1 8 DIN Temperature, Process and Strain PID Controllers i8 Series shown smaller than actual size. For Temp. Units U High Quality The i8 covers a broad U 5-Year Warranty selection of transducer and transmitter inputs with 2 input U High Accuracy: 0.5C models. (0.9F), 0.03% Reading The universal temperature and current ranges. The iS has built-in U User-Friendly, process instrument (i models) 5 or 10 Vdc excitation for bridge Simple to Configure handles 10 common types of transducers, 5 Vdc 40 mA or thermocouples, multiple RTDs, and U Free Software 10 Vdc 60 mA (any excitation several process (DC) voltage and voltage between 5 and 24 Vdc is U Full Autotune PID Control current ranges. This model also available by special order). This U Universal Inputs: RTD, features built-in excitation, 24 Vdc iS model supports 4- and 6-wire 25 mA. With its wide choice of Thermocouple, Process bridge configurations, ratiometric signal inputs, this model is an excellent and non-ratiometric measurements. Voltage/Current, Strain choice for measuring or controlling The iS features fast and easy U Totally Programmable temperature with a thermocouple, in process calibration/scaling of Color Displays Standard RTD, or 4 to 20 mA transmitter. the signal inputs to any engineering The strain and process instruments U Built-In Excitation units. This model also features (iS models) measure inputs from Standard 10-point linearization which allows load cells, pressure transducers, the user to linearize the signal U 2 Control or Alarm and most any strain gage sensor input from extremely nonlinear Outputs: DC Pulse, as well as process voltage and transducers of all kinds. Mechanical Relays, Input Type Range Accuracy Analog Voltage Universal Process and Current Process Voltage 0 to 100 mV, 0 to 1 V, 0 to 10 Vdc 0.03% rdg U Embedded Internet Process Current 0 to 20 mA (4 to 20 mA) 0.03% rdg Connectivity Available Excitation 24 V 25 mA 1 The NEWPORT i8 is a 8 DIN size Universal Strain/Process 96 x 48 mm (3.7 x 1.9 ) digital Process Voltage 0 to 100 mV, -100 to 1 V, 0 to 10 Vdc 0.03% rdg panel meter featuring the big Process Current 0 to 20 mA (4 to 20 mA) 0.03% rdg iSeries color-changing display. The Excitation 5 V 40 mA, 10 V 60 mV digits are twice the size of typical 1 8 DIN panel meters. The iSeries Nickel RTD Input (FS Required) meters feature the only LED RTD-1N (Nickel MIL-T-7990B) 0 to 200C (32 to 392F) 0.1C (0.2F) displays that can be programmed RTD-2N (Nickel MIL-T-7990B) -40 to 300C (-40 to 572F) 0.3C (0.5F) to change color between GREEN, Temperature AMBER, and RED at any setpoint or alarm point. The i8 model is J Iron - Constantan -210 to 760C (-346 to 1400F) 0.4C (0.7F) available as an extremely accurate -270 to -160C/-160 to 1372C 1.0C/0.4C K CHROMEGA- ALOMEGA programmable digital panel meter (-454 to -256F/-256 to 2502F) (1.8F/0.7F) with no outputs or with dual outputs -270 to -190C/-190 to 400C 1.0C/0.4C T Copper - Constantan for controlling or alarming functions. (-454 to -310F/-310 to 752F) (1.8F/0.7F) Other options include isolated -270 to -220C/-220 to 1000C 1.0C/0.4C E CHROMEGA - Constantan programmable analog output, serial (-454 to -364F/-364 to 1832F) (1.8F/0.7F) communications, Modbus and -50 to 40C/40 to 1768C 1.0C/0.5C R Pt / 13%Rh-Pt Ethernet. The user can easily (-58 to 104F/104 to 3214F) (1.8F/0.9F) program the i8 for any control or -50 to 100C/100 to 1768C 1.0C/0.5C S Pt / 10%Rh-Pt alarming requirement from simple (-58 to 212F/212 to 3214F) (1.8F/0.9F) on/off to full autotune PID with a 100 to 640C/640 to 1820C 1.0C/0.5C B 30% Rh-Pt / 6%Rh-Pt choice of form C SPDT relays, solid (212 to 1184F/1184 to 3308F) (1.8F/0.9F) state relays, DC pulse, and analog C 5% Re-W / 26%Re-W 0 to 2320C (32 to 4208F) 0.4C (0.7F) (voltage and current) outputs. -250 to -100C/-100 to 1300C 1.0C/0.4C N Nicrosil - Nisil Fully isolated analog output for (-418 to -148F/-148 to 2372F) (1.8F/0.7F) retransmission of the process value L J DIN -200 to 900C (-328 to 1652F) 0.4C (0.7F) is available in addition to the control -200 to 900C (-328 to 1652F) 0.4C (0.7F) Pt, 0.00385, 100, 500, 1000 and alarm relays (specify model Pt, 0.00392, 100, 500, 1000 -200 to 850C (-328 to 1652F) 0.4C (0.7F) i8A33). 1Dimensions: in (mm) At Any Setpoint patented Totally Programmable Color Displays TOP VIEW The NEWPORT i/8, i/16, and i/32 are the 1 1 1 first complete series of 8, 16 and 32 DIN process control instruments with totally programmable color displays. The display can be programmed to change color at any setpoint or alarm point. To Order Visit newportUS.com/i8 embed for Pricing and Details Model No. Output 1 Output 2 2 Control Outputs i833 Relay Relay i844 DC pulse DC pulse Options i843 DC pulse Relay i842 DC pulse 0.5 A SSR Ordering Suffix Description i822 0.5 A SSR 0.5 A SSR Limit alarm version (alarms only, -AL *3*4 i823 0.5 A SSR Relay no PID control) i824 0.5 A SSR DC pulse Simplified menu (on/off control or -SM *6 alarms, no PID) i853 Analog Relay i854 Analog DC pulse Networks Options i852 Analog 0.5 A SSR -EIT Ethernet with embedded Web server 2 Control Outputs and Isolated Analog Output Isolated RS232 and RS485/422, -C24 *2 i8A33 Relay Relay 300 to 19.2 Kb i8A44 DC pulse DC pulse Ethernet with embedded Web i8A43 DC pulse Relay -C4EIT server + isolated RS485/422 hub *1 for up to 31 devices i8A42 DC pulse 0.5 A SSR Power Supply i8A22 0.5 A SSR 0.5 A SSR *2*5 i8A23 0.5 A SSR Relay -DC 12 to 36 Vdc, 24 Vac i8A24 0.5 A SSR DC pulse Factory Setup Strain/Process Input with 2 Control Outputs ,FS Factory setup and configuration iS833 Relay Relay Customizedi Model for iS834 Relay DC pulse ,FS(RTD-1N) MIL-T-7990B nickel RTD input, 0 to 200C (32 to 392F) iS844 DC pulse DC pulse iS843 DC pulse Relay Customizedi Model for ,FS(RTD-2N) MIL-T-7990B nickel RTD input, iS842 DC pulse 0.5 A SSR -40 to 300C (-40 to 572F) iS822 0.5 A SSR 0.5 A SSR Software (Requires Network Option) iS823 0.5 A SSR Relay OPC-SERVER iS824 0.5 A SSR DC pulse OPC server/driver software license LICENSE iS853 Analog Relay *1 Ethernet options are not available for the i8A controller. iS854 Analog DC pulse *2 -DC, -C24, and -C4EIT not available with excitation. iS852 Analog 0.5 A SSR *3 Analog output is not available with -AL units. Comes with complete operators manual. *4 i8A0x-AL contains 1 alarm and 1 analog retransmission. 1 Ordering Examples: i8A22, 8 DIN temperature/process *5 20 to 36 Vdc for i8A, i8-C4EIT, i8-EIT. controller with isolated analog output and 2 SSR outputs. 1 *6 -SM option not available on iS strain models. iS833, 8 DIN strain/process controller with 2-relay outputs. 2