Product data sheet XPSAC3421P Characteristics module XPSAC - Emergency stop - 115 V AC Product availability: Stock - Normally stocked in distribution facility Main Range of product Preventa Safety automation Product or component Preventa safety module type Safety module name XPSAC Safety module applica- For emergency stop and switch monitoring tion Function of module Emergency stop Switch monitoring Safety level Can reach PL e/category 4 conforming to EN/ISO 13849-1 Can reach SILCL 3 conforming to EN/IEC 62061 Safety reliability data DC > 99 % conforming to EN/ISO 13849-1 MTTFd = 210.4 years conforming to EN/ISO 13849-1 PFHd = 3.56E-9 1/h conforming to EN/IEC 62061 Type of start Unmonitored Connections - terminals Captive screw clamp terminals, removable terminal block, clamping capacity: 2 x 0.5...2 x 1.5 mm flexi- ble cable with cable end, with double bezel Captive screw clamp terminals, removable terminal block, clamping capacity: 1 x 0.2...1 x 2.5 mm flexi- ble cable with cable end, with double bezel Captive screw clamp terminals, removable terminal block, clamping capacity: 1 x 0.2...1 x 2.5 mm solid cable with cable end, with double bezel Captive screw clamp terminals, removable terminal block, clamping capacity: 1 x 0.25...1 x 2.5 mm flexi- ble cable with cable end, with double bezel Captive screw clamp terminals, removable terminal block, clamping capacity: 2 x 0.2...2 x 1 mm solid cable with cable end, with double bezel Captive screw clamp terminals, removable terminal block, clamping capacity: 2 x 0.2...2 x 1.5 mm flexi- ble cable with cable end, with double bezel Captive screw clamp terminals, removable terminal block, clamping capacity: 2 x 0.25...2 x 1 mm flexi- ble cable with cable end, with double bezel Output type Relay instantaneous opening 3 NO, volt-free Number of additional 1 solid state output circuits Us rated supply volt- 115 V AC (- 15...15 %) age Complementary Supply frequency 50/60 Hz Power consumption in VA <= 7 VA AC Uc control circuit voltage 115 V Breaking capacity C300: 180 VA, AC-15 (holding) relay output C300: 1800 VA, AC-15 (inrush) relay output Breaking capacity 1.5 A at 24 V (DC-13) time constant: 50 ms for relay output Output thermal current 6 A per relay relay output Ith conventional free air thermal current 10.5 A Associated fuse rating 4 A fuse type gG or gL for relay output conforming to EN/IEC 60947-5-1, DIN VDE 0660 part 200 6 A fuse type fast blow for relay output conforming to EN/IEC 60947-5-1, DIN VDE 0660 part 200 Minimum output current 10 mA relay output Minimum output voltage 16 V for relay output Aug 11, 2019 1 The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.Response time on input open <= 100 ms Ui rated insulation voltage 300 V (degree of pollution: 2) conforming to DIN VDE 0110 part 1 300 V (degree of pollution: 2) conforming to IEC 60947-5-1 Uimp rated impulse withstand voltage 4 kV overvoltage category III conforming to IEC 60947-5-1 4 kV overvoltage category III conforming to DIN VDE 0110 part 1 Local signalling 2 LEDs Current consumption 60 mA at 115 V AC (on power supply) Mounting support 35 mm symmetrical DIN rail Product weight 0.46 lb(US) (0.21 kg) Environment Standards EN/IEC 60947-5-1 EN 60204-1 EN 1088/ISO 14119 EN/ISO 13850 Product certifications CSA TV UL IP degree of protection IP20 (terminals) conforming to EN/IEC 60529 IP40 (enclosure) conforming to EN/IEC 60529 Ambient air temperature for operation 14...131 F (-10...55 C) Ambient air temperature for storage -13...185 F (-25...85 C) Ordering and shipping details Category 22477 - SAFETY MODULES (PREVENTA) Discount Schedule SAF2 GTIN 00785901297536 Nbr. of units in pkg. 1 Package weight(Lbs) 0.54000000000000004 Returnability Y Country of origin ID Offer Sustainability California proposition 65 WARNING: This product can expose you to chemicals including: - - - - - - - Substance 1 Lead and lead compounds, which is known to the State of California to cause can- cer and birth defects or other reproductive harm. - - - - - - - More information For more information go to www.p65warnings.ca.gov Contractual warranty Warranty period 18 months 2