Power Protection and Conditioning
1
MCR Hardwired Series Power Line Conditioning with Voltage Regulation
The MCR Hardwired Series provides excellent noise
Features
ltering and surge suppression to protect con nect ed
3% output voltage regulation
equip ment from damage, deg ra da tion or misoperation.
Noise attenuation
Combined with the ex cel lent voltage regulation inherent to
- 120 dB common mode
Sola/Hevi-Dutys patented ferroresonant design, the MCR
- 60 dB transverse mode
can in crease the actual Mean Time Before Failure (MTBF)
of pro tect ed equipment. The MCR is a perfect choice where
Surge suppression tested to ANSI/IEEE
dirty power, caused by impulses, swell, sags, brownouts and
C62.41 Class A & B Waveform:
waveform distortion can lead to costly downtime because of
- <10 V let through typical
damaged equip ment.
Acts as a step-up or step-down transformer
Harmonic ltering
Hardwired
Galvanic isolation provides exceptional
circuit pro tec tion.
25 year typical MTBF
No maintenance required
Applications
In dus tri al automation and control equip ment PLCs
Machine tools
Computer loads and electronic equipment
Robotics
Related Products
Semiconductor fabrication equipment
On-line UPS (S4K Industrial)
Surge Suppression
Three Phase Power Conditioners
Selection Tables: Single Phase
Group 2 MCR Series, 60 Hz Only
Height Width Depth Ship Weight Design Elec
VA Catalog Number Voltage Input Voltage Output
(inch) (inch) (inch) (lbs) Style Conn
120 120, 208, 240, 480 120 9 4 5 15 1 D
63-23-112-4
250 120, 208, 240, 480 120 10 6 8 27 1 D
63-23-125-4
500 120, 208, 240, 480 120, 208, 240 13 9 7 37 1 E
63-23-150-8
750 120, 208, 240, 480 120, 208, 240 14 9 7 52 1 E
63-23-175-8
1000* 120, 208, 240, 480 120, 208, 240 17 9 7 62 1 E
63-23-210-8
1500* 120, 208, 240, 480 120, 208, 240 17 13 9 95 1 E
63-23-215-8
2000* 120, 208, 240, 480 120, 208, 240 18 13 9 109 1 E
63-23-220-8
3000* 120, 208, 240, 480 120, 208, 240 19 13 9 142 1 E
63-23-230-8
5000* 120, 208, 240, 480 120, 208, 240 28 13 9 222 1 E
63-23-250-8
7500** 208, 240, 480 120, 208, 240 27 26 9 362 2 F
63-28-275-8
10000** 208, 240, 480 120, 208, 240 28 26 9 446 2 F
63-28-310-8
15000** 63-28-315-8 208, 240, 480 120, 208, 240 28 38 10 710 3 F
* Canadian option: cULus certied units must be ordered by changing -8 (UL only) to -C8.
** UL Listed Only. Use Group 3 for cULus.
Gross Automation (877) 268-3700 www.solahevidutysales.com sales@grossautomation.com
28
Gross Automation (877) 268-3700 www.solahevidutysales.com sales@grossautomation.comPower Protection and Conditioning
1
Selection Tables: Single Phase
Group 3 MCR Series, 60 Hz Only
Height Width Depth Ship weight Design Elec
VA Catalog Number Voltage Input Voltage Output
(inch) (inch) (inch) (lbs) Style Conn
500 600 120, 208, 240 13 9 7 38 1 B
63-31-150-8
1000 600 120, 208, 240 17 9 7 62 1 B
63-32-210-8
2000 600 120, 208, 240 18 13 10 109 1 B
63-32-220-8
3000 600 120, 208, 240 19 13 10 142 1 B
63-32-230-8
5000 208, 240, 480, 600 120, 208, 240 28 13 10 221 1 A
63-29-250-8
7500 208, 240, 480, 600 120, 208, 240 27 25 10 360 2 A
63-29-275-8
10000 208, 240, 480, 600 120, 208, 240 28 25 10 441 2 A
63-29-310-8
15000 208, 240, 480, 600 120, 208, 240 28 38 10 706 3 A
63-29-315-8
Group 4 MCR Series, 50 Hz Only (5% output voltage regulation)
Height Width Depth Ship weight Design Elec
VA Catalog Number Voltage Input Voltage Output
(inch) (inch) (inch) (lbs) Style Conn
120 110, 120, 220, 240, 380, 415 110, 120, 220, 240 9 6 8 24 1 C
63-23-612-8
250 110, 120, 220, 240, 380, 415 110, 120, 220, 240 11 6 8 27 1 C
63-23-625-8
500 110, 120, 220, 240, 380, 415 110, 120, 220, 240 13 9 7 40 1 C
63-23-650-8
1000 110, 120, 220, 240, 380, 415 110, 120, 220, 240 18 9 7 64 1 C
63-23-710-8
2000 110, 120, 220, 240, 380, 415 110, 120, 220, 240 18 13 10 113 1 C
63-23-720-8
3000 110, 120, 220, 240, 380, 415 110, 120, 220, 240 27 13 10 162 1 C
63-23-730-8
5000 110, 120, 220, 240, 380, 415 110, 120, 220, 240 30 13 10 266 1 C
63-23-750-8
7500 220, 240, 380, 415 110, 120, 220, 240 28 26 10 393 2 C1
63-28-775-8
10000 220, 240, 380, 415 110, 120, 220, 240 30 26 10 490 2 C2
63-28-810-8
15000 220, 240, 380, 415 110, 120, 220, 240 30 38 10 776 3 C2
63-28-815-8
Specifications
Parameter Condition Value
Input
Continuous at full load (lower input voltage possible at lighter load) +10% to -20% of nominal
Voltage
For temporary surge or sags +20% to -35% of nominal
1
at Full Load & 80% of nominal input voltage I (VA/.89)/(V x 80%)
Current
in in
See Operating Characteristics section for details. 50 Hz or 60 Hz depending on model
Frequency
Output
V >80% and <110% of nominal 5% for 50 Hz units, 3% for 60 Hz units
Line Regulation
in
At Nominal Input Voltage Current limited at 1.65 times rated current
Overload Protection
At full load within input range 3% total RMS content
Output Harmonic Distortion
-Common Mode 120 dB
Noise Attenuation
-Transverse Mode 60 dB
General
At Full Load Up to 92%
Efficiency
Storage Temperature Humidity <95% non-condensing -20 to +85C
Humidity <95% non-condensing -20 to 50C
Operating Temperature
Full Resistive Noise 35 dBA to 65 dBA
Audible Noise
60 Hz Models UL1012, CSA evaluated by UL
Approvals
50 Hz Models CE (EMC & LVD)
See General Information section for details 10 + 2 Years
Warranty
Notes:
1 - Consult user manual for fuse sizing.
Gross Automation (877) 268-3700 www.solahevidutysales.com sales@grossautomation.com
29