20kA High Performance Surge Protection Device SPD-20HP series IP663 +-= <+= 77 3 .- 4 ( , 00 % & - 5 ( ( ) */ + + , 6 - ( , .- +// 0 0 .- 1 ( 2* +-= <+ + 1 - 1 0= 1 ( .- 0 0 1 1 > ( 1 > = 0 1 1 0 0 1 0 1 = 0= 0 1 1 > , +-= <+ 1 ( .- 1 +- ( ) * ) * * + 1 ). This lower clamping + voltage can also help to extend the life-time of the luminaire. It also features a built-in LED indicator that notifies when replacement of the module is needed. 77 8 9 77* : & 8 7 9 & * : < + 0 ) File Name:SPD-20HP-SPEC 2018-08-09 20kA High Performance Surge Protection Device SPD-20HP series SPECIFICATION MODEL SPD-20HP-277S SPD-20HP-480S OPERATING VOLTAGE 120 ~ 277VAC 50/60Hz 347 ~ 480VAC 50/60Hz MCOV/U Note.1 C 320VAC 510VAC (MAX. CONTINUOUS OPERATING VOLTAGE) CONTINUOUS CURRENT (max.) 5A 5A L-N: 810V L-N: 1400V MLV Note.2 L-G: 1560V L-G: 1560V (MEASURED LIMITING VOLTAGE) N-G: 1570V N-G: 1570V L-N: 1000V U Note.3 P ----- L-G/PE: 3800V (VOLTAGE PROTECTION LEVEL) N-G/PE: 2900V I (NOMINAL DISCHARGE CURRENT) Note.4 10kA, 8/20s n I (MAX. DISCHARGE CURRENT) Note.5 20kA, 8/20s max. OPERATING TEMPERATURE -40 ~ +75 SAFETY STANDARDS UL1449(Fourth Edition), EN61643-11 approved UL1449(Fourth Edition) approved DIMENSION 71.6*67.7*32 (L*W*H) PACKING 0.233Kg/Unit 1.67Kg/one box(6pcs) 9Kg/carton(including 5 boxs) 0.243Kg/Unit 1.73Kg/one box(6pcs) 9.3Kg/carton(including 5 boxs) NOTE: > ):3* : Maximum Continuous Operating Voltage - maximum r.m.s. voltage that could be continuously applied to the SPD. : . MLV: UL1449 Measured limiting voltage the highest value of residual voltage measurements during the application of impuls 0 & ) an average voltage value of 15 impulses. . U : IEC 61643-11 Voltage protection level the highest value of residual voltage measurements during the application of impulses of 8/20 + nominal discharge current()In a rounding voltage value of maximum measurement. . Nominal Discharge Current I (A): The nominal discharge current is a measure of the SPDs endurance capability 15 impulses of discharge current uses the 8/20s current waveform. . Maximum Discharge Current I (A): The maximum discharge current is a measure of the SPDs maximum capability single impulse of discharge current uses the 8/20s current waveform. All Devices pass maximum discharge current with possible, safe opening of thermal disconnect. SPECIFICATION for SPD-20HP-277S only SPECIFICATION Value Condition Temporary Overvoltage (V) 403VAC LV System Fault for TN power Grid TOV UT t = 5s T Temporary Overvoltage (V) 529VAC LV System Fault for TN power Grid TOV UT t = 120 min. T Power grids TN Backup fuse (A) 21A Maximum gG Fuse Optical Light ON: SPD is functional End of life indication Yes Light OFF: SPD has reached end-of-life Max earth leakage current at Uc (A) 50 IEC 61643-11 Test Classification Test Class II and III EN 61643-11 Type Classification Type 2 and 3 UL 1449 Type 4CA Repetitive Surge Capability Pulse Rating (8x20 Sec) 100000 MODEL SIZE = 20MM o o T = -55 C TO 85 C A 130 to 625V M(AC) RATING Strikes Surge 1 10000 2 15 1 20,000A 2 10 4 10 5 3 10 2 15,000A 1000 6 10 10 15 10,000A 100 100 3,000A 10 1,000 1,600A 10,000 650A 1 10 100 1000 10000 IMPULSE DURATION (s) 100,000 400A 1,000,000 240A File Name:SPD-20HP-SPEC 2018-08-09 SURGE CURRENT (A)