FF 018 Filter Fan 14 - 69 cfm Very low noise Minimal mounting depth Functional design Time-saving installation Weather and UV resistant Filter fans are used to provide an optimum climate in enclosures. The interior temperature of an enclosure can be reduced by channeling cooler filtered outside air into the enclosure thus expelling heated internal air. The resulting air flow prevents formation of localized heat pock- ets and protects the electronic components from overheating. The plastic used for the hood of this filter fan series is highly weather resistant, as well as impact and UV light resistant. Technical Data Axial fan, ball bearing service life min. 50,000 h at 77 F (25 C) and 65 %RH aluminum fan body, plastic rotor Connection 2 wires w/cage clamps, AWG 14 (2.5 mm), length 4 (100 mm) Housing (filter fan and exhaust filter) Plastic, UL 94V-0, light grey Hood (filter fan and exhaust filter) Plastic, UL 94V-0, light grey weather and UV light resistant according to UL 746C (f1) Mounting frame with double-sided industrial adhesive for mounting to the outside of enclosure certain operating circumstances may make the additional use of screws necessary cut-out template included Filter media rating G4 acc. to DIN EN 779, filtering degree 94 % Filter material synthetic fiber with progressive construction, temperature resistant to 212 F, self-extinguishing class F1 moisture resistant to 100 %RH, reusable - can be cleaned by washing or vacuuming Operating / Storage temperature +14 to +158 F (-10 to +70 C) / -40 to +158 F (-40 to 70 C) Protection class I (grounded) Enclosure ventilation using a filter fan and exhaust filter Protection type IP55 (according to VDE), UL Type 1 Special features Note: Using fine filter mat F5 increases the protection to UL Type 12 but reduces the air flow The self-adhesive seal of the mounting frame prevents dust and water from entering the cabinet. Functional design of the intake and exhaust fan hoods very effectively prevents direct infiltration of falling water and dust. The advantage is that the filter mat does not rapidly become contaminated with dirt and therefore does not need to be exchanged as often. The air channeling makes the filter fan particularly quiet in operation. All filter fan models are also available with integrated airflow monitor. The direction of air flow can easily be switched by reversing the axial fan. EMC versions and other voltages are available upon request. Air volume Operating Power Average noise level Mounting Enclosure Weight Air volume, Part No. with Approvals free blowing voltage consumption (DIN EN ISO 4871) depth cut-out (approx.) exhaust filter 1) 01800.0-00 AC 230 V, 5 0Hz 12 cfm (21 m/h ) 9 cfm (16 m/h) 13 W 31 dB (A) 1.8 (45 mm) 3.8 x 3.8 1.3 lbs. (0.6 kg) UL File No. E234324, VDE 01800.0-01 AC 120 V, 60 Hz 14 cfm (24 m/h) 11 cfm (18 m/h) 13 W 31 dB (A) 1.8 (45 mm) 3.8 x 3.8 1.3 lbs. (0.6 kg) UL File No. E234324 1) 01801.0-00 AC 230 V, 5 0Hz 32 cfm (55 m/h) 25 cfm (42 m/h) 15 W 40 dB (A) 2.3 (58 mm) 4.9 x 4.9 2.2 lbs. (1.0 kg) UL File No. E234324, VDE 01801.0-01 AC 120 V, 60 Hz 37 cfm (63 m/h) 28 cfm (48 m/h) 15 W 40 dB (A) 2.3 (58 mm) 4.9 x 4.9 2.2 lbs. (1.0 kg) UL File No. E234324 1) 01802.0-00 AC 230 V, 5 0Hz 60 cfm (102 m/h) 40 cfm (68 m/h) 15 W 39 dB (A) 3.4 (86 mm) 6.9 x 6.9 2.9 lbs. (1.3 kg) UL File No. E234324, VDE 01802.0-01 AC 120 V, 60 Hz 69 cfm (117 m/h) 46 cfm (78 m/h) 15 W 39 dB (A) 3.4 (86 mm) 6.9 x 6.9 2.9 lbs. (1.3 kg) UL File No. E234324 1) air volume increases by 15% when operating AC 230 V filter fans at 60 Hz Specifications are subject to change without notice. Suitability of this product for its intended use and any associated risks must be determined by the end customer/ buyer in its final application. STEGO, Inc. 1395 South Marietta Parkway Building 800 Marietta, GA 30067 Tel: (770) 984-0858 Fax: (770) 984-0615 Toll free: 1-888-783-4611 (US & Canada only) www.stegousa.com FF018/11-12/US VentilatingFF 018 Filter Fan 14 - 69 cfm Time-saving assembly and maintenance STEGO s filter fans are easily installed by one person from outside the cabinet. 1.) Make cut-out in the cabinet wall. The cut edge of the cabinet opening should be free of dirt, filings and grease. A template for the enclosure cut-out is included with the filter fan. 2.) Remove protective film from the sealing strips on the mounting frame. Press mounting frame into the cabinet opening. The frame stays permanently in the cabinet. 3.) Electrically connect the axial fan using the cage clamp connectors. Push the unit into the mounting frame. Affix using screws if necessary. 4.) Insert the filter mat in the hood. Clip on. Finished. Installation sketch To change the filter mat, simply remove the filter hood, insert the new mat and snap the hood back again. No tools are required. Maintenance of the fan can easily be performed without removing the mounting frame (2). Dimensional Drawing 2.0 3.4 8.2 1.6 2.3 6.2 1.4 1.8 5.1 Drilling template for mounting frame 7.4 (188 mm) 5.4 (137 mm) 4.3 (109 mm) 1/8 (3mm) 1/8 (3mm) 1/8 (3mm) EF 118 Exhaust Filter Part No. Mounting depth Enclosure cut-out Weight (approx.) Filter mat Protection type Approvals 11800.0-00 0.6 (16 mm) 3.8 x 3.8 0.6 lbs. (0.3 kg) G4 acc. to DIN EN 779, filtering degree 94 % IP55* UL File No. E234324 11801.0-00 0.6 (16 mm) 4.9 x 4.9 0.8 lbs. (0.4 kg) G4 acc. to DIN EN 779, filtering degree 94 % IP55* UL File No. E234324 11802.0-00 0.6 (16 mm) 6.9 x 6.9 1.3 lbs. (0.6 kg) G4 acc. to DIN EN 779, filtering degree 94 % IP55* UL File No. E234324 *according to VDE FM 086 Filter Mats Filter mat 3.5 x 3.5 (89 x 89 mm) 4.6 x 4.6 (118 x 118 mm) 6.6 x 6.6 (168 x 168 mm) G4 (1 packing unit = 3 pcs.) Part No. 08600.0-00 Part No. 08601.0-00 Part No. 08602.0-00 F5 (1 packing unit = 3 pcs.) Part No. 08603.0-00 Part No. 08604.0-00 Part No. 08605.0-00 Specifications are subject to change without notice. Suitability of this product for its intended use and any associated risks must be determined by the end customer/ buyer in its final application. STEGO, Inc. 1395 South Marietta Parkway Building 800 Marietta, GA 30067 Tel: (770) 984-0858 Fax: (770) 984-0615 Toll free: 1-888-783-4611 (US & Canada only) www.stegousa.com FF018/11-12/US Ventilating 4.3 (109 mm) 3.8 5.3 5.4 (137 mm) 4.9 6.7 7.4 (188 mm) 6.9 8.9