199 Power Relays
GENERAL SPECIFICATIONS
www.serelays.com
File No. E43641
IEC 60947-1
168986
File No. E43641
DPDT SPDT SPST-DM
199AX, 199X, 199AMX, 199ADX, 199DX,
199ADE, 199DE,
,4 ,4
PART NUMBERS 199MX, 199ABX, 199ADYX, 199DYX, 199P , 199AP
199ADBE, 199DBE
199BX 199ADBX, 199DBX
CONTACT CHARACTERISTICS
Number and type of contacts SPST, SPDT, DPST, DPDT SPST-DM, SPST-DB DPDT, SPDT SPST-DM
Contact material AgSnO
Thermal (carrying) current rating 40 A 50 A
Maximum switching voltage 600 V(rms)
Rated Switching current at Resistive 40 A at 300 VAC; 40 A at 300 VAC; 50 A at 300 VAC; 50 A at 300 VAC;
voltage 5 A at 480 VAC; 12 A at 480 VAC; 5 A at 480 VAC; 12 A at 480 VAC;
5 A at 600 VAC; 10 A at 600 VAC; 5 A at 600 VAC; 10 A at 600 VAC;
40 A at 28 VDC 40 A at 28 VDC 50 A at 28 VDC 50 A at 28 VDC
Motor 2 HP at 120 to 600 VAC
Tungsten 15 A at 120 VAC
Pilot duty A600
Minimum switching requirement 1 A at 5 VAC/VDC
COIL CHARACTERISTICS
Voltage range 6 to 600 VAC; 6 to 250 VDC
5
Operating range (% of Nominal) 85% to 110% (AC); 80% to 110% (DC)
Average power consumption (Maximum) 10 VA; 4 W
Drop-out voltage threshold 10% (AC/DC)
PERFORMANCE CHARACTERISTICS
Electrical life (IEC 60947-1) Rated resistive load Please refer to Table 3
Operating time (response time) 30 ms
Dielectric strength Between coil and 2200 V 2200 V 2200 V 2200 V
contact
Between poles 2200 V N/A 2200 V N/A
Between open contacts 1600 V 2200 V 1600 V 2200 V
ENVIRONMENT
Product certications UL, CSA, CE, RoHS
Ambient temperature range (around the device) -55 to +100 C (Storage)
-55 to +55 C (Operation)
Termination 10 (5.3) AWG (mm)
Terminal tightening torque 11 to 15 in-lb (1.2 to 1.7 Nm)
Weight 227 to 312 g (8 to 11 oz)
For auxiliary switch ratings, please refer to Table 1.
For ratings with blowout magnet, please refer to Table 2.
For UL listed installations, proper wire rating and terminations required.
4
Recommended ring, fork, or box wire termination.
5
Recommended mounting positions: horizontal or vertical (not upside down).
Document No. 600SP02-0710 2010 Schneider Electric USA.
Power R ela y sTable 1: Auxiliary Switch Ratings
Table 2: Additional DC Ratings with Blowout Magnets
AUXILIARY SWITCH RATINGS
RELAY VOLTAGE RATING W/BLOWOUT MAGNET
Resistive Load 120/250 VAC (50/60 Hz) 10 A
110 VDC 20 A www.serelays.com
Motor Load 125/250 VAC (50/60 Hz) 0.25 HP
220 VDC 8 A
Tungsten Load 125 VAC (50/60 Hz) 3 A
325 VDC 4 A
500 VDC 2 A
Table 3: Contact Ratings & Electrical Endurance (per IEC 60947-1, 60947-4-1)
CURRENT/HORSEPOWER ESTIMATED ELECTRICAL Notes:
LOAD VOLTAGE FREQUENCY LOAD TYPE SEE NOTE(S)
RATINGS ENDURANCE
1. 50 A rating refer to models with pressure wire
connectors only.
AC LOAD
2. Resistive AC load ratings are based on a power
50 A 300 V 50/60 Hz Resistive 25,000 cycles 1, 4
factor of 0.85 to 1.0.
40 A 50,000 cycles 2, 4
3. Motor horsepower ratings are based on a power
2 HP 120 to 600 V Motor 50,000 cycles 3, 4
factor of 0.4 to 0.5, and an initial inrush current not
15 A 120 V Tungsten 20,000 cycles 4, 5
in excess of six times the full load current.
A600 --- --- Pilot Duty 100,000 cycles 4
4. All ratings are based on applying the rated nominal
DC LOAD
power to the relay coil in such a manner as to
provide a clean make and break, and does not
40 A 28 V DC Resistive 100,000 cycles 4
result in any contact chatter or multiple actuation
20 A 110 V
of the contacts.
8 A 220 V
5. The tungsten rating is based on cold lament
4 A 325 V
inrush current not exceeding 15 times the rated
2 A 500 V
steady state lamp current.
RELAY DIMENSIONS
RELAY WIRING DIAGRAMS
shown in inches (millimeters)
14 A1 24 A121
SPDT Short base w/Auxiliary Switch
22
DPST-NO
12
14 A211
12 A2 11
2.06
1.95
(52.4)
(49.6) SPDT DPDT
14 A1 22 A121
1.874 0.81 0.19
1.874
0.374
0.31
(47.60) (20.7) (4.8)
2.5 2.49 1.15 2.49
(47.60)
2.5
(9.50)
(8.0)
(63.6) (63.2) (29.3) (63.2)
(63.6)
13 A2 12 A211
DPDT Long base w/Auxiliary Switch
SPST-NO-DM
SPST-NO-DM
12 A1 24 A121
2.31
1.98
(58.8)
(50.3)
13 A2 14 A211
DPST-NO
1.874
1.874 0.19
0.374
(47.60)
2.5 (47.60) 3.13 (4.8) 1.15 2.56
2.5
(9.50)
(65.0)
(63.6) (79.4) (29.3)
(63.6)
Document No. 600SP02-0710 2010 Schneider Electric USA.
Power R elay s