Product Data Sheet EPBAP81 Enclosed Power Terminal Block 760 Amps 600 Volts AC/DC Wire Range 2 2 Line: (2) 500 kcmil - 4 AWG (253 mm - 21 mm ) 2 2 Load: (2) 500 kcmil - 4 AWG (253 mm - 21 mm ) Electrical Ratings 760 Amps 600V per UL 1953 & CSA 22.2 No.158, class B & C requirements 1000 V AC/DC per IEC 60947-7-1 (CE) Short circuit current ratings (SCCR): See SCCR section below for speci cations. CU7AL - 75C connector terminal rating with copper or aluminum wire Touch protection: IP-20 (IEC 60529) Factory & Field Wiring Agency Compliance UL - UL Listed Terminal Block, Evaluated to UL 1953, File No.QPQS.E309401 CSA - certifed to C22.2 No. 158, File No. LR19766 (wire classes B & C only) CE compliant to IEC 60947-7-1 Material Information Insulator base: Thermoplastic Flammability rating of insulator base UL94V0 Insulator base temperature rating: -40C to 125C (UL RTI) Connector: aluminum, tin plated Terminal set screws: aluminum, tin plated Connector mounting screw: steel, zinc plated RoHS compliant A Regal Brand www.marathonsp.com 1Termination Speci cations Wires / Wire Size 1 Line & Load Side Torque Wire Class (UL) (CU Stranded) Terminal 42.3 Nm 500 kcmil - 4 AWG 1 B, C (375 lbfin) 42.3 Nm 350 kcmil - 2 AWG 1 B, C, G, H, I (DLO) (375 lbfin) Aluminum stranded wire range: 500 kcmil - 4 AWG Wire strip length: 1 1/2 in. (38mm) IP-20 protection: 500 kcmil - 4/0 Terminal screw drive: 8 mm hex 1 For information on copper stranded wire classes please visit: