EMC filters
3-line filters
Sine-wave output filters
300/520 V AC, 4 A ... 390 A, 40 C
Series/Type: B84143V*R/S229
Date: April 2018
EPCOS AG 2018. Reproduction, publication and dissemination of this publication, enclosures hereto and the
information contained therein without EPCOS' prior express consent is prohibited.
EPCOS AG is a TDK Group Company.Line reactors, output chokes and output filters B84143V*R/S229
Sine-wave output filters for 3-phase systems
Sine-wave output filters for 3-phase systems
Rated voltage V : 300/520 V AC
R
Rated current I : 4 A to 390 A
R
Construction
3-line filters
Features
Reduction of motor noise and eddy current losses
Generation of sinusoidal phase-to-phase voltage with low
ripple
dv/dt reduction
Easy to install
1)
Degree of protection: IP00
Optional housing for degree of protection IP21 can be
ordered separately with ordering code B84143Q*R229
Optimized for long motor cables and operation under full
2)
load
Natural cooling
Wiring between inverter and filter must be shorter than
10 meters!
Designed with reference to IEC 60939 und UL1283
UL approved insulation system
(system designation: T-EIS-CF1)
Typical applications
Frequency converters for motor drives, e.g.
elevators
pumps
conveyer systems
HVAC systems (heating, ventilation and air conditioning)
Terminals
Up to 95 A: Finger-safe terminal blocks
162 A ... 390 A: Copper busbars
Marking
Marking on component:
Manufacturers logo, ordering code, rated voltage, rated
current, rated motor frequency, rated switch frequency, rated
temperature, climatic category, date code
Minimum data on packaging:
Manufacturer's logo, ordering code, quantity, date code
1) According to IEC 60529
2) The maximum permissible motor cable length depends on the application and must be checked.
Please read Cautions and warnings and Page 2 of 24
Important notes at the end of this document.