Product data sheet RM35UA13MW Characteristics multifunction voltage control relay RM35-U - range 15..600 V Main Range of product Zelio Control Product or component Modular measurement and control relays type Relay type Multifunction voltage control relay Relay name RM35UA Relay monitored pa- Overvoltage or undervoltage detection rameters Time delay Adjustable 0.3...30 s, 0 + 10 % on crossing the threshold Switching capacity in 1250 VA VA Minimum switching cur- 10 mA at 5 V DC rent Maximum switching 5 A AC/DC current Power consumption in <= 3.5 VA AC VA Measurement range 15...600 V voltage Utilisation category DC-14 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1 DC-12 conforming to IEC 60947-5-1 AC-15 conforming to IEC 60947-5-1 AC-14 conforming to IEC 60947-5-1 AC-13 conforming to IEC 60947-5-1 AC-12 conforming to IEC 60947-5-1 Complementary Reset time 1500 ms for time delay Maximum switching voltage 250 V AC/DC Us rated supply voltage 24...240 V AC/DC Supply voltage limits 20.4...264 V AC/DC Power consumption in W <= 0.6 W DC Control circuit frequency 40...70 Hz +/- 10 % Resistance across terminals 600 mOhm E3-M terminals 300 mOhm E2-M terminals 150 mOhm E1-M terminals Output contacts 2 C/O Nominal output current 5 A Measuring cycle <= 30 ms measurement cycle as true rms value Hysteresis 5...50 % of threshold setting Delay at power up <= 600 ms Measurement accuracy +/- 10 % of the full scale value Repeat accuracy +/- 2 % for time delay +/- 0.5 % for input and measurement circuit Measurement error < 1 % over the whole range with voltage variation +/- 0.05 %/C with temperature variation Polarity Non reversible polarity on DC supply Sensitivity scale 60...600 V E3-M terminals 30...300 V E2-M terminals 15...150 V E1-M terminals Threshold setting 10...100 % Marking CE : 73/23/EEC CE : EMC 89/336/EEC Mar 20, 2015 1 The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.Overvoltage category III conforming to IEC 60664-1 Insulation resistance > 500 MOhm at 500 V DC conforming to IEC 60664-1 > 500 MOhm at 500 V DC conforming to IEC 60255-5 Ui rated insulation voltage 600 V conforming to IEC 60664-1 250 V conforming to IEC 60664-1 Operating voltage tolerance - 15 % + 10 % Un Supply frequency 50/60 Hz +/- 10 % Insulation Between supply and measurement Operating position Any position without derating Connections - terminals Screw terminals 2 x 0.2...2 x 1.5 mm - AWG 24...AWG 16, flexible cable with ca- ble end Screw terminals 1 x 0.2...2 x 2.5 mm - AWG 24...AWG 12, flexible cable with ca- ble end Screw terminals 2 x 0.5...2 x 2.5 mm - AWG 20...AWG 14, solid cable without cable end Screw terminals 1 x 0.5...1 x 4 mm - AWG 20...AWG 11, solid cable without ca- ble end Tightening torque 0.6...1 N.m conforming to IEC 60947-1 Housing material Self-extinguishing plastic Status LED 1 LED yellow for relay ON 1 LED green for power ON Mounting support 35 mm symmetrical DIN rail conforming to EN/IEC 60715 Electrical durability 100000 cycles Mechanical durability <= 30000000 cycles Operating rate <= 360 operations/hour under full load Width 35 mm Product weight 0.08 kg Environment Immunity to microbreaks 10 ms Electromagnetic compatibility Immunity for industrial environments conforming to NF EN/IEC 61000-6-2 Emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3 Emission standard for industrial environments conforming to EN/IEC 61000-6-4 Standards EN/IEC 60255-6 Product certifications CSA C-Tick GL GOST UL Ambient air temperature for storage -40...70 C Ambient air temperature for operation -20...50 C Relative humidity 95 % at 55 C conforming to IEC 60068-2-30 Vibration resistance 1 gn (f = 57.6...150 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1 0.35 mm (f = 5...57.6 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1 Shock resistance 5 gn conforming to IEC 60068-2-27 IP degree of protection IP30 (casing) conforming to IEC 60529 IP20 (terminals) conforming to IEC 60529 Pollution degree 3 conforming to IEC 60664-1 Dielectric test voltage 2 kV AC 50 Hz, 1 min conforming to IEC 60664-1 2 kV AC 50 Hz, 1 min conforming to IEC 60255-5 Non-dissipating shock wave 4 kV conforming to IEC 61000-4-5 4 kV conforming to IEC 60664-1 4 kV conforming to IEC 60255-5 2