DRB15-100 Series Specifications Model DRB15 DRB30 DRB50 DRB100 Input Input Voltage range Vac 85 - 264, 120 - 373Vdc (1) Input Surge Voltage - Withstands 300Vac for 5 seconds Input Frequency Hz 47 - 63 Input Current (110/230Vac) A 0.27 / 0.17 0.55 / 0.33 0.9 / 0.55 1.2 / 0.6 Inrush Current (Cold Start) A 35 40 50 40 Leakage Current (240Vac) mA <1.5 <1.5 <0.55 <1.5 Power Factor (110/230Vac) - 0.55 / 0.42 0.56 / 0.46 0.6 / 0.5 0.98 0.93 Harmonic Compliance - Meets EN61000-3-2 Class A No Load Power Consumption W <0.3 <0.3 <0.3 <0.5 Hold Up Time (230Vac input) ms >20 Efficiency - See model selector table Average Efficiency (230Vac) % 88 87 / 89 87 / 88 87 Conducted & Radiated EMI - EN55011-B, EN55032-B, VCCI-B, FCC-B Immunity - See immunity table Safety Agency Certifications - IEC/EN/CSA/UL62368-1, 60950-1, UL508 Listed, UL1310 Class 2 (see model selector), CE Mark, Class 1 Div 2, Group A, B, C, D (ISA 12.12.01) Immunity Test Standard Test Level Criteria ESD EN61000-4-2 4 A - Radiated Susceptibility EN61000-4-3 3 A - Electrical Fast Transient Burst EN61000-4-4 4 A - Surge EN61000-4-5 3 A - Conducted Susceptibility EN61000-4-6 3 A - Magnetic fields EN61000-4-8 4 A - 0% for 1 cycle A - Voltage dips 40% for 10/12 cycles B - EN61000-4-11 and input interruptions 70% for 25/30 cycles B - 80% for 250/300 cycles B - SEMI F47 Line Dip SEMI F47 - - > 200Vac input Output Temperature Derating Output Temperature Derating DRB15 DRB30, DRB50, DRB100 2 DRB15-100 Series