INTERNET-DATASHEET of Art.-No. 85002 Evolution Power supply 3-phase, primary switched IN: 360-520VAC OUT: 22-28V/20ADC Output voltage: 22...28 V DC Input voltage: 3 x 360...520 V AC/480...745 V DC Current: 20 A Image stable output voltage, short-circuit and overload protected Wide voltage input touch protected (EN 60529) IP20 Approvals Input Input voltage 3 x 360...520 V AC/480...745 V DC Input current 3 x 1.3 A Inrush current after 1 ms <= 19 A Primary fusing 3 x 10 A Frequency 50/60 Hz Output Output voltage 24 V DC (SELV), 1 % 22...28 V adjustable Nominal output current 20 A (+55 C) 15.8 A (+70 C) Efficiency 90 % Mains failure bridging >= 19 ms (400 V AC) Ripple <= 50 mV eff Spikes <= 100 mV ss Protection Short-circuit and overload protected LED display LED (green): OK LED (red): overload Parallel usage/serial usage yes/yes General data Standards (EN 60950-1), (EN 61204-3), (EN 55011 A) Temperature range -25...+70 C (storage temperature -40...+85 C) Relative humidity 5...95 %, no condensation Mounting method DIN-rail mountable TH35 (EN 60715) Dimensions H x W x D 132 x 113 x 136 mm Commercial data Gross weight 2000 Net weight 2000 Weight unit gram Basic unit pc. Customs tariff number 85044081 Unit (piece) 1 Limited value 1 Comments MCS switch mode power supplies meet the (EN 61000-3-2) standard for harmonic current. All data on this data sheet was compiled carefully. Liability regarding correctness, completeness, and actuality is limited to gross negligence. Created: 08/10 Murrelektronik GmbH Falkenstrae 3, D-71570 Oppenweiler Fon +49 7191 47-0, Fax +49 7191 47-130 info murrelektronik.com www.murrelektronik.comINTERNET-DATASHEET of Art.-No. 85002 Circuit diagram Dimension drawing All data on this data sheet was compiled carefully. Liability regarding correctness, completeness, and actuality is limited to gross negligence. Created: 08/10 Murrelektronik GmbH Falkenstrae 3, D-71570 Oppenweiler Fon +49 7191 47-0, Fax +49 7191 47-130 info murrelektronik.com www.murrelektronik.com