FieldServer Data Sheet BACnet Router FS-ROUTER-BAC Rev. 1.C Overview The FieldServer BACnet Router offers a complete BACnet Internetworking solution for BACnet/IP, BACnet Ethernet, and BACnet MS/TP networks. This is the first standalone BACnet Router that has been certified by BTL to ensure the highest standard for BACnet integration. The FieldServer BACnet Router is available in two models: The FS-ROUTER-BAC has two RS-485 ports enabling up to 64 BACnet MS/TP devices to be connected to it without the use of additional line drivers. Relative to a single port router, the dual port router halves device response time by distributing devices over the two RS-485 ports. The FS-ROUTER-BAC1 offers a single RS-485 port and is a cost-effective option for configurations of 32 or fewer BACnet MS/TP devices without the need for additional line drivers. The FieldServer BACnet Router has an easy one page configuration, greatly simplifying the installation process. DeviceFind, a unique discovery feature, allows the integrator to push a button and discover all the BACnet devices connected to the router, greatly simplifying the commissioning process. BACnet Router Features and Benefits Multiple BACnet Routing Connections BACnet/IP & BACnet MS/TP BACnet/IP & BACnet/IP BACnet MS/TP & BACnet Ethernet BACnet/IP & BACnet Ethernet BACnet MS/TP & BACnet MS/TP Ease of Use DeviceFind: a unique feature that discovers devices connected to the FieldServer BACnet Router. BACnet Broadcast Management Device (BBMD) for a connection between different subnets. Web Based configuration with no additional software needed for configuration. NAT support with secondary BACnet/IP connection for routing between public and private IP networks. Foreign Device Registration (FDR), exposing devices details on different subnets. SMC Cloud registration connects your devices to the cloud, allowing secure remote access for diagnostics, monitoring, alarming and configuration. On-board diagnostics allow easy troubleshooting for both serial and Ethernet communications. Ease of Installation MDIX to use any Ethernet cable for commissioning and installation. DHCP to automatically obtain the IP setting from the network. Software ToolBox to find and diagnose all FieldServer BACnet routers on the network. Wide range of input power requirements, AC or DC. www.sierramonitor.com FieldServer Data Sheet BACnet Router FS-ROUTER-BAC Rev. 1.C Specifications Communication Other Approvals Serial RS-485 Web Configuration CE & FCC Galvanic isolation Toolbox diagnostic utility TUV approved to UL 916, EN 60950-1, EN 50491-3 Baud: 9600, 19200, 38400, 57600, 76800, 115200 Table, Wall mount and CSA C22.2 standards Ethernet DIN rail mount included CSA C22.2 standards 10/100BaseT BTL Certification Rev. 12 MDIX Construction GOST-R Certified DHCP Dimensions: (HxWxD) RoHS Compliant 4.5 x 2.9 x 1.6 in. Environment (11.5 x 7.4 x 4.1 cm) 0 0 0 0 Operating temperature: -40 to 75 C (-40 to 167 F) Weight: 0.4 lbs (0.2 Kg) Relative humidity: 5-90% RH non-condensing Power Requirements 9-30VDC or 12-24VAC Current draw 12V: 240 mA *Specifications subject to change without notice Ordering Information The FieldServer BACnet Router is available in the following hardware configurations: FSROUTERBAC (2 Serial Ports) FSROUTERBAC1 (1 Serial Port) Options The Accessory Kit consists of a power supply, Ethernet cable, screwdriver, DIN rail mount, and a USB flash drive that includes all manuals, data sheets, notes and the discovery tool. FS-8915-36-QS Accessory Kit, 110/220V Sierra Monitor Corporation 1991 Tarob Court, Milpitas, California 95035 USA 11/17 O. +1 408 262-6611 TF. +1 800 72 SIERRA (74377) E. sales sierramonitor.com www.sierramonitor.com