Product datasheet
ATS48D32Y
Characteristics
Main
Range of product Altistart 48
Product or component type Soft starter
Product destination Asynchronous motors
Product specific application Heavy duty industry and pumps
Device short name ATS48
[Us] rated supply voltage 208...690 V (- 15...10 %)
Motor power kW 11 kW at 400 V for severe applications
11 kW at 440 V for severe applications
11 kW at 500 V for severe applications
11 kW at 525 V for severe applications
15 kW at 400 V for standard applications
15 kW at 440 V for standard applications
15 kW at 660 V for severe applications
22 kW at 660 V for standard applications
22 kW at 690 V for standard applications
7.5 kW at 230 V for standard applications
18.5 kW at 500 V for standard applications
18.5 kW at 525 V for standard applications
18.5 kW at 690 V for severe applications
5.5 kW at 230 V for severe applications
Motor power hp 10 hp at 230 V for standard applications
15 hp at 460 V for severe applications
20 hp at 460 V for standard applications
20 hp at 575 V for severe applications
25 hp at 575 V for standard applications
5 hp at 208 V for severe applications
7.5 hp at 208 V for standard applications
7.5 hp at 230 V for severe applications
Power dissipation in W For standard applications 104 W
For standard applications 74 W
Utilisation category AC-53A
Type of start Start with torque control (current limited to 5 In)
IcL starter rating 32 A (connection in the motor supply line) for
standard applications
32 A (connection in the motor supply line) for
severe applications
IP degree of protection IP20
Complementary
Assembly style With heat sink
Function available External bypass (optional)
Supply voltage limits 177...759 V
Supply frequency 50...60 Hz (- 5...5 %)
Network frequency 47.5...63 Hz
Device connection In the motor supply line
Factory setting current 27 A
[Uc] control circuit voltage 110 - 15 % to 230 + 10 %, 50/60 Hz
Control circuit consumption 30 W
Discrete output number 2
Discrete output type (LO1) logic output 0 V common configurable
(LO2) logic output 0 V common configurable
(R1) relay outputs fault relay NO
(R2) relay outputs end of starting relay NO
(R3) relay outputs motor powered NO
Output absolute accuracy precision +/- 5 %
Minimum switching current Relay outputs 10 mA at 6 V DC
Maximum switching current Logic output 0.2 A at 30 V DC
1 / 3
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.Relay outputs 1.8 A at 230 V AC inductive load, cos phi = 0.5, L/R = 20 ms
Relay outputs 1.8 A at 30 V DC inductive load, cos phi = 0.5, L/R = 20 ms
Discrete input number 5
Discrete input type PTC, 750 Ohm at 77 F (25 C)
(Stop, Run, LI3, LI4) logic, <= 8 mA 4300 Ohm
Discrete input voltage 24 V (<= 30 V)
Discrete input logic Positive logic (Stop, Run, LI3, LI4) state 0 < 5 V and <= 2 mA, state 1 > 11 V and >= 5
mA
Supply inrush current Adjustable 0.4...1.3 Icl
Analogue output type (AO) current output 0-20 mA or 4-20 mA <= 500 Ohm
Communication port protocol Modbus
Connector type 1 RJ45
Communication data link Serial
Physical interface RS485 multidrop
Transmission rate 4800, 9600 or 19200 bps
Installed device 31
Protection type Phase failure (line)
Thermal protection (motor)
Thermal protection (starter)
Marking CE
Type of cooling Forced convection
Operating position Vertical +/- 10 degree
Height 10.83 in (275 mm)
Width 6.3 in (160 mm)
Depth 7.48 in (190 mm)
Product weight 10.8 lb(US) (4.9 kg)
Power range 4...6 kW at 200...240 V 3 phases
7...11 kW at 200...240 V 3 phases
15...25 kW at 380...440 V 3 phases
15...25 kW at 480...500 V 3 phases
Motor starter type Soft starter
Environment
electromagnetic compatibility Conducted and radiated emissions conforming to IEC 60947-4-2 level A
Conducted and radiated emissions conforming to IEC 60947-4-2 level B
Damped oscillating waves conforming to IEC 61000-4-12 level 3
Electrostatic discharge conforming to IEC 61000-4-2 level 3
Immunity to electrical transients conforming to IEC 61000-4-4 level 4
Immunity to radiated radio-electrical interference conforming to IEC 61000-4-3 level 3
Voltage/current impulse conforming to IEC 61000-4-5 level 3
standards EN/IEC 60947-4-2
product certifications CCC
CSA
C-Tick
DNV
GOST
NOM 117
SEPRO
TCF
UL
vibration resistance 1 gn (f = 13...200 Hz) conforming to EN/IEC 60068-2-6
1.5 mm (f = 2...13 Hz) conforming to EN/IEC 60068-2-6
shock resistance 15 gn 11 ms conforming to EN/IEC 60068-2-27
noise level 52 dB
pollution degree Level 3 conforming to IEC 60664-1
relative humidity 0...95 % without condensation or dripping water conforming to EN/IEC 60068-2-3
ambient air temperature for operation 14...104 F (-10...40 C) without derating
14...104 F (-10...40 C) without derating
40...60 C with current derating of 2 % per C
ambient air temperature for storage -13...158 F (-25...70 C)
operating altitude <= 3280.84 ft (1000 m) without derating
> 3280.84...6561.68 ft (> 1000...2000 m) with current derating of 2.2 % per additional
100 m