R3N miniature industrial relays 10 A / 250 V AC Relays of general application For plug-in sockets: 35 mm rail mount acc. to PN-EN 60715 on panel mounting Miniature dimensions Cadmium - free contacts AC and DC coils WT (mechanical indicator + lockable front test button) - standard features of relays. Relays may be provided with the test buttons (no latching) and plugs - page 10 Recognitions, certifi cations, directives: RoHS, Contact data Number and type of contacts 3 CO Contact material AgNi, AgNi/Au 0,2 m Rated / max. switching voltage AC 250 V / 440 V Min. switching voltage 10 V Rated load (capacity) AC1 10 A / 250 V AC AC15 3 A / 120 V 1,5 A / 240 V (B300) AC3 370 W (single-phase motor) DC1 10 A / 24 V DC (see Fig. 3) DC13 0,22 A / 120 V 0,1 A / 250 V (R300) Min. switching current 5 mA Max. inrush current 20 A Rated current 10 A Max. breaking capacity AC1 2 500 VA Min. breaking capacity 0,3 W Contact resistance 100 m Max. operating frequency at rated load AC1 1 200 cycles/hour no load 18 000 cycles/hour Coil data Rated voltage 50/60 Hz AC 6 ... 240 V DC 5 ... 220 V Must release voltage AC: 0,2 Un DC: 0,1 Un Operating range of supply voltage see Tables 1, 2 Rated power consumption AC 1,6 VA DC 0,9 W Insulation according to PN-EN 60664-1 Insulation rated voltage 250 V AC Rated surge voltage 4 000 V 1,2 / 50 s Overvoltage category III Insulation pollution degree 2 Dielectric strength between coil and contacts 2 500 V AC type of insulation: basic contact clearance 1 500 V AC type of clearance: micro-disconnection pole - pole 2 500 V AC type of insulation: basic Contact - coil distance clearance 2,5 mm creepage 4 mm General data Operating / release time (typical values) AC: 10 ms / 8 ms DC: 13 ms / 3 ms Electrical life 5 resistive AC1 > 10 10 A, 250 V AC cos see Fig. 2 7 Mechanical life (cycles) > 2 x 10 Dimensions (L x W x H) 27,5 x 21,2 x 35,6 mm Weight 35 g o Ambient temperature storage -40...+85 C o o operating AC: -40...+55 C DC: -40...+70 C Cover protection category IP 40 PN-EN 60529 Environmental protection RTI PN-EN 116000-3 Shock resistance (NO/NC) 10 g / 5 g Vibration resistance 5 g 10...150 Hz The data in bold type pertain to the standard versions of the relays. 1 www.relpol.com.pl Export Sales Department phone +48 68 47 90 832, 951 e-mail: export relpol.com.pl 14.07.2014 R3N miniature industrial relays Coil data - DC voltage version Table 1 Coil resistance Coil operating range Rated voltage Acceptable Coil code at 20 C V DC V DC resistance min. (at 20 C) max. (at 55 C) 1005 5 28 10% 4,0 5,5 1006 6 40 10% 4,8 6,6 1012 12 160 10% 9,6 13,2 1024 24 640 10% 19,2 26,4 1048 48 2 600 10% 38,4 52,8 1060 60 4 000 10% 48,0 66,0 1080 80 7 100 10% 64,0 88,0 1110 110 13 600 10% 88,0 121,0 1125 125 16 000 10% 100,0 137,5 1220 220 54 000 10% 176,0 242,0 The data in bold type pertain to the standard versions of the relays. Coil data - AC 50/60 Hz voltage version Table 2 Coil resistance Coil operating range Rated voltage Acceptable Coil code at 20 C V AC V AC resistance min. (at 20 C) max. (at 55 C) 5006 6 9,8 10% 4,8 6,6 5012 12 39,5 10% 9,6 13,2 5024 24 158 10% 19,2 26,4 5042 42 470 10% 33,6 46,2 5048 48 640 10% 38,4 52,8 5060 60 930 10% 48,0 66,0 5080 80 1 720 10% 64,0 88,0 5110 110 3 450 10% 88,0 121,0 5115 115 3 610 10% 92,0 127,0 5120 120 3 770 10% 96,0 132,0 5127 127 4 000 10% 101,6 139,0 5220 220 15 400 10% 176,0 242,0 5230 230 16 100 10% 184,0 253,0 5240 240 16 800 10% 192,0 264,0 The data in bold type pertain to the standard versions of the relays. NEW TECHNOLOGY The new R2N, R3N, R4N relays are modernized versions of the R2, R3, R4 relays. The modernization covered the design of the relays and the manufacturing process. 2 www.relpol.com.pl Export Sales Department phone +48 68 47 90 832, 951 e-mail: export relpol.com.pl 14.07.2014