Product data sheet METSEPM5111 Characteristics PM5111 powermeter w modbus - upto 15th H - 1DO 33alarms - flush - MID Main Range PowerLogic Product name PowerLogic PM5000 Device short name PM5111 Product or component type Power meter Complementary Power quality analysis Up to the 15th harmonic Device application Power monitoring Type of measurement Energy Active and reactive power Voltage Current Frequency Power factor Us rated supply voltage 100...415 V AC (45...65 Hz) 125...250 V DC Network frequency 60 Hz 50 Hz In rated current 5 A 1 A Poles description 1P + N 3P 3P + N Power consumption in VA 10 VA at 415 V Display type Backlit LCD Display resolution 128 x 128 pixels Sampling rate 64 samples/cycle Measurement current 10...9000 mA Analogue input type Current (impedance 0.3 mOhm) Voltage (impedance 5 MOhm) Measurement voltage 35...690 V AC 45...65 Hz between phases Dec 28, 2017 1 Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications20...400 V AC 45...65 Hz between phase and neutral Frequency measurement range 45...65 Hz Number of inputs 0 Measurement accuracy +/- 0.5 % active energy +/- 2 % reactive energy +/- 0.5 % active power +/- 0.5 % apparent power +/- 0.05 % frequency +/- 0.005 % power factor +/- 0.5 % current +/- 0.5 % voltage Accuracy class Class 0.5S (active energy according to IEC 62053-22) Number of outputs 1 digital Communication port protocol Modbus RTU and ASCII 2 wires, : 9.6, 19.2 and 38.4 kbauds, even/odd or none, insulation: 2500 V JBUS Communication port support RS485 Data recording Time stamping Min/Max of instantaneous values Mounting mode Flush-mounted Mounting support Framework Standards IEC 62053-24 IEC 61557-12 EN 50470-3 UL 61010-1 EN 50470-1 IEC 60529 IEC 62053-22 Product certifications CE conforming to IEC 61010-1 CULus conforming to UL 61010-1 MID conforming to EN 50470-1 MID conforming to EN 50470-3 Width 96 mm Depth 72 mm Height 96 mm Product weight 380 g Environment Electromagnetic compatibility conducted and radiated emissions class class B, conforming to EN 55022 limits for harmonic current emissions class class A, conforming to IEC 61000-3-2 electrostatic discharge class level 4, conforming to IEC 61000-4-2 conducted RF disturbances class level 3, conforming to IEC 61000-4-6 magnetic field at power frequency class level 4, conforming to IEC 61000-4-8 IP degree of protection IP52 (front) conforming to IEC 60529 IP30 (body) conforming to IEC 60529 Relative humidity 5...95 % 50 C Pollution degree 2 Ambient air temperature for operation -25...70 C Ambient air temperature for storage -40...85 C Operating altitude 2000 m Offer Sustainability Sustainable offer status Green Premium product RoHS (date code: YYWW) Compliant - since 1340 - Schneider Electric declaration of conformity Schneider Electric declaration of conformity REACh Reference not containing SVHC above the threshold Reference not containing SVHC above the threshold Product environmental profile Available Product end of life instructions Available 2