DENSEI-LAMBDA SWS100 SPECIFICATIONS CA731-01-01A MODEL SWS100-3 SWS100-5 SWS100-12 SWS100-15 SWS100-24 ITEMS 1 Nominal Output Voltage V 3.3 5 12 15 24 2 Maximum Output Current A 20 20 8.5 6.7 4.3 3 Maximum Output Power W 66 100 102 100.5 103.2 4 Efficiency (Typ) (115/230VAC) ( * 1 ) % 69 / 70 75 / 77 79 / 81 81 / 83 82 / 84 85 ~ 265VAC (47-63Hz) or 120 ~ 370VDC 5 Input Voltage Range ( * 2 ) 0.9 / 0.5 1.2 / 0.6 6 Input Current (Typ) (115/230VAC) ( * 1 ) A 7 Inrush Current (Typ) ( * 3 ) 16A at 115VAC, 32A at 230VAC, Ta=25oC, Cold Start Built to meet EN61000-3-2 8 PFHC 0.99 / 0.95 9 Power Factor (Typ) (115/230VAC) ( * 1 ) 10 Output Voltage Range V 2.97~3.63 4.5~5.5 10.8~13.2 13.5~16.5 21.6~26.4 11 Ripple and Noise (115/230VAC) ( * 1, 4 ) mV 100 100 100 100 150 12 Line Regulation ( * 4, 5 ) mV 20 20 48 60 96 13 Load Regulation ( * 4, 6 ) mV 40 40 96 120 144 14 Temperature Coefficient Less than 0.02%/C 15 Over Current Protection ( * 7 ) A 21~ 21~ 8.9~ 7.0~ 4.5~ 16 Over Voltage Protection ( * 8 ) V 3.79~4.95 5.75~6.95 13.8~16.2 17.2~20.3 27.6~32.4 17 Hold-Up Time (Typ) (115/230VAC) ( * 1 ) 20ms 18 Leakage current ( * 9 ) 0.75mA Max, 0.25mA(Typ) at 115VAC / 0.5mA(Typ) at 230VAC 19 Series Operation Possible 20 Operating Temperature ( * 10 ) - 10 ~ + 60 C (Refer to Output Derating Curve) 21 Operating Humidity 30 ~ 90 %RH (No dewdrop) 22 Storage Temperature - 30 ~ +85C 23 Storage Humidity 10 ~ 95%RH (No dewdrop) 24 Cooling Convection cooling 25 Withstand Voltage Input - Output : 3.0kVAC (20mA), Input - FG : 2.0kVAC (20mA) Output - FG : 500VAC (100mA) for 1min. More than 100M at Ta=25C and 70%RH, Output - FG : 500VDC 26 Isolation Resistance 27 Vibration At no operating, 10 - 55Hz ( sweep for 1min ) 2 19.6m/s Constant, X, Y, Z 1hour each 28 Safety Approved by UL60950, CSA60950, EN60950, EN50178 29 EMI ( * 1 ) Built to meet FCC-Class B, EN55011/EN55022-B 30 Immunity ( * 1 ) Built to meet EN61000-4-2,-3,-4,-5,-6,-8,-11 31 Weight (Typ) g 600 32 Dimension mm 45 x 96 x 188 (Refer to Outline Drawing) * Read instruction manual carefully , before using the power supply unit. = NOTES= * 1 : At maximum output power, nominal input voltage, Ta = 25C. * 2 : For cases where conformance to various safety specs ( UL, CSA, EN ) are required, to be described as 100 - 240VAC, 50 / 60Hz on name plate. * 3 : Not applicable for the in-rush current to Noise Filter for less than 0.2ms. * 4 : Please refer to Fig A for measurement of line & load regulation, ripple and noise voltage. Ripple & noise are measured at 20MHz by using a 12 twisted pair terminated with a 0.1uF and 47uF capacitor. * 5 : 85 - 265VAC, constant load. * 6 : No load - Full load(Maximum power), constant input voltage. Fig. A +V * 7 : Constant current limit with automatic recovery. A Avoid to operate at overload or dead short for more than 30seconds. TB1 * 8 : OVP circuit will shutdown output, manual reset (Re power on). -V * 9 : Measured by each measuring method of UL, CSA, EN. *10: Refer to Output Derating Curve (next page) for details of output derating versus ambient temperature and mounting method . Measurement point for Vo Line/Load Regulation, and ripple and noise.DENSEI-LAMBDA SWS100 OUTPUT DERATING CA731-01-02A SWS100-3,5,12,15,24 OUTPUT DERATING VS Ta CURVE (CONVECTION COOLING) 100 80 MOUNTING A 60 MOUNTING B,C 40 20 0 -10 0 1020 304050 60 Ta(C) Force Air Cooling : Recommended minimum air velocity is 1.2m/s, flow through the component side of power suppl SWS100-3,5,12,15,24 OUTPUT DERATING VS Ta CURVE (FORCE AIR COOLING) 100 80 60 MOUNTING A,B,C 40 20 0 -10 0 10 203040506070 Ta(C) MOUNTING A MOUNTING B MOUNTING C DON T USE DON T USE (STANDARD MOUNTING) LOAD(%) LOAD(%)