RWS1000/1500-B Series 1000W to 1500W Single Output General Purpose Power Supplies Features Cost E ective Wide Range AC Input 85 - 265VAC Enclosed Construction Compact Sizes SEMI F47 Line Dips 7 Year Warranty Key Market Segments & Applications Speci cations Model RWS1000B RWS1500B AC Input Voltage range (1) VAC 85 - 265VAC (47 - 63Hz) DC Input Voltage range* VDC 120 - 340VDC* Inrush Current (100 / 200VAC) A 60 / 60A Power Factor (100 / 200VAC) - Meets EN61000-3-2 (0.98 / 0.95) Input Current (100/200VAC) (Typ) A 13 / 7A 19 / 10A Temperature Coe cient %/C <0.02%/C Regulation - See Model Selector Overcurrent Protection - >105%, Constant Current Style. After 5s unit will shutdown Overvoltage Protection (2) V Shuts down output, cycle AC line or remote on/o to reset Hold Up Time (Typ at 100% load) ms 20ms Leakage Current (max) mA <1.2mA Standby Voltage (Vsb) - 5V 1A (always on). See options table (/S su x) Remote Sense - Yes Remote On/O - See options table. Apply external voltage or Vsb to enable output voltage DC Good, Fan Alarm - See options table Parallel Operation - See options table Series Operation - Yes o o Operating Temperature C -20 to +60 C, derate linearly to 60% load from 50 to 60 C o o Reverse air (/RF): -20 to +70 C, derate linearly to 50% load from 50 to 70 C Storage Temperature C -30 to +75C Operating Humidity (non condensing) %RH 20 - 90%RH Storage Humidity (non condensing) %RH 10 - 90%RH Cooling - Internal Fan, air intake from input/output terminals Withstand Voltage VAC Input to Ground 2kVAC, Input to Output 4kVAC, Output to Ground 1.5kVAC for 1 min. Isolation Resistance M >100M at 25C & 70%RH, Output to Ground 500VDC 2 Vibration (non operating) 10 - 55Hz: 19.6m/s (sweep 1 min) X, Y, Z for 1 hour 2 Shock - < 196.1 m/s Safety Agency Certi cations - IEC/UL/CSA/EN60950-1, IEC/UL/CSA/EN62368-1, CE Mark Line Dips - SEMI-F47 (200VAC input) Conducted & Radiated EMI - EN55011 / EN55032-B, FCC Class B, VCCI-B Immunity - IEC61000-4-2, -3, -4, -5, -6, -8, -11, IEC61000-6-2 Weight (Typ) g 2,000g 3,000g Size (WxHxD) mm 127 x 63 x 198mm 127 x 63 x 261mm In 5 x 2.48 x 7.8 5 x 2.48 x 10.28 MTBF - Telcordia SR-332 issue 3** hours 1,834,313 1,222,361 Warranty yrs Seven Years (1) Derate linearly to 80% load from 90 to 85VAC input *Safety certi ed for AC input only **24V output model, 25C ambient, full load, 230VAC input (2) See speci cations on website for individual limits. Note the remote on/o function is an option - see options table 1-800-526-2324 www.us.tdk-lambda.com/lp/ 44 Disclaimer: us.tdk-lambda.com/lp/legal.htmRWS1000/1500-B Series Output Ratings Adjust Range Max Current Max Output Load Reg Line Reg Ripple Noise E ciency (typ) % Model Voltage (V) (A) Power (w) (mV) (mV) (mV) 115/230VAC RWS1000B-12 12V 10.2-13.8V 84 1008 96 48 150 82 / 85 RWS1000B-12/S 12V 10.2-13.8V 84 1008 96 48 150 82 / 85 RWS1500B-12 12V 10.2-14.4V 125 1500 96 48 150 81 / 85 RWS1500B-12/S 12V 10.2-14.4V 125 1500 96 48 150 81 / 85 RWS1000B-15 15V 12.8-17.2V 67 1005 120 60 150 82 / 85 RWS1000B-15/S 15V 12.8-17.2V 67 1005 120 60 150 82 / 85 RWS1500B-15 15V 12.8-18.0V 100 1500 120 60 150 82 / 85 RWS1500B-15/S 15V 12.8-18.0V 100 1500 120 60 150 82 / 85 RWS1000B-24 24V 20.4-28.8V 42 1008 144 96 180 85 / 88 RWS1000B-24/S 24V 20.4-28.8V 42 1008 144 96 180 85 / 88 RWS1500B-24 24V 20.4-28.8V 63 1512 144 96 180 85 / 88 RWS1500B-24/S 24V 20.4-28.8V 63 1512 144 96 180 85 / 88 RWS1000B-36 36V 30.6-41.4 28 1008 216 144 250 85 / 88 RWS1000B-36/S 36V 30.6-41.4 28 1008 216 144 250 85 / 88 RWS1500B-36 36V 30.6-43.2 42 1512 216 144 250 85 / 88 RWS1500B-36/S 36V 30.6-43.2 42 1512 216 144 250 85 / 88 RWS1000B-48 48V 40.8-57.6 21 1008 288 192 300 85 / 88 RWS1000B-48/S 48V 40.8-57.6 21 1008 288 192 300 85 / 88 RWS1500B-48 48V 40.8-57.6 32 1536 288 192 300 85 / 88 RWS1500B-48/S 48V 40.8-57.6 32 1536 288 192 300 85 / 88 Outline Drawing RWS 1000B Outline Drawing RWS 1500B Options For Additional Information, please visit Su x Description us.tdk-lambda.com/lp/products/rwsb-series.htm /CO2 Double Sided Board Coating /FO Parallel Operation, DC Good and Fan Alarm Signals /R Remote On/O /RF Reverse Fan (Air exits over input/output terminals) /RFO Remote On/O , Parallel Operation, DC Good and Fan Alarm Signals /S Remote On/O , 5V 1A Standby Output 1-800-526-2324 www.us.tdk-lambda.com/lp/ 45 Revision B2: Jun 2019