Bulletin No. CUB5-L Drawing No. LP0584 Released 04/16 Tel +1 (717) 767-6511 Fax +1 (717) 764-0839 www.redlion.net MODEL CUB 5 - MINIATURE ELECTRONIC 8-DIGIT DUAL COUNTER AND RATE INDICATOR LCD, REFLECTIVE OR GREEN/RED LED BACKLIGHTING 0.46 (11.7 mm) HIGH DIGITS OPTIONAL SETPOINT OUTPUT CARD OPTIONAL SERIAL COMMUNICATIONS CARD (RS232 or RS485) OPTIONAL USB PROGRAMMING CARD OPERATES FROM 9 TO 28 VDC POWER SOURCE PROGRAMMABLE SCALING FOR COUNT AND RATE BI-DIRECTIONAL COUNTING, UP/DOWN CONTROL QUADRATURE SENSING (UP TO 4 TIMES RESOLUTION) U BUILT-IN BATCH COUNTING CAPABILITY C R L US LISTED IND. CONT. EQ. 51EB DISPLAY COLOR CHANGE CAPABILITY AT SETPOINT OUTPUT NEMA 4X/IP65 SEALED FRONT BEZEL COUNTER GENERAL DESCRIPTION The CUB5 receives incoming pulses and multiplies them by the Count Scale The CUB 5 provides the user the ultimate in flexibility, from its complete Factor to obtain the desired reading for the count display. Input A accepts the user programming to the optional setpoint control and communication capability. signal for the count and Input B is used for quadrature, dual counter, anti- The meter can be programmed as a single or dual counter with rate indication coincidence counting, or up/down control counting. capability. The display can be toggled either manually or automatically between the selected displays. RATE The CUB5 display has 0.46 (11.7 mm) high digits. The LCD is available in The rate indicator utilizes the signal at Input A to calculate the rate value two versions, reflective (CUB5R000) and backlight (CUB5B000). The backlight using a time interval method (1/tau). The unit counts on the negative edge of the version is user selectable for green or red backlighting with variable display input pulses. After the programmed minimum update time elapses and the next intensity. negative edge occurs, the unit calculates the input rate based on the number of The counter is programmable for one of eight different count modes, edges that occurred during the elapsed time. The input rate is then multiplied by including bi-directional and quadrature. When programmed as a dual counter, the rate scaling value to calculate the rate display. each counter has a separate scale factor and decimal points. In the counter/rate At slower rates, averaging can be accomplished by programming the rate indicator mode, each have their own scaling and decimal point read-outs in minimum update time for the desired response. Extensive scaling capabilities different engineering units. The internal batch counter can be used to count allow practically any desired reading at very slow count rates. setpoint output activations. The meter has two separate inputs which provide different functions SAFETY SUMMARY depending on which operating mode is selected. Input A accepts the signal for the Count and/or Rate displays, while Input B accepts the signal for the Count All safety related regulations, local codes and instructions that appear in this literature or on equipment must be observed to ensure personal safety and to display or direction control. In the anti-coincidence mode, both inputs are monitored simultaneously so that no counts are lost. The resulting display can prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection be chosen as the sum or difference of the two inputs. The Rate Indicator has programmable low (minimum) and high (maximum) update times to provide provided by the equipment may be impaired. Do not use this meter to directly command motors, valves, or other actuators optimal display response at any input frequency. There is a programmable user input that can be programmed to perform a variety of functions. not equipped with safeguards. To do so can be potentially harmful to persons or equipment in the event of a fault to the meter. The capability of the CUB5 can be easily expanded with the addition of option cards. Setpoint capability is field installable with the addition of the single setpoint relay output card or the dual setpoint solid state output card. Serial communications capability for RS232 or RS485 is added with a serial option card. The CUB5 can be powered from an optional Red Lion Micro-Line/Sensor CAUTION: Risk of Danger. CAUTION: Risk of electric shock. Power Supply (MLPS), which attaches directly to the back of a CUB5. The Read complete instructions prior to MLPS is powered from 85 to 250 VAC and provides up to 400 mA to drive the installationand operation of the unit. unit and sensors. Note: Recommended minimum clearance (behind the panel) for mounting clip installation is 2.15 (54.6) H x 3.00 (76.2) W. DIMENSIONS In inches (mm) .13 (3.3) ON ECE +.024 1.30 1 2 34 -.000 1.29 (32.8) 1.54 (39.1) +6 (33 ) 9876543.2 -0 SEL RST +.025 2.95 (74.9) .15 (3.8) 1.71 2.68 -.000 (43.4) +8 (68 ) -0 1o rderin G i forMn ation TYPE MODEL NO. DESCRIPTION PART NUMBER CUB5R Dual Counter & Rate Indicator with Reflective Display CUB5R000 CUB5 CUB5B Dual Counter & Rate Indicator with Backlight Display CUB5B000 CUB5RLY Single Relay Option Card CUB5RLY0 CUB5SNK Dual Sinking Open Collector Output card CUB5SNK0 Optional Plug-in Cards RS485 Serial Communications Card CUB5COM1 CUB5COM RS232 Serial Communications Card CUB5COM2 CUB5USB USB Programming Card CUB5USB0 +12 VDC Micro-Line Power Supply, 85 to 250 VAC source, 400 mA max out MLPS1000 MLPS +24 VDC Micro-Line Power Supply, 85 to 250 VAC source, 200 mA max out MLPS2000 CBLPRO Programming Cable RS232 (RJ11-DB9) CBLPROG0 Accessories CBPRO Communication Cable RS485 (RJ11-DB9) CBPRO007 1 SFCRD Crimson PC Configuration Software, Free Download Available SFCRD200 CBLUSB USB Programming Cable CBLUSB00 1 Crimson software is a free download from