MVAD160 Series www.murata-ps.com 160W 2 X 4 AC-DC Power Supply Converter DESCRIPTION The MVAD160 series switching power supplies utilize advanced component and circuit technologies to deliver high ef ciency. Designed for Medical, Telecom, and Industrial applications to satisfy 1U height design considerations, the MVAD160 Series measures only 2.0 x 4.0 x 1.5 . All models offer universal AC input and compliance to worldwide safety and EMC standards. ORDERING GUIDE Natural Convection Conduction Cooling Forced Air Cooling Main Model Number Aux Output (V2) Cooling ( ta = 50C) ( ta = 85C) ( 350LFM /ta=50C) Output (V1) MVAD160-125 12V MVAD160-245 24V 5V MVAD160-485 48V 110W 110W 160W MVAD160-12 12V no aux output MVAD160-24 24V no remote sense MVAD160-48 48V no V1 remote FEATURESURES 110W Wide Operating Temperature range INPUT CHARACTERISTICS AC-DC Power Supply Parameter Conditions Min. Typ. Max. Units 1 Single phase 85 120/230 264 Vac IT (2nd Ed.) and Medical (3rd Ed. MOPP) safety Input Voltage Operating Range 2 DC 200 300 Vdc approved, excluding conduction cooling condi- Input Frequency 47 50/60 63 Hz tion Turn-on Input Voltage Input rising at full load 84 Vac 2 x 4 standard footprint Turn-off Input Voltage Input falling at full load 84 Input Current 90Vac input, full load 2.1 A High ef ciency up to 93% Inrush Current At 264Vac, at 25C cold start 100 Apk Remote sense OUTPUT CHARACTERISTICS Remote On/Off (for V1, Negative logic) Main Output Line, Load, Cross Typical Ef ciency Universal AC input Model Number Load Current Load Capacitance Voltage (V1) Regulation 230Vac full load Low pro le - 1U package MVAD160-12x 12V 0 to 13.34A 0 to 1500F 92% MVAD160-24x 24V 0 to 6.67A 0 to 680F 2% Convection, conduction, and forced-air cooled 93% MVAD160-48x 48V 0 to 3.34A 0 to 330F operation Aux Output Line, Load, Model Number Load Current Load Capacitance Voltage (V2) Cross Regulation Complies with 5000m altitude (at class I IT MVAD0160-xx5 5V 0 to 0.1A 0 to 220pF 5% equipment) RoHS compliant Main Output Characteristics (all models) Less than 0.3W input power at no load remote Parameter Conditions Min. Max. Units off Transient Response 50% load step, min.5% load, 1A/sec slew rate 5 %V1 Settling Time to 1% of Nominal 50% load step, min.5% load, 1A/sec slew rate 2 msec Complies with ErP/Energy star requirement Turn On Delay After application of input power 1.5 sec (average ef ciency > 87%) 5 Output Voltage Rise Monotonic, 0 to 100% load 200 msec Setpoint Accuracy 115Vac, 110W load, 25C 0.5 %V1 Output Holdup 100% load 10 msec Temperature Coef cient 0.02 %/C 3 Ripple Voltage & Noise min. 5% load 1 %V1 Compensates for up to total 400mV of positive Remote Sense and negative lead drops with remote sense 400 mV connected. 1 Refer to power derating curve vs. input voltage. Input test condition on safety approval : 100-240Vac 10%. 2 Applicable for IT Equipment only. 3 Ripple and noise are measured with 0.1 F of ceramic capacitance and 47 F of electrolytic capacitance on each Available now at of the power supply outputs. The output noise requirements apply over a 0 Hz to 20 MHz bandwidth. A short MVAD160 Series 160W 2 X 4 AC-DC Power Supply Converter ENVIRONMENTAL CHARACTERISTICS Parameter Conditions Min. Typ. Max. Units Storage Temperature Range -40 85 Refer to power derating curve vs. operating temperature -40 85 C Operating Temperature Range Start up -40 Operating Humidity Non-condensing 10 95 % For class I IT equipment deployment -200 5000 Operating Altitude m Other -200 2000 MTBF Telcordia SR-332 M1C3 50C, 110W 1M Hours Operating, IEC60068-2-27, half-sine 5G, 6ms, 3 times Complies per face, 6 faces Shock Non-operating, IEC60068-2-27, half-sine, 30G, 18ms, 3 Complies times per face, 6 faces Operating, IEC60068-2-6, 1.0G, 10-150Hz, 10minutes Complies per axis, on all 3 axes Vibration Non-operating, IEC60068-2-6, 2.0G, 10-150Hz, 10min- Complies utes per axis, on all 3 axes IEC60950-1:2005 2nd Ed. Am1:2009 EN60950-1:2006 A11:2009 A1:2010 A12:2011 UL60950-1, 2nd Ed., 2011-12-19 & CSA C22.2 No. 60950-1-07, 2nd Ed., 2011-12 Safety IEC60601-1:2005 3rd Ed. + CORR.1(2006) + CORR.2(2007) ANSI/AAMI ES60601-1 (2005+C1:09 + A2:10), CSA-C22.2 No. 60601-1(2008), MOPP CE Marking per LVD 6 Warranty 2 years Outside Dimensions 2.0 x 4.0 x 1.5 (50.8mm x 101.6mm x 38.1mm) Weight 0.42lbs (190g) typical PROTECTION CHARACTERISTICS Parameter Conditions Min. Typ. Max. Units V1 Latching (50% load) 110 140 Overvoltage Protection V2 Latching (50% load) 110 170 % V1 Hiccup mode Auto Recovery 110 170 Overcurrent Protection V2 Hiccup mode Auto Recovery 0.11 0.4 A Overtemperature Protection Auto recovery Complies ISOLATION CHARACTERISTICS Parameter Conditions Min. Typ. Max. Units Primary to Earth Ground (1x MOPP) 1500 Vac 7 Isolation Primary to Secondary (2x MOPP) 4000 Secondary to Earth Ground 500 Vdc 264Vac, 60Hz, 25C 350 A Leakage Current (under normal conditions) 240Vac, 60Hz, 25C 300 A Touch Current 264Vac, 60Hz, 25C 100 A EMISSIONS AND IMMUNITY Characteristic Standard Compliance Input Current Harmonics IEC/EN 61000-3-2 Class D, Class C Voltage Fluctuation and Flicker IEC/EN 61000-3-3 Complies EN 55022 Class B, (Class A as Class II equipment deployment) Conducted Emissions FCC Part 15 Class B, (Class A as Class II equipment deployment) ESD Immunity IEC/EN 61000-4-2 Level 4, Criterion A Radiated Field Immunity IEC/EN 61000-4-3 Level 2, Criterion A Electrical Fast Transient Immunity IEC/EN 61000-4-4 Level 3, Criterion A Surge Immunity IEC/EN 61000-4-5 Level 4, Criterion A RF Conducted Immunity IEC/EN 61000-4-6 Level 2, Criterion A Magnetic Field Immunity IEC/EN 61000-4-8 Level 2, Criterion A Voltage dips, interruptions IEC/EN 61000-4-11 Level 3, Criterion B 6 At Ta<50C. 7 Class I equipment deployment. power