Product data sheet GV3P73 Characteristics Motor circuit breaker, TeSys Deca, 3P, 62-73 A, thermal magnetic, EverLink terminals Main Range TeSys TeSys Deca Product name TeSys GV3 TeSys Deca Product or Component Circuit breaker Type Device short name GV3P Device Application Motor Trip unit technology Thermal-magnetic Complementary Poles description 3P Network type AC Utilisation category AC-3 IEC 60947-4-1 Category A IEC 60947-2 Network frequency 50/60 Hz Fixing mode 35 mm symmetrical DIN rail clipped Panel screwed with 3 x M4 screws) Operating position Any position Motor power kW 37KW 400/415 V AC 50/60 Hz 55KW 690 V AC 50/60 Hz 45kW 500 V AC 50/60 Hz Breaking capacity 50KA Icu 400/415 V AC 50/60 Hz 50KA Icu 440 V AC 50/60 Hz 12KA Icu 500 V AC 50/60 Hz 6KA Icu 690 V AC 50/60 Hz 65kA Icu 230/240 V AC 50/60 Hz Ics rated service short-circuit breaking capacity 100% 230/240 V AC 50/60 Hz 60% 400/415 V AC 50/60 Hz 60% 440 V AC 50/60 Hz 50% 500 V AC 50/60 Hz 50% 690 V AC 50/60 Hz Control Type Rotary knob Line Rated Current 73A Thermal protection adjustment range 6273A Magnetic tripping current 1120A Ue rated operational voltage 690 V AC 50/60 Hz Ui rated insulation voltage 690V AC 50/60 Hz IEC 60947-2 Uimp rated impulse withstand voltage 6kV IEC 60947-2 Power dissipation per pole 8W Mechanical durability 50000cycles Electrical durability 20000cycles AC-3 415 V In Maximum operating rate 25cyc/h Rated duty Continuous IEC 60947-4-1 Tightening torque 44.25Lbf.In (5N.m) EverLink BTR screw connectors 0.04in (25mm) 70.81lbf.in (8N.m) EverLink BTR screw connectors 0.05in (35mm) Mechanical robustness Shocks 30 Gn for 11 ms opened IEC 60068-2-27 Vibrations 4 Gn, 5...300 Hz IEC 60068-2-6 Shocks 5 Gn for 11 ms closed IEC 60068-2-27 Oct 13, 2021 1 The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.Suitability for isolation Yes IEC 60947-1 Phase failure sensitivity Yes IEC 60947-4-1 Height 5.20in (132mm) Width 2.17in (55mm) Depth 5.35in (136mm) Product Weight 2.12lb(US) (0.96kg) Color Dark grey Green SE GREEN 2) Environment Standards EN/IEC 60947-2 EN/IEC 60947-4-1 CSA C22.2 No 60947-4-1 UL 60947-4-1 Product Certifications IECEE CB Scheme UL CSA CCC EAC ATEX BV LROS (Lloyds register of shipping) DNV-GL ABS UKCA Protective treatment TC IP degree of protection IP20 IEC 60529 IK degree of protection IK09 Ambient air temperature for operation -4140F (-2060C) Ambient Air Temperature for Storage -40176F (-4080C) Fire resistance 1760F (960C) IEC 60695-2-1 Operating altitude 0...9842.52 ft (0...3000 m) Ordering and shipping details GTIN 3606481304513 Nbr. of units in pkg. 1 Package weight(Lbs) 2.23lb(US) (1.011kg) Packing Units Unit Type of Package 1 PCE Package 1 Height 2.56in (6.5cm) Package 1 width 5.75in (14.6cm) Package 1 Length 6.30in (16cm) Unit Type of Package 2 P06 Number of Units in Package 2 120 Package 2 Weight 297.45lb(US) (134.92kg) Package 2 Height 29.53in (75cm) Package 2 width 23.62in (60cm) Package 2 Length 31.50in (80cm) Offer Sustainability Sustainable offer status Green Premium product REACh Regulation REACh Declaration EU RoHS Directive Compliant EU RoHS Declaration Mercury free Yes RoHS exemption information Yes China RoHS Regulation China RoHS Declaration 2