Product data sheet Specifications Estop or guard ,Harmony XPS, connected to supply terminals 24 V AC/DC , no inputs, screw XPSBAC14AP Product availability : Stock - Normally stocked in distribution facility Main Harmony Safety Automation Range of Product Product or Component Type Safety module Safety module name XPSBAC Safety module application For emergency stop and protective guard applications Function of module Emergency stop button with 2 NC contacts Guard monitoring with 1 or 2 limit switches Can reach PL e/category 4 for normally open relay contact ISO 13849-1 Safety level Can reach SILCL 3 for normally open relay contact IEC 62061 Can reach SIL 3 for normally open relay contact IEC 61508 Can reach PL c/category 1 for normally closed relay contact ISO 13849-1 Can reach SILCL 1 for normally closed relay contact IEC 62061 Can reach SIL 1 for normally closed relay contact IEC 61508 MTTFd > 30 years for normally open relay contact ISO 13849-1 Safety reliability data Dcavg >= 99 % for normally open relay contact ISO 13849-1 PFHd = 0.95E-09 for normally open relay contact ISO 13849-1 HFT = 1 for normally open relay contact IEC 62061 PFHd = 0.95E-09 for normally open relay contact IEC 62061 SFF > 99% for normally open relay contact IEC 62061 HFT = 1 for normally open relay contact IEC 61508-1 PFHd = 0.95E-09 for normally open relay contact IEC 61508-1 SFF > 99% for normally open relay contact IEC 61508-1 Type = B for normally open relay contact IEC 61508-1 MTTFd > 30 years for normally closed relay contact ISO 13849-1 DC > 60 % for normally closed relay contact ISO 13849-1 PFHd = 0.95E-09 for normally closed relay contact ISO 13849-1 HFT=0 for normally closed relay contact IEC 62061 PFHd = 0.95E-09 for normally closed relay contact IEC 62061 SFF > 60% for normally closed relay contact IEC 62061 HFT=0 for normally closed relay contact IEC 61508-1 PFHd = 0.95E-09 for normally closed relay contact IEC 61508-1 SFF > 60% for normally closed relay contact IEC 61508-1 Type = B for normally closed relay contact IEC 61508-1 NC pair Electrical circuit type Removable screw terminal block, 0.2...2.5 mm solid or flexible Connections - terminals Removable screw terminal block, 0.25...2.5 mm flexible with ferrule single conductor Removable screw terminal block, 0.2...1.5 mm solid or flexible twin conductor Removable screw terminal block, 2 x 0.25...1 mm flexible with ferrule without cable end, with bezel Removable screw terminal block, 2 x 0.5...1.5 mm flexible with ferrule with cable end, with bezel Us Rated Supply Voltage 24 V AC - 15...10 % 24 V DC - 20...20 % Complementary Unlimited Synchronisation time between inputs Automatic/manual/monitored Type of start 1.5W 24 V DC Power consumption in W Mar 8, 2022 1 Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applicationsPower consumption in VA 3.5VA 24 V AC 50/60 Hz Input protection type Internal, electronic Safety outputs 4 NO + 1 NC Safety inputs 0 Input compatibility Normally closed circuit ISO 14119 XC limit switch ISO 14119 Mechanical contact ISO 14119 Normally closed circuit ISO 13850 Power supply Input terminal 5A AC-1 Ie rated operational current 3A AC-15 5A DC-1 3A DC-13 3A AC-1 1A AC-15 3A DC-1 1A DC-13 0 Control outputs Ith conventional free air 6A thermal current 10A gG NO relay output circuit IEC 60947-1 Associated fuse rating 10mA relay output Minimum output current 5V relay output Minimum output voltage Response time 150 ms at 24 V AC 80 ms at 24 V DC 300V 2)EN/IEC 60947-1 Ui rated insulation voltage 4kV II EN/IEC 60947-1 Uimp rated impulse withstand voltage LED green power power ON Local signalling LED red error error LED yellow state status LED yellow start1 start input LED yellow start2 start input 35 mm symmetrical DIN rail Mounting Support 4.72in (120mm) Depth 3.94in (100mm) Height 0.89in (22.5mm) Width 0.44lb(US) (0.200kg) Net weight Environment -13131F (-2555C) Ambient Air Temperature for Operation Standards IEC 60947-5-1 IEC 61508-1 functional safety standard IEC 61508-2 functional safety standard IEC 61508-3 functional safety standard IEC 61508-4 functional safety standard IEC 61508-5 functional safety standard IEC 61508-6 functional safety standard IEC 61508-7 functional safety standard ISO 13849-1 functional safety standard IEC 62061 functional safety standard TV Product certications cULus IP20 terminals)EN/IEC 60529 IP degree of protection IP40 housing)EN/IEC 60529 IP54 mounting area)EN/IEC 60529 595% non-condensing Relative Humidity 2 Mar 8, 2022