Product data sheet METSEPM5340 Characteristics PM5340 powermeter w ethernet - upto 31st H - 256K 2DI/2DO 35alarms - flush mount Main Range PowerLogic Product name PowerLogic PM5000 Device short name PM5340 Product or component Power meter type Complementary Power quality analysis Up to the 31st harmonic Device application Power monitoring Multi-tariff Type of measurement Active and reactive power Energy Power factor Frequency Voltage Current Supply voltage 125...250 V DC 100...415 V AC (45...65 Hz) Network frequency 50 Hz 60 Hz In rated current 1 A 5 A Type of network 1P + N 3P 3P + N Power consumption in VA 10 VA at 415 V Display type Backlit LCD Display resolution 128 x 128 pixels Sampling rate 64 samples/cycle Measurement current 10 mA...9 A Analogue input type Voltage (impedance 5 MOhm) Current (impedance 0.3 mOhm) Measurement voltage 20...400 V AC 45...65 Hz between phase and neutral 35...690 V AC 45...65 Hz between phases Frequency measurement range 45...65 Hz Number of inputs 2 digital Measurement accuracy +/- 0.5 % voltage +/- 0.5 % current +/- 0.005 % power factor +/- 0.05 % frequency +/- 0.5 % apparent power +/- 0.5 % active power +/- 2 % reactive energy +/- 0.5 % active energy Accuracy class Class 0.5S (active energy according to IEC 62053-22) Number of outputs 2 digital 2 relay Information displayed Tariff 4 Dec 15, 2015 1 The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.Communication port protocol Modbus TCP/IP : 10/100 Mbit/s, insulation: 2500 V Communication port support Ethernet Data recording Data logs Event logs Min/Max of instantaneous values Time stamping Alarm logs Maintenance logs Memory capacity 256 kB Mounting mode Flush-mounted Mounting support Framework Standards IEC 60529 IEC 61557-12 IEC 62053-22 EN 50470-1 EN 50470-3 IEC 62053-24 Product certifications CULus conforming to UL 61010-1 CE conforming to IEC 61010-1 Width 96 mm Depth 72 mm Height 96 mm Product weight 430 g Environment Electromagnetic compatibility conducted and radiated emissions class class B, conforming to EN 55022 magnetic field at power frequency class level 4, conforming to IEC 61000-4-8 conducted RF disturbances class level 3, conforming to IEC 61000-4-6 electrostatic discharge class level 4, conforming to IEC 61000-4-2 limits for harmonic current emissions class class A, conforming to IEC 61000-3-2 IP degree of protection IP30 (body) conforming to IEC 60529 IP52 (front) conforming to IEC 60529 Relative humidity 5...95 % 50 C Pollution degree 2 Ambient air temperature for operation -25...70 C Ambient air temperature for storage -40...85 C Operating altitude 2000 m 2