Product data sheet METSEPM8240 Characteristics PowerLogic PM8000 - PM8240 Panel mount meter - intermediate metering Main Range PowerLogic Product name PowerLogic PM8000 Device short name PM8240 Product or component type Power meter Complementary Power quality analysis Waveform capture Harmonic distortion Programmablity (logic and math functions) Voltage sag and swell detection Up to the 63rd harmonic Compliance report EN 50160 Power quality monitoring IEC 62586 Power quality measurement IEC 61000-4-30 : class S Device application Power monitoring WAGES metering Type of measurement Power factor (total) Apparent power (total) Active and reactive power (total) Active and reactive power (per phase, rms) Apparent power (per phase, rms) Power factor (per phase, rms) Voltage Current Frequency Us rated supply voltage 90...415 V AC +/- 10 % (45...65 Hz) 110...415 V DC +/- 10 % Network frequency 50 Hz 60 Hz In rated current 10 A 5 A 1 A Poles description 1P + N 3P Dec 28, 2017 1 Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications3P + N Power consumption in VA 18 VA at 415 V AC Power consumption in VA 36 VA at 415 V AC Display type Colour TFT LCD Display resolution 320 x 240 pixels QVGA Sampling rate 256 samples/cycle Measurement current 50...10000 mA Analogue input type Current (impedance 0.3 mOhm) Voltage (impedance 5 MOhm) Measurement voltage 57...400 V AC 42...69 Hz between phase and neutral 100...690 V AC 42...69 Hz between phases Frequency measurement range 42...69 Hz Number of inputs 3 digital 30 V AC 3 digital 60 V DC Measurement accuracy +/- 0.2 % active energy +/- 0.1 % voltage +/- 0.1 % current Accuracy class Class 0.2 (active energy according to ANSI C12.20) Class 0.2S (active energy according to IEC 62053-22) Class 0.2 (active power according to IEC 61557-12) Class 0.5S (reactive energy according to IEC 62053-24) Class 0.5 (power factor according to IEC 61557-12) Class 0.2 (voltage according to IEC 61557-12) Class 0.2 (current according to IEC 61557-12) Number of outputs 1 pulse Information displayed Voltage Current Frequency Power Energy consumption Harmonic distortion Communication port protocol DNP3 IEC 61850 Modbus RTU 2-wire, : 115 kbauds, ION 2-wire, : 115 kbauds, Modbus TCP/IP Ethernet Modbus TCP/IP daisy chain : 10/100 Mbit/s, RSTP 801.1d 2004 Communication port support Ethernet RS485 (screw terminal block) Communication network type IPv6 (internet protocol) Data recording Time stamping Harmonics logs Waveform logs Data logs GPS synchronisation Event logs Alarm logs Trending/Forecasting Sequence of event recording Min/Max of instantaneous values Sag and swell logs Memory capacity 512 MB Web services File upload/download via FTP Web server Customizable home page Alarm notification by e-mail Viewing of captured waveform HTTP server Communication service SMTP e-mail notification DHCP RSTP support NTP time synchronization Cybersecurity Enable/Disable communication ports Syslog protocol support Robust security logs 2