state switch to initiate the time sequence is Setting Accuracy: acceptable. See www.macromatic.com/leakage or contact Maximum Setting (Adjustable): +5%, -0% Macromatic for information regarding leakage current limits and Minimum Setting (Adjustable): +0%, -50% other solid state design considerations. Repeat Accuracy (constant voltage and temperature): Output Contacts: +0.1% or +50ms, whichever is greater DPDT 10A 240V AC/30V DC, Reset Time: 1/2HP 120/240V AC (N.O.), 1/3HP 120/240V AC (N.C.) Functions Triggered with Input Voltage: 0.1 Seconds B300 & R300 (N.O.) AC15 & DC13 Functions Triggered with Control Switch: 0.04 Seconds Life: Start-up Time: Mechanical: 10,000,000 operations (Time from when power is applied until unit is timing) Full Load: 100,000 operations 0.05 Seconds Approvals: Maintain Function Time: Low Voltage & File E109466 (Time unit continues to operate after power is removed) EMC Directives 0.01 Seconds EN60947-1, EN60947-5-1 Temperature: o o o o Operating: -28 to 65 C (-18 to 150 F) o o o o Storage: -40 to 85 C (-40 to 185 F) Dimensions TR-602, TR-605, TR608, TR609, TR-613, TR-615, TR-616, TR-631-TR-651, TR-661 & TR-665 TR-617, TR-618 & TR-619 All Dimensions in Inches (Millimeters) 800.238.7474 www.macromatic.com sales macromatic.com 31