Phase Failure Relays
WILMAR Protective Relays 1000 Series Function:
47
ANSI/IEEE C37.90-1978
UL file No. E58048
CSA file No. LR61158
TERMINAL STRIPS
#6 - 32 SCREWS
Phase failure relays protect motors, equipment and
personnel from damage or injury caused by open
phase, reversed phase sequence, or low voltage in a
three phase system. Models are available for 50 and
60 Hz with voltages up to 575 volts. Motor control
switchboards are a common application.
Operation:
The contacts of the relay will close only when it
senses normal conditions of three phase power at
the proper phase sequence.
The relay contacts will remain in their normally open
position (de-energized) when voltage with incorrect
phase sequence is applied, one or more phases are
open, or at undervoltage condition.
PART NUMBER SELECTION
Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.
PART NUMBER SELECTION
Sample Part No. 1004X
Type:
1001 = 120 V, 60 Hz, 3 phase,L-L
1007 = 208 V, 60 Hz, 3 phase, L-L
1002 = 230 V, 60 Hz, 3 phase,L-L
PRODUCT SPECIFICATIONS
1012 = 300 V, 60 Hz, 3 phase, L-L
Part Number 1000 Series
1013 = 350 V, 60 Hz, 3 phase, L-L
Nominal Voltage .............................
See Table
1003 = 380 V, 50 Hz, 3 phase, L-L
1004 = 460 V, 60 Hz, 3 phase,L-L
Voltage Drop-Out ...........................
75% to 100% of nominal, screwdriver adjustable
1005 = 525 V, 60 Hz, 3 phase,L-L
Pick-Up to Drop-Out Differential .... 3% approx.
1006 = 575 V, 60 Hz, 3 Phase, L-L
o o
Mounting:
Ambient Operating Temperature ....
-40 C to +70 C
X = Flange
Temperature Drift ........................... 1%
Blank - Stud
Time Delay ..................................... See Curve
Consult factory for additional models and options
Output Contacts .............................
One set, normally open
Contact Ratings ..............................
10 amp at 28 VDC resistive
Notes:
10 amp at 230 VAC resistive 1. Remove screw for access to the undervoltage
adjustment.
2. Clockwise rotation of the adjustment
potentiometer will raise the drop-out voltage.
30 Tyco Electronics / www.tycoelectronics.com / Factory Direct Technical Support: 800-253-4560, ext. 2023 (U.S., Canada, Mexico) or 805-220-2020, ext. 2023 (International)
13
3 /16
3
2 /4
1
3 /2