10/30/2019 | Page 1 of 3
Schneider Electric Relays
200 N. Martingale Rd., Suite 1000
Schaumburg, IL 60173
Phone: 847-441-2540 Fax: 847-881-0741
E-Mail: relays@schneider-electric.com Web site: www.serelays.com
ITEM # W92S11A22D-120, 92 DIN & FLANGE COVER POWER RELAYS / DPDT, 30 AMP RATING (AC)
W92 92S11A22D-120
SPECIFICATIONS | CONTACT CHARACTERISTICS | COIL CHARACTERISTICS | PERFORMANCE CHARACTERISTICS | ENVIRONMENT |
PRODUCT CERTIFICATIONS
Specifications
Check Inventory Check Distributor Inventory
Status Standard
Legacy Part No. W92S11A22-120
Cover Style DIN & Flange Cover
WARNING: This product can expose you to chemicals including:
Substance 1: Nickel compounds, which is known to the State of California to
cause cancer.
California Proposition 65 Warning
Substance 2: DIDP, which is known to the State of California to cause birth
defects or other reproductive harm.
For more information go to www.p65warnings.ca.gov
Contact Characteristics
Contact Rating 30 A
Contact Configuration DPDT10/30/2019 | Page 2 of 3
Contact Materials Silver Alloy
Maximum Switching Voltage (V) 300 V
3 A at 277 VAC 50/60 Hz (Normally Closed Contact)
Switching Current at Voltage (AC, Resistive)
30 A at 277 VAC 50/60 Hz (Normally Open Contact)
20 A at 28 V (Normally Open Contact)
Switching Current at Voltage (DC, Resistive)
3 A at 28 V (Normally Closed Contact)
Switching Current at Voltage (Pilot Duty) 720 VA (Normally Open Contact)
100 mA at 6 VAC/VDC (Normally Closed Contact)
Minimum Switching Requirement
500 mA at 12 VAC/VDC (Normally Open Contact)
Coil Characteristics
Nominal Input Voltage 120 VAC 50/60 Hz
Coil Resistance (Ohms) 1600 Ohm
Operating Range - % of Nominal (AC) 80 to 110 %
Operating Range - % of Nominal (DC) 80 to 110 %
Average Consumption (AC / VA) 4 VA
Average Consumption (DC / W) 1.70 W
Drop-out Voltage Threshold (DC) 10 %
Drop-out Voltage Threshold (AC) 10 %
Performance Characteristics
Electrical Life (UL508), Operations at Rated
100000
Current (Resistive)
Mechanical Life, Unpowered 5000000
Operating Time (Response Time) 15 ms
Environment
Ambient Air Temperature around the Device
-40 to +85 C
- Storage
Ambient Air Temperature around the Device
-40 to +55 C
- Operation
Shock Resistance 10 g-n