Uninterruptible Power Systems
2
S1K Mini-Tower Off-line UPS
The S1K series provides economical protection from
damaging impulses and power interruptions. These units
include two types of outlets; three for critical devices needing
battery back-up and surge protection such as the CPU and
one surge protected only outlet for non-critical devices like
printers and fax machines. The S1K is ideal for point of sale
and office applications.
Applications
PCs
Workstations
E179213
Computer Terminals
Certifications and Compliances
Features
Listed, UPS Equipment
Lightweight, compact design
- UL 1778, CSA C22.2 No. 107.3
4 NEMA 5-15R outlets, (3 Battery, 1 Surge)
Data-line surge protection for phone or network
included on every unit.
Related Products
DB9 communications Interface
Surge Protective Devices
Software and cable included
Active Tracking Filters
Step sinewave output
Portable MCR Power Conditioners
Two year limited warranty
Selection Table
Capacity Catalog Volts, Frequency Typical Back-up Time * Input Plug/ Approx. Ship Weight
(VA/W) Number In/Out (minutes) Output Receptacle lbs (kg)
320/240 10 8.8 (4.00)
S1K320
520/340 15 11.6 (5.30)
S1K520
5-15P / 5-15R
650/390 15 8.1 (3.70)
S1K650
(3) Battery (1) Surge
115 Vac, 50 or 60 Hz
850/600 25 10.8 (4.90)
S1K850
1200/720 30 10.8 (4.90)
S1K1200
1500/900 70 5-15P / 5-15R (4) Battery 30.0 (13.60)
S1K1500
* For a typical PC with a 15 monitor.
S1K Accessories
Catalog Number Description Approx. Ship Weight lbs (kg)
Wall/panel mount bracket kit for S1K (320VA~1200VA) UPS 1.0 (0.45)
S1K-PMBRK **
RS232 to USB Adapter Cable 1.0 (0.45)
UPSMON-USB
** Not applicable to S1K1500 and S1K650
Contact Technical Services at (800) 377-4384 with any questions.
66
Visit our website at www.solahd.com. Uninterruptible Power Systems
2
Specifications
Catalog Number S1K320 S1K520 S1K650 S1K850 S1K1200 S1K1500
320/240 520/340 650/390 850/600 1200/720 1440/900
Capacity (VA/Watts)
Dimensions - inches (mm)
5.30 x 3.80 x 12.60 5.30 x 3.80 x 12.60 7.50 x 5.11 x 15.00
5.30 x 3.80 x 12.6 5.30 x 3.80 x 10.40
Unit (H x W x D) -
(135.0 x 97.0 x (135.0 x 97.0 x (191.0 x 130.0 x
in. (mm) (135.0 x 97.0 x 320.0) (135.0 x 97.0 x 264.0)
320.0) 320.0) 381.0)
8.8 (4.00) 11.6 (5.30) 8.1 (3.70) 10.8 (4.90) 30.0 (13.60)
Weight - lbs (kg)
Input Parameters
115V + 20% / -25% 115V +/-15% 115V +/-25%
Voltage
50 or 60 Hz 10% (auto sensing)
Frequency
6 ft. with NEMA 5-15P
Input Power Cord
Output AC Parameters
Step sinewave at 115V
Voltage
(Battery Mode)
10% 5%
50 or 60 Hz
Frequency
(On Battery)
1 Hz 0.3 Hz 1 Hz
AVR automatically increases output
Auto Voltage
voltage 15% above input voltage if 91% AVR
Regulation
to 75% of nominal. AVR decrease output N/A (See first column
(AVR function
voltage 13% below input voltage if 109% to for definition)
under Normal
125% of nominal
Mode)
UPS automatic
shutdown if over-
UPS automatic shutdown if overload exceeds 105% of nominal at 20 seconds, load exceeds 110%
Overload
120% at 10 seconds, 130% at 3 seconds of nominal at
Protection
60 seconds, 130%
at 3 seconds
UPS output cut off immediately
Short Circuit
Battery Parameters
Sealed, maintenance-free lead acid batteries
Battery Type
4 milliseconds, Typical
Transfer Time
Back-up Time *
10-20 15-25 15-30 25-40 30-45 70-80
(minutes)
4 hours 6 hours
Recharge Time
Environmental
Operating
0C to 40C
Temperature
Storage
-15C to 50C
Temperature
0% to 90%, non-condensing
Relative Humidity
0-95% humidity non-condensing, 0-40C up to 10,000 ft. (3000m)
Ambient Operation
< 40dBA (1 meter from surface)
Audible Noise
Standards
FCC Part 15, Subpart B, Class A
EMC
Meets IEEE C62.41, Category A
Surge Protection
* For a typical PC with a 15 monitor.
Contact Technical Services at (800) 377-4384 with any questions.
67