Data sheet 6EP1332-5BA10 SITOP PSU100C 24 V/4 A SITOP PSU100C 24 V/4 A STABILIZED POWER SUPPLY INPUT: AC 120-230 V (DC 110-300 V) OUTPUT: DC 24 V/4 A Input Input 1-phase AC or DC Rated voltage value Vin rated 100...230V Voltage range AC 85...264V Input voltage 110...300V for DC Wide-range input Yes Overvoltage resistance 2.3 Vin rated, 1.3 ms Mains buffering at Iout rated, min. 20ms at Vin = 230 V Rated line frequency 50...60Hz Rated line range 47...63Hz Input current 2.25A at rated input voltage 100 V 1.15A at rated input voltage 230 V Switch-on current limiting (+25 C), max. 34A It, max. 3As Built-in incoming fuse internal Protection in the mains power input (IEC 898) Recommended miniature circuit breaker: from 16 A characteristic B or from 10 A characteristic C Output Output Controlled, isolated DC voltage Rated voltage Vout DC 24V Total tolerance, static 3% Residual ripple peak-peak, max. 200mV Residual ripple peak-peak, typ. 80mV 6EP1332-5BA10 Changes preserved 22.05.2015 Copyright Siemens AG Page 1/3Spikes peak-peak, max. (bandwidth: 20 MHz) 300mV Spikes peak-peak, typ. (bandwidth: 20 MHz) 80mV Adjustment range 22.2...26.4V Product function Output voltage adjustable Yes Output voltage setting via potentiometer Status display Green LED for output voltage OK On/off behavior Overshoot of Vout approx. 1 % Startup delay, max. 1.5s Voltage rise, typ. 400ms Rated current value Iout rated 4A Current range 0...4A +55 ... +70 C: Derating 3,5%/K Note Active power supplied typical 96W Parallel switching for enhanced performance Yes Start-up with single nominal load only Numbers of parallel switchable units for enhanced 2 performance Efficiency Efficiency at Vout rated, Iout rated, approx. 88% Power loss at Vout rated, Iout rated, approx. 13W Active power loss during no-load operation maximum 0.75W Closed-loop control Dynamic mains compensation (Vin rated 15 %), 0.1% max. Dynamic load smoothing (Iout: 10/90/10 %), Uout 3% typ. Load step setting time 10 to 90%, typ. 4ms Load step setting time 90 to 10%, typ. 4ms Protection and monitoring Output overvoltage protection Yes, according to EN 60950-1 Current limitation, typ. 4.8A Property of the output Short-circuit proof Yes Short-circuit protection Electronic shutdown, automatic restart Overload/short-circuit indicator - Safety Primary/secondary isolation Yes Galvanic isolation Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 Protection class Class I Leakage current 3.5mA maximum 0.4mA typical CE mark Yes 6EP1332-5BA10 Changes preserved 22.05.2015 Copyright Siemens AG Page 2/3