DATA SHEET G4 Digital AC Output Modules Form 0252-120920 G4 Digital AC Output Modules Features 4000 volts optical isolation (transient) Built-in LED status indicator Logic levels of 5, 15, and 24 VDC Removable fuse Current rating: 3 amps at 45 C UL Motor Load rating: 1.5 amps Ability to withstand one-cycle surge of 80 amps Operating temperature: -30 C to 70 C G4OAC5A and G4OAC5AMA Modules Description Opto 22s G4 AC output modules are used to control or switch AC loads. Each module provides up to 4000 volts of optical isolation (transient) between field outputs and the control side of the circuit, and each features zero voltage turn-on and Part Numbers zero current turn-off. All AC output modules are equivalent to single-pole, single-throw, normally open contacts (Form A, Part Description SPST-NO) except the G4OAC5A5, which is equivalent to a single-pole, single-throw, normally closed contact (Form B, G4OAC5 G4 AC Output 12140 VAC, 5 VDC Logic SPST-NC). G4 AC Output 12140 VAC, 5 VDC Logic, G4OAC5FM Factory Mutual Approved The G4OAC5MA and the G4OAC5AMA are special modules G4OAC5A G4 AC Output 24280 VAC, 5 VDC Logic featuring a manual-on/manual-off/automatic switch, ideal for diagnostic testing of control applications. G4 AC Output 24280 VAC, 5 VDC Logic, G4OAC5AFM Factory Mutual Approved Typical applications for AC output modules include switching G4 AC Output 24280 VAC, 5 VDC Logic loads such as AC relays, solenoids, motor starters, heaters, G4OAC5A5 NC lamps, and indicators. G4 AC Output 24280 VAC, 5 VDC Logic G4OAC5A5FM Part numbers ending in FM are Factory Mutual approved. NC, Factory Mutual Approved G4 AC Output 12140 VAC, 5 VDC Logic G4OAC5MA With Manual/Auto Switch G4 AC Output 24280 VAC, 5 VDC Logic G4OAC5AMA With Manual/Auto Switch G4 AC Output 12140 VAC, 15 VDC G4OAC15 Logic G4 AC Output 24280 VAC, 15 VDC G4OAC15A Logic G4 AC Output 12140 VAC, 24 VDC G4OAC24 Logic G4 AC Output 24280 VAC, 24 VDC G4OAC24A Logic Opto 22 43044 Business Park Drive Temecula, CA 92590-3614 www.opto22.com PAGE SALES 800-321-6786 951-695-3000 FAX 951-695-3095 sales opto22.com SUPPORT 800-835-6786 951-695-3080 FAX 951-695-3017 support opto22.com 1 2012 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations.G4 Digital AC Output Modules Specifications G4OAC5 G4OAC5A G4OAC5A5 Units G4OAC5MA G4OAC5AMA G4OAC5FM* G4OAC5AFM* G4OAC5A5FM* Nominal line voltage VAC 120 120/240 120/240 120 120/240 Output voltage range VAC 12140 24280 24280 12140 24280 Diagnostic Diagnostic Key feature Normally closed switch switch Current rating: At 45 C ambient A 3 3 3 3 3 At 70 C ambient A 2 2 2 2 2 UL Motor Load Rating A 1.5 1.5 1.5 1.5 1.5 Isolation input-to- output (transient): volts 1 ms 4000 4000 4000 4000 4000 1 minute 1500 1500 1500 1500 1500 Off-state leakage at mA 5 1.25/2.5 1.25/2.5 5 1.25/2.5 RMS nominal voltage (60 Hz) Nominal logic voltage VDC 5 5 5 5 5 Logic voltage range VDC 48 48 48 48 48 Logic pickup voltage VDC 4 4 4 4 4 Logic dropout voltage VDC 1 1 1 1 1 Logic input current at mA 12 12 12 12 12 nominal logic voltage Control resistance ohms 220 220 220 220 220 (Rc in schematic) One-cycle surge A peak 80 80 80 80 80 Turn-on time 60 Hz milliseconds 8.3** 8.3** 8.3** 8.3** 8.3** Turn-off time 60 Hz milliseconds 8.3*** 8.3*** 8.3*** 8.3*** 8.3*** Peak repetitive voltage VAC 500 500 500 500 500 Minimum load current mA 20 20 20 20 20 Output voltage drop V 1.6 1.6 1.6 1.6 1.6 maximum peak Operating frequency Hz 2565 2565 2565 2565 2565 V/micro- dV/dT-off-state 200 200 200 200 200 seconds snubbed for snubbed for snubbed for snubbed for snubbed for dV/dT-commutating -- 0.5 power 0.5 power 0.5 power 0.5 power 0.5 power factor load factor load factor load factor load factor load Temperature Operating: C -30 to +70 -30 to +70 -30 to +70 -30 to +70 -30 to +70 Storage: C -30 to +85 -30 to +85 -30 to +85 -30 to +85 -30 to +85 * Part numbers ending in FM are Factory Mutual approved. ** One-half cycle maximum. Module turns on at the zero volt crossing of the AC sine wave. *** One-half cycle maximum. Module turns off at the zero current crossing of the AC sine wave. Opto 22 43044 Business Park Drive Temecula, CA 92590-3614 www.opto22.com PAGE SALES 800-321-6786 951-695-3000 FAX 951-695-3095 sales opto22.com SUPPORT 800-835-6786 951-695-3080 FAX 951-695-3017 support opto22.com 2 2012 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations. DATA SHEET G4 Digital AC Output Modules Form 0252-120920